background image

Copyright 2005 Wheelock, Inc.  All rights reserved. 

 

 

 

 

 

 

 

  

P84234H 

Sheet 1 of 4 

 

 

 

273 Branchport Avenue 
Long 

Branch, 

NJ 

 

07740 

         

 

 

Thank you for using our products.

 

(800)  631-2148 (USA) 

 

(800) 

 

397-5777 

(CANADA) 

       

  INSTALLATION INSTRUCTIONS

 

www.wheelockinc.com 

 

         

 

 

SERIES NS TWO WIRE APPLIANCES 

(WALL MOUNT VERSIONS)

 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL: 

Wheelock’s Series NS Horn Strobe Appliances require only 2-wires for operation of the horn and strobe appliance and provide a selectable continuous or Code 3 Horn 
tone and continuous strobe when connected directly to a fire alarm control panel (FACP).  They can also provide a synchronized Code 3 Horn tone and synchronized 
strobe when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock power supplies.  They are the ideal choice for applications where 
the audible silence feature is required.  The NS Appliances are UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired and UL Standard 464 for 
Audible Signal Appliances. The 24V NS is also ULC Listed under Standard CAN/ULC-S526-02 for Visual Signaling Appliances and Standard CAN/ULC-S525-99 for 
Audible Signaling Appliances for Fire Alarm Systems.  The 1575W candela wall mounted strobes are listed at 15 candela under UL Standard 1971 and meet 75 candela 
intensity on axis with low current draw.  They are listed for 

indoor use only

 and equipped with a NS nounting plate (NSMP) that can be mounted to single-gang, 

double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox (See wiring and mounting information).  These strobe models are Listed for 

wall 

mounting only

.  The NS appliances uses a xenon flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability for 

effective visible signaling. 

 

Series NS Appliances can be field set for high (HI) or low (LO) dBA sound output. 

 

These strobe models are designed for use with either filtered DC (VDC) or unfiltered full-wave-rectified (FWR) input voltage.  All inputs are polarized for compatibility 
with standard reverse polarity supervision of circuit wiring by a FACP. 

 

NOTE:

  The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is specified by ANSI and 

NFPA 72 for standard emergency evacuation signaling.  

The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose. 

 

NOTE

:  All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems - CAN/ULC-S524-01 and Canadian 

Electrical Code, Part 1.  Final acceptance is subject to authorities having jurisdiction (AHJ). 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.  FAILURE TO COMPLY WITH ANY OF 

THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS 
INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

SPECIFICATIONS: 

 

Table 1:  UL and ULC Ratings

 

Strobe Candela 

(cd) 

 

Models 

Regulated 

Voltage 

(VDC/VRMS) 

Voltage Range Limit Per 

UL 464 and UL 1971 

(VDC/VRMS) 

Voltage Range Per CAN/ULC-S526-02 

And CAN/ULC-S525-99 

(VDC/VRMS) 

UL ULC 

NS-241575W* 24 

16.0-33.0 

20.0-31.0 

15 75 

NS-121575W* 12 

8.0-17.5 ------ 

15 

-- 

 

*  1575W models are UL Listed for 15cd and meet 75cd on axis.  NS-121575 is not ULC approved. 

 

Table 2:  dBA Sound Output for 24VDC Per UL and ULC 

Description 

Volume 

Reverberant Per UL 464 

Anechoic Per CAN/ULC-S525-99 

  

16.0VDC 

24.0VDC 

33.0VDC 

20.0VDC 

24.0VDC 

31.0VDC 

 Low 

77 

81 

83 

87 

89 

91 

Continuous Horn 

High 

83 

87 

90 

90 

92 

94 

 Low 

72 

76 

79 

87 

89 

91 

Code 3 Horn 

High 

79 

82 

86 

90 

92 

94 

ULC Directional Characteristics:  Rated output 92dBA (Unit set on high volume and 24VDC) 
-3dBA:  60 degrees left, 40 degrees right                       -6dBA:  70 degrees left, 70 degrees right

 

 
 
 

Table 2A:  dBA Sound Output for 12VDC Per UL 

Description 

Volume 

Reverberant Per UL 464 

  

8.0VDC 

12.0VDC 

17.5VDC 

 Low 

72 

76 80 

Continuous Horn 

High 

78 

83 

86 

 Low 

67 

72 74 

Code 3 Horn 

High 

75 

79 

82 

 

1.

 

Strobes will produce 1 flash per second over the "Regulated Voltage" range. 

2.

 

Anechoic dBA is measured on axis in a non-reflective (free field) test room using fast meter response.  For peak dBA (measured with peak meter response), add 
5dBA to anechoic values as shown in Table 2 &2A.  Reverberant dBA is a minimum UL rating based on sound pressure measurements in a reverberant test room. 

3.

 

All models are UL Listed for indoor use with a temperature range of +32

°

F to +120

°

F (0

°

C to +49

°

C) and maximum humidity of 93% 

±

 2% RH.  The effect of 

shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and not subjected to misuse or 
abuse.   

Reviews: