Installation Leaflet

 

 

 

 

Feb 2019 - Rev G 

SPECIFICATION 

 

FURTHER INFORMATION

 

In common with all IP66 rated fittings the ACL 
Industry luminaire is protected against ingress of 
dust and water projected from a nozzle. However 
care must be taken in the siting of these 
luminaires. They can be mounted outdoors under 
a canopy or covered environment but should not 
be in direct sunlight or open areas exposed to 
adverse weather conditions. In particular they 
should not be installed in an environment liable to 
produce standing water on the fitting or IP glands.  

Lamp type: 

LED 4000°K 

Control Gear: 

Fixed Output  / DALI 

Body Material: 

Light Grey PC 

Diffuser 
material: 

Opal High Impact PC with 
internal prisms 

Supply: 

220-240V AC, 50Hz 

Operating 
temp: 

Standard -20°C to 25°C 

Emergency -5°C to 25°C 

Conductor: 

2.5mm

2

 max 

Rating: 

IP66 / IK08 

Weight: 
1283mm 
1578mm 

 
Std 2.75 kg Em. 3.25 kg 
Std 3.4 kg Em. 3.9 kg 

GENERAL INFORMATION 

1.  A qualified electrician, in 

accordance with IEE wiring 
regulations, should carry out 
connection to mains wiring. 

2.  Ensure mains power is 

turned off during 
maintenance. 

3.  Ensure that the rated voltage 

and frequency requirements 
are compatible with the 
available mains supply. 

4.  This unit must be 

EARTHED. 

5.  Cleaning of reflectors and 

lenses should be carried out 
using clean, soft and lint free 
cloths and anti-static 
cleaning fluid. 

6.  Do not carry out high voltage 

insulation test, i.e. 
500/1000v this may damage     
internal components. 

7. 

Replacing the light source 
within this luminaire shall 
only be carried out by the 
manufacturer, 
service agent or a 
similar qualified 
person.

 

 

PLEASE NOTE: In 
freezer applications 
product must be 
mounted a minimum 
of 1M from any 
ventilation including 
the freezer door. 

All measurements in 
mm unless stated 
otherwise, see website 
for product codes and 
lumen outputs

 

Variant  Length  Cable Entry 

Points 

Mount Bracket 
Centres 

Surface Mount 
Centres 

0.6m 

663 

530 

390 

266 

1.2m 

1283 

1050/1170 

800 

676 

1.5m 

1578 

1345/1170 

1100 

976 