background image

MICROMATIC

®

 STANDARD 

RESPONSE UPRIGHT 

SPRINKLER VK100 (K5.6)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Page 1 of 6

Form No. F_052014  Rev 14.1

1.  DESCRIPTION

The Viking Micromatic

®

 Standard Response Upright VK100 Sprinkler is a small, ther-

mosensitive, glass-bulb spray sprinkler available in several different finishes and tem-

perature ratings to meet design requirements. The special  Polyester and Electroless 

Nickel PTFE  (ENT) coatings can be used in decorative applications where colors are 

desired. In addition, these coatings have been investigated for installation in corrosive 

atmospheres and are listed/approved as corrosion resistant as indicated in the Approval 

Charts. (Note: 

FM Global approves the ENT coating as corrosion resistant.

 FM Global has 

no approval classification for Polyester coatings as corrosion resistant.)
Viking standard response sprinklers may be ordered and/or used as open sprinklers (glass 

bulb and pip cap assembly removed) on deluge systems. Refer to 

Ordering Instructions

.

2.  LISTINGS AND APPROVALS

cULus Listed: 

Category VNIV

FM Approved:

 Classes 2001, 2002, 2015, 2017, 2043

NOTE: 

Other International approval certificates are available upon request.

Refer to Approval Chart 1 and UL Design Criteria on pages cULus Listing requirements, and refer to Approval Chart 2 and FM 

Design Criteria for FM Approval requirements that must be followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar)

 

Maximum Working Pressure: 175 psi (12 bar) wwp 

Factory tested hydrostatically to 500 psi (34.5 bar)

Thread size: 1/2” NPT, 15 mm BSP

Nominal K-Factor: 5.6 U.S. (80.6 metric**)

 

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: 2-3/8” (60 mm)

†  cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE 

Approvals ONLY is 5 psi (0.35 bar). 

** Metric K-factor measurement shown is in Bar.  When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Material Standards:

Frame Casting: Brass UNS-C84400 or QM Brass

Deflector: Brass UNS-C23000 or Copper UNS-C19500

Bulb: Glass, nominal 5 mm diameter

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with 

PTFE Tape

Screw: Brass UNS-C36000

Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel 

UNS-S30400

For Polyester Coated Sprinklers:

 

Belleville Spring-Exposed

For ENT coated Sprinklers: Belleville Spring - Exposed, Screw and Pipcap - ENT plated.

††Not for FM Approval.

Ordering Information:

 (Also refer to the current Viking price list.)

Order Micromatic

®

 Standard Response Upright VK100 by first adding the appropriate suffix for the sprinkler finish and then the 

appropriate suffix for the temperature rating to the sprinkler base part number. 

Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, Wax Coated = C, Wax Over Polyester = V-/W, 

ENT = JN

Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 212 °F (100 °C) = M, 286 °F 

(141 °C) = G, 360 °F (182 °C) = H, 500 °F (260 °C) = L, OPEN = Z (PTFE only).

For example, sprinkler VK100 with a 1/2” thread, Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12986AB

Viking Technical Data may be found on 

The Viking Corporation’s Web site at 

http://www.vikinggroupinc.com.

The Web site may include a more recent 

edition of this Technical Data Page.

(New Page for VK100)

Summary of Contents for Micromatic VK100

Page 1: ...bar wwp Factory tested hydrostatically to 500 psi 34 5 bar Thread size 1 2 NPT 15 mm BSP Nominal K Factor 5 6 U S 80 6 metric Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 3 8 60 mm cULus Listing FM Approval and NFPA 13 installs require a minimum of 7 psi 0 5 bar The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi 0 35 bar Metric K factor measurement shown is ...

Page 2: ...1 B Twelve head capacity Part No 01725A available since 1971 4 INSTALLATION Refer to appropriate NFPA Installation Standards 5 OPERATION During fire conditions the heat sensitive liquid in the glass bulb expands causing the glass to shatter releasing the pip cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern t...

Page 3: ...86 F 141 C Dk Brown Wax5 Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to specific installation standards 3 Sprinklers of Ultra High temperature rating are intended for use inside ovens dryers or similar enclosures with ...

Page 4: ...r shown by 10 0 3 This table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 4 Listed by Underwriters Laboratories Inc for use in the U S and Canada 5 cULus Listed as corrosion resistant 6 Other colors are available on request with the same Listings and Approvals as the standard colors 7 Sprinklers of Ultra High temperatur...

Page 5: ...is table shows the listings and approvals available at the time of printing Check with the manufacturer for any additional approvals 4 Other colors are available on request with the same Approvals as the standard colors 5 Sprinklers of Ultra High temperature rating are intended for use inside ovens dryers or similar enclosures with normal operating temperatures above 300 F 149 C Where the ambient ...

Page 6: ...No F_052014 Rev 14 1 Figure 2 Wrench 13577W B for Wax Coated Sprinklers Wax Coated Upright Sprinkler Step 1 Carefully slide the wrench sideways around the deflector ensuring engage ment with the sprinklger wrench flats Sprinkler wrench 13577W B must be used for installing wax coated sprinklers A 1 2 ratchet is required not available from Viking Step 2 Carefully press the wrench downward and ensure...