Installation and Operating Manual 

 

Battery Protector 100 

Switching Capacity 12 V - 24 V / 100 Amperes

  

No.  3078 

 

 

Please read the Safety Regulations, mounting instructions and operating manual completely prior  

to starting connection and start-up. 

 

 

Fully automatic battery protection for intervention vehicles, high-quality campers and the marine field. 

The battery protector 100 is connected between supply battery and consumer loads. It protects the battery from dangerous 

deep discharge and the consumer loads from low voltage as well as from overvoltage. 
Note: The values being indicated in parentheses ( ) apply to 24 V operation. 

 

 

Functions: 

 

The unit protects the battery from dangerous deep discharge.

 

 

Maximum admissible current 100 A; thus, it is also suitable for high-capacity consumer loads.

 

 

Suitable for any type and brand of lead batteries (Acid, Gel, Dryfit, Heavy Duty, Solar, fleece, AGM etc.). The automatic 

switching threshold ensures an additional protection against latent consumer loads. 

 

Suitable for lithium batteries LiFePO4. 

 

Disconnection of the consumer loads for protection against dangerous overvoltage.

 

 

The disconnection can be cancelled manually by means of the 

"EMERGENCY-ON"

 function.

 

 

It can also be used as efficient, remote-controlled main-switch with battery control.

 

 

Full remote control with external single-pole remote switch is possible. 

 

Preliminary alarm as soon as the switch-off level is reached. 

 

Visual indication of the operating state. 

 

Audible indication in case of preliminary alarm and disconnection (can be deactivated, optionally). 

 

Output for external alarm indication (max. 0.2 A short circuit-proof). 

 

Input for separate sensor line for unfalsified measurement of the battery voltage. 

 

Immediate emergency shut-down in case of defective battery or extremely discharged battery. 

 

Least own electricity consumption during operation (acc. to EN13976).  

 

No own electricity consumption in case of disconnection by external remote switch. 

 

 

Installation: 

1.

 

Choose an installation place being clean and being protected from humidity and dust. 

2.

 

The installation place of the unit should be chosen in such a way, that the cables of battery and consumer loads can 

be as short as possible (losses) to ensure that the push-button "EMERGENCY" is easily accessible. 

3.

 

Fasten the unit securely with screws at the casing flanges. The unit can be installed in any position.   

4.

 

In case of great distance to the battery, we recommend to connect a separate sensor cable.  

5.

 

The cable lugs of the connection cables for battery and load should be connected solidly to the terminal lugs 

"Battery" and "Load" by means of the delivered screws M6. Recommended tightening torque approx. 

6-7 Nm

.

 

The enclosed insulation protection angle must be installed as short-circuit protection for this area. 

6.

 

Observe to fasten the connection cables in such a way, that neither high tensible force, nor high force of pressure is 

acting on the terminal lugs. 

 

 

Содержание Battery Protector 100

Страница 1: ...ry alarm as soon as the switch off level is reached Visual indication of the operating state Audible indication in case of preliminary alarm and disconnection can be deactivated optionally Output for external alarm indication max 0 2 A short circuit proof Input for separate sensor line for unfalsified measurement of the battery voltage Immediate emergency shut down in case of defective battery or ...

Страница 2: ... controller generator charging converter etc are connected directly to the battery to ensure battery charging even with switched off battery protector Powerful inverters with own low voltage disconnection are also connected directly to the battery Option Operation with Sensor Line Sensor Selector Switch 6 Sens Set Batt to position ON Particularly in case of powerful consumer loads being equipped w...

Страница 3: ...he preliminary alarm will be reset If a low voltage disconnection had been released for all that restart can be effected Automatically according to the connection voltage rates which are listed in the table charging mode or Manually at any time by means of the key EMERGENCY ON OFF or remote switch OFF and again ON Key EMERGENCY ON OFF The laterally installed key allows the following functions 1 Ma...

Страница 4: ...delay times or automatic switching threshold 3 2 1 Disconnection Voltage 24 V Connection Voltage 21 2 V 40 s 24 8 V 1 s x 23 0 V 40 s 25 0 V 1 s x 23 6 V 40 s 25 6 V 1 s x x Automatic 25 0 V 2 s 3 2 1 Disconnection Voltage 12 V Connection Voltage x 10 6 V 40 s 12 4 V 1 s x x 11 5 V 40 s 12 5 V 1 s x x 11 8 V 40 s 12 8 V 1 s x x x Automatic 12 5 V 2 s The unit can extend the lifetime of Lithium LiF...

Страница 5: ...rs for the correct disconnection voltage and the time If a battery is permanently discharged with only small current rates disconnection must be effected in case of higher voltage levels By this method the cells are protected from degenerative changes and lasting damages at the electrodes The disconnection will be effected at 12 2 V in 4 weeks Consumer loads with large current draw will cause a qu...

Страница 6: ...rs are protected by disconnection of the supply voltage at 15 5 V 31 5 V Reconnection is effected 20 seconds after a drop below this voltage level If such high voltage levels will be reached repeatedly the charging controller the battery the charger and the battery terminals should be checked Lifetime of the battery The battery protector 100 can extend the lifetime of the battery considerably The ...

Страница 7: ...of gas or dust explosion exists Observe the safety regulations Open air operation of the unit is not allowed Cables are always to be laid in such a way that damage is excluded Observe to fasten them tightly Never lay 12V 24cables and 230 V mains supply cables into the same cable conduit empty conduit Check live cables or leads periodically for insulation faults points of break or loosened connecti...

Страница 8: ...ing PNP maximum 0 2 A Internal fuse 1 A self resetting after disconnection of the consumer Output Voltage During Alarm active 12 V 24 V Voltage at terminal Battery minus approx 0 3 V Output Voltage without Alarm not active 0 V Fitting Position of Unit any Working Temperature Range 20 45 C Protection Class IP21 Dimensions mm 105 x 77 x 38 mm Weight 180 g Ambient Conditions Humidity of Air max 95 RH...