background image

MICROFAST

®

 QUICK 

RESPONSE VERTICAL 

SIDEWALL SPRINKLER 

VK306 (K5.6)

TECHNICAL DATA

Page 1 of 3

Form No. F_060614    18.10.18    Rev 17.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

1.  DESCRIPTION

The Viking Microfast

®

 Quick Response Vertical Sidewall Sprinkler VK306 is a small thermo-

sensitive glass bulb spray sprinklers designed for installation in either the upright or pendent 

position. The VK306 is available with finishes and temperature ratings to meet design require-

ments. 

2.  LISTINGS AND APPROVALS

FM Approved:

 Class 2012

Refer to the Approval Chart and Design Criteria for FM Approval  requirements 

that must be followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar) 

Rated to 175 psi (12 bar) water working pressure.

 

Factory tested hydrostatically to 500 psi (34.5 bar)

Thread size: 1/2” NPT, 15 mm BSP

Nominal K-Factor: 5.6 U.S. (80.6 metric**)

 

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: 2-1/4” (58 mm)

** Metric K-factor measurement shown is in Bar.  When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Material Standards:

Frame Casting: Brass UNS-C84400 or QM Brass 

Deflector: Brass UNS-C23000 

Bulb: Glass, nominal 3 mm diameter

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Screw: Brass UNS-C36000

Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

For Polyester Coated Sprinklers:

 

Belleville Spring-Exposed

Ordering Information:

 (Also refer to the current Viking price list.)

Order Quick Response Vertical Sidewall Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the ap-

propriate suffix for the temperature rating to the sprinkler base part number. 

Finish Suffix: Brass = A, and Chrome = F

Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, and   286 °F (141 °C) = G

For example, sprinkler VK306 with a 1/2” NPT thread, Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12983AB

Available Finishes And Temperature Ratings:

 Refer to Table 1.

Accessories:

 (Also refer to the “Sprinkler Accessories” section of the Viking data book.)

Sprinkler Wrench:

A. Standard Wrench: Part No. 21475M/B (available since 2017). 

Sprinkler Cabinets:

A. Six-head capacity: Part No. 01724A (available since 1971)

B. Twelve-head capacity: Part No. 01725A (available since 1971)

4.  INSTALLATION

Refer to appropriate NFPA Installation Standards.

5.  OPERATION

During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and 

sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern 

to extinguish or control the fire.

6.  INSPECTIONS, TESTS AND MAINTENANCE

Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.

Replaces Form No. F_060614 Rev 17.1

(Added P65 Warning.)

Summary of Contents for MICROFAST VK306

Page 1: ... Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Screw Brass UNS C36000 Pip Cap and Insert Assembly Copper UNS C11000 and Stainless Steel UNS S30400 For Polyester Coated Sprinklers Belleville Spring Exposed Ordering Information Also refer to the current Viking price list Order Quick Response Vertical Sidewall Sprinklers by first adding the appropriate suffix for the sprinkler fin...

Page 2: ... GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly Figure 1 Standard Sprinkler Wrench 21475M B Wrench Flat Protective Sprinkler Clip TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Bulb Color Ordinary 135 F 57 C 100 F ...

Page 3: ... When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This table shows the listings and approvals available at the time of printing Other approvals may be in process 4 Viking vertical sidewall sprinklers may be installed pendent or upright DESIGN CRITERIA Also refer to the Approval Chart above FM Approval Requirements Vertical Sidewall Sprinkler VK306 is FM Approved as a Qui...

Page 4: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 5: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 6: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 7: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 8: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Reviews: