background image

P83963 E 

Sheet 1 of 5  

 

273 Branchport Avenue 
Long Branch, N.J.  07740 
(800) 

 

631-2148 

US           

 

Thank you for using our products.

 

(800) 

 

397-5777 

– 

Canada         

 

INSTALLATION INSTRUCTIONS

 

www.wheelockinc.com

                  

    

 

MIZ-MINI 

HORNS

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL

Electronic MIZ-Mini Horns are designed to produce high sound output with minimal current requirements.   They are UL Listed under 
UL 464, Standard for Audible Signal Appliances and ULC Listed under Standard CAN/ULC-S525-99, Standard for Audible Signal 
Appliances For Fire Alarm Systems

.

 All inputs are polarized for compatibility with standard reverse polarity supervision of circuit 

wiring by a Fire Alarm Control Panel (FACP).  MIZ-Mini Horns are recommended for alarm signaling for individual rooms in 
apartments, motels, hotels and offices.  These appliances are attractive in appearance and reliable performers.  They mount to standard 
backboxes to reduce the cost of installation.  All models are Listed for indoor use with the backboxes specified in these instructions 
(See Mounting Options). 

 

They provide a selectable Continuous or Code 3 horn tone when connected directly to a Fire Alarm Control Panel (FACP).  They can 
also provide a synchronized Code 3 horn tone when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or 
Wheelock’s Power Supplies. 

 

NOTE

:  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol  .  All warnings are printed in bold capital letters. 

 

WARNING:  READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

WARNING:  THE MIZ APPLIANCE IS A “FIRE ALARM DEVICE – DO NOT PAINT.” 

 

SPECIFICATIONS: 

 

Table 1:  UL and ULC Listed Models and Ranges 

Reverberant dBA Per 

UL 464 at 10 Feet 

Anechoic dBA Per 

CAN/ULC-S525-99 at 10 Feet 

 

Current 

Continuous 

Code 3 

Continuous 

Code 3 

 

Models 

 

Voltage 

DC RMS  dBA  dBA 

dBA 

dBA 

 

Mounting 

Options 

  8.0 

.011 

.017 

74.8* 

70.3* 

79.8** 

79.7** 

12.0 .016 .025  77.9  73.8*  83.3**  82.9** 

 

MIZ-TC12 

17.5 .023 .035  80.9  76.8 

86.9 

86.7 

 

A,B 

16.0 .012 .027  79.7  75.5 

84.8**  84.7** 

24.0 .017 .038  83.2  78.8 

87.9 

87.9 

 

MIZ-TC24 

33.0 .024 .043  85.8  81.3 

90.6 

89.7 

 

A,B 

 

WARNING:  OPERATING THE SERIES MIZ-TC12 UL VERSION, AT MINIMUM VOLTAGE (8.0VDC TO 12.0VDC) WILL NOT 

MEET THE 75dBA MINIMUM UL REVERBERANT SOUND LEVEL REQUIRED FOR PUBLIC MODE FIRE PROTECTION 
SERVICE (NOTED BY * IN TABLE 1). THIS IS ACCEPTABLE ONLY FOR GENERAL SIGNALING (NON-FIRE ALARM) USE. 

 

WARNING:  OPERATING THE MIZ-TC12 AND MIZ-TC24 AT MINIMUM VOLTAGE (8.0VDC TO 12.0VDC FOR 12 VOLT 

MODEL AND 16.0 FOR 24.0VDC MODEL) WILL NOT MEET THE 85dBA MINIMUM ULC ANECHOIC SOUND LEVEL REQUIRED 
FOR FIRE PROTECTION SERVICE (NOTED BY ** IN TABLE 1).   THIS IS ACCEPTABLE ONLY FOR GENERAL SIGNALING 
(NON-FIRE ALARM) USE. 

 

WARNING:  FOR UL APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 

16.0-33.0 VOLTS FOR 24.0VDC MODELS AND 8.0-17.5 VOLTS FOR 12.0VDC MODELS USING FILTERED (DC) OR UNFILTERED 
FULL-WAVE-RECTIFIED (FWR).  DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION. 

 

WARNING:  FOR ULC APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 

20.0-31.0 VOLTS FOR 24VDC MODELS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR).  APPLY 80% 
AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION. 

 

NOTE

: 1. Anechoic dBA is measured in anechoic chamber with fast meter response.  2. Reverberant dBA is rated per  UL 464, 

Standard  for Audible Signal Appliances.  3. As per ULC requirement, the -3dB off-axis is 15

°

 and the -6dB off-axis is 30

°

 

Copyright 2003 Wheelock, Inc.  All rights reserved. 