Installation and Wiring Instructions 

 

 

PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION. 
THESE INSTRUCTIONS SHOULD BE LEFT WITH THE END USER. 

 

 
 

GALAXY™

TWIN FANS 

GDB:Galaxy In-line belt driven, twin fan 
GDD:Galaxy In-line direct driven, twin fan 
GRB:Galaxy Roof mounting belt driven, twin fan 
GRD:Galaxy Roof mounting direct driven, twin fan 

Model Ranges
 

GBD 
GDD 
GRB 
GRD 

Summary of Contents for GALAXY GBD Series

Page 1: ...TING INSTALLATION THESE INSTRUCTIONS SHOULD BE LEFT WITH THE END USER GALAXY TWIN FANS GDB Galaxy In line belt driven twin fan GDD Galaxy In line direct driven twin fan GRB Galaxy Roof mounting belt driven twin fan GRD Galaxy Roof mounting direct driven twin fan Model Ranges GBD GDD GRB GRD ...

Page 2: ...e reached during operation must be eliminated by using appropriate guards meeting statutory requirements All electrical installation must be undertaken by a suitably qualified and competent person and must be carried out in accordance with all relevant Statutory Requirements Please check the details on the unit rating plate to ensure that the correct power supply Voltage Frequency and Phase is ava...

Page 3: ... If not isolate power supply and check wiring 8 Check that the current amps taken by the fan does not exceed the current shown on the rating plate 9 Ensure rotation of impeller is correct Incorrect rotation may cause irreversible damage to the motor Three phase units require a trial connection to reverse direction interchange any two supply leads RESPONSIBILITY Vent Axia as suppliers of the equipm...

Page 4: ...thin the values shown then the drive should be satisfactory A measured force below the lower value indicates under tensioning Adjustment The belt tension can be adjusted by displacing the motor After any adjustment re check belt alignment Replacement Of Drive Components 1 Belts The drive belts should be replaced periodically as they are worn First move the motor toward the fan by a sufficient amou...

Page 5: ...In line Belt Driven Twin fan Unit A B C D E F G Weight kg GDB1 480 850 1000 650 250 110 790 125 GDB2 540 1100 1175 762 305 116 790 175 GDB3 675 1250 1450 900 400 135 1090 210 GDB4 765 1500 1450 1000 457 153 1090 270 ...

Page 6: ...10 530 425 175 100 55 20 GDD2 260 740 525 225 150 55 20 GDD2X 260 740 525 225 150 55 20 GDD2XH 260 740 525 225 150 55 20 GDD3 330 740 600 250 150 90 20 GDD4S 390 900 700 350 200 95 30 GDD4 390 900 700 350 200 95 30 GDD5 440 1000 800 400 325 57 52 GDD6 440 1000 800 450 350 44 59 GDD7 575 1250 1000 650 400 86 64 ...

Page 7: ...Driven Twin fan Unit A B C D E F G H J Weight kg GRB1 500 900 1100 900 500 250 247 100 900 90 GRB2 600 1150 1175 1120 762 305 150 27 5 1120 120 GRB3 700 1450 1450 1450 900 400 150 1450 195 GRB4 800 1550 1450 1550 1000 450 150 1450 215 ...

Page 8: ...50 150 25 690 75 22 GRD2X 340 750 700 700 225 150 150 25 690 75 22 GRD2XH 340 750 700 700 225 150 150 25 690 75 22 GRD3 390 750 700 700 250 150 150 25 690 75 21 GRD4S 450 850 800 800 300 200 150 25 790 75 32 GRD4 450 850 800 800 300 200 150 25 790 75 32 GRD5 550 1000 950 950 500 250 150 25 940 75 55 GRD6 550 1050 1050 1050 600 300 150 1040 75 65 GRD7 650 1250 1150 1150 750 350 150 50 1140 75 65 ...

Page 9: ...t be provided with single phasing prevention 7 Where products have TK connections on the fan terminal strip these are independently connected to a thermal switch in the windings of the motor and should be used as part of the control system 8 Ensure that all earth connections have been made After completing and checking the connections to the terminal box replace the terminal box lid ensuring that ...

Page 10: ...10 GRD1 GRD2 GRD3 GRD4 GRD4S GRD5 GRD6 GRD7 GRD1X GRD2X GRD2XH ...

Page 11: ...11 GDD1 GDD2 GDD3 GDD4 GDD4S GDD5 GDD6 GDD7 GDD1X GDD2X GDD2XH ...

Page 12: ...S Tel 0844 8560590 Fax 01293 565169 TECHNICAL SUPPORT Tel 0844 8560595 Fax 01293 539209 For details of the warranty and returns procedure please refer to www vent axia com or write to Vent Axia Ltd Fleming Way Crawley RH10 9YX As part of the policy of continuous product improvement Vent Axia reserves the right to alter specifications without notice 84GALAXY INST E 0613 ...