Page 1: ...MTG765 UT wireless HMI User manual Wuxi XINJE Electric Co Ltd File no HC12 20161207 2 D ...

Page 2: ... 1 3 PARTS 5 1 3 1 Structure 5 1 4 DIMENSIONS 8 1 4 1 Dimensions 8 1 4 2 Using environment 8 1 5 PROGRAMMING SOFTWARE 9 2 MTG765 UT APPLICATION 10 2 1 ONE MASTER ONE SLAVE COMMUNICATION 10 2 2 ONE MASTER MULTI SLAVE APPLICATIONS 13 2 2 1 Connection 14 2 1 2 Parameter setting 14 ...

Page 3: ...stic effects Rich picture library screen running without stuck Control Digital control dynamic data display and monitor bar chart real time historic graph time trend graph XY trend graph XY line chart discrete continuous data bar chart real time alarm historic alarm records etc User defined data collection and storage User authority setting 9 levels of password protection Import the program throug...

Page 4: ...ications Item MTG765 UT Electric Power 4W Charging input parameter 5 0V 2 0A 9 0V 2 0A 12V 1 5A Battery life always ON 8 hours Charging time 10 hours Ambient Operation temperature 0 45 Ambient humidity 10 RH 90 RH no condensation Air No corrosive gas Protection The front cover is accord to IP65 Cooling mode Natural cooling Structure Dimension mm 217 1 158 0 36 6 Interface PLC port built in Built i...

Page 5: ...unction Channel button Select the wireless communication channel Wireless communication baud rate Set the wireless communication baud rate DIP switch Set the forced download mode and screen adjustment 0 1 2 3 4 5 6 7 8 9 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 Wireless communication baud rate Channel button DIP switch USB B port USB A port Micro USB Power Label ...

Page 6: ... communication delay and tranferring distance Please refer to the following table for details For the reasons of obstacles blocking or shielding the transferring distance maybe different from the table please confirm it according to the actual conditions Testing location DIP1 DIP2 Transferring speed bps Communication distance meter Notes Building ON ON 4800 40 60 At least 3 walls ON OFF 9600 20 45...

Page 7: ...d the program 3 Turn off the switch 2 repower on the HMI 4 USB B port MTG765 UT has one USB B port USB2 0 which is located at the back left side of the cover It can download and upload program The transferring speed is 480Mbps USB B port pin definition 1 Please use shielding USB cable 2 please install the USB driver 3 connect the PC and HMI via USB cable click or to download program 1 2 3 4 ON OFF...

Page 8: ...interface to charge the wireless HMI Input parameters 5 0V 2 0A 9 0V 2 0A 12V 1 5A 7 Power Please touch and hold the power button to startup or shut down the MTG765 UT HMI 1 4 Dimensions 1 4 1 Dimensions MTG765 UT Unit mm 1 4 2 Using environment MTG765 UT is often used indoor 217 1 158 0 36 6 Pin Definition Notes 1 5V 5V voltage signal 2 DATA Data signal 3 DATA Data signal 4 5V 5V ground signal ...

Page 9: ...e will condense inside the HMI 1 5 Programming software MTG765 UT is fit for the programming software Toucwhin v2 d 3k and up version The details please refer to Touchwin software manual Note The communication device in the software only can be PLC port device and the device model must be XINJE XC or XD series PLC or Modbus RTU device The communication parameters must be 19200bps 8 data bit 1 stop...

Page 10: ...e 19200bps 8 data bits 1 stop bit even parity the parameters cannot be changed 2 S BOX can be equipped with mobile antenna to enhance the wireless communication ability 2 1 One master one slave communication This application will make the wireless communication between MTG765 UT and XC3 series PLC The devices in the network MTG765 UT S BOX T XC3 32T E DVP cable 2 1 1 Connection S BOX T needs to co...

Page 11: ...PLC serial port 1 settings ...

Page 12: ...MTG765 UT PLC port settings 2 Set the same transferring speed for the devices in the network Set the speed to 115200bps set off all the DIP switch at the back of MTG765 UT and S BOX T ...

Page 13: ...rn the channel button to 0 for all the devices MTG765 UT S BOX T 4 The networking is completed Edit the HMI program and download 2 2 One master multi slave applications Application MTG765 UT monitors two XD3 series PLC through left expansion board S BOX T ED The devices in the network 1 MTG765 UT 2 S BOX T ED 2 XD3 16R ...

Page 14: ...ements when the MTG765 UT wireless monitors the XD3 series PLC through S BOX T ED same wireless communication channel same wireless baud rate same communication parameters of MTG765 UT PLC port and PLC port 3 and must be 19200bps 8 1 E which cannot be changed 1 Set the PLC serial port parameters to 19200 8 1 E The station no of the two PLC is 1 and 2 PLC station no 1 settings ...

Page 15: ...PLC station no 2 settings MTG765 UT PLC port settings 2 Set the same transferring speed for the devices Set the speed to 115200bps set off all the DIP switch at the back of MTG765 UT and S BOX T ED ...

Page 16: ...devices We select channel 0 for MTG765 UT and S BOX T ED Turn the channel button to 0 for all the devices MTG765 UT S BOX T ED 4 The networking is completed Edit the HMI program and download in the HMI The object station no in the HMI program is the PLC station no ...