GLT-299-7-13  Rev.1 

Jan 24, 2022 

 

Instruction Manual

      

  

          

 

VDOT-ZMU-SCI  Zone Module

                        

 

Before Installation 

Please read these instructions carefully and keep for future reference.   

The information in this document is subject to change without notice. 

For updates please refer to our website. 

 
 
 
 
 
 
 
 

Note

  : 

Follow the requirements for the installation of the product in 

accordance with the Specifications. Otherwise it may cause malfunction.

 

Note 

: 

Do not install the product in any location where oil, dust, iron 

powder, chemicals, or hydrogen sulphide may occur or affect the product. 

It may cause malfunction.

   

 

This package contains the following items: 

Main unit

  ………………………………………………………………

Outer cover  

… … … … … … … … … … … … … … … … … … … … … …

Instruction Manual

  ……………………………………………………

Tapping screw

  …………………………………………………………

Pan head screw  

…………………………………………………………

EOL Resistor  (VDOT-RE-10k)

…………………………………………………

 

General Description 

VDOT-ZMU-SCI Zone Module with Short Circuit Isolator is intended for 

use in addressable two wire systems, which can be connected with 

2-wire conventional detectors. The module monitors and transmits the 

status (normal, open, short, or alarm) of zone with the  detectors to a 

control panel. The initiating device circuit (IDC) can be wired on Class A 

or Class B.   

 

General Operation 

Normal standby condition: The module receives polling from the control 

panel at the regular interval. Polling LED (green) flashes. 

Alarm condition: When an external input is activated, Input LED (red) 

illuminates, and the module communicates to the control panel the 

alarm status. 

Trouble condition: If an overcurrent occurs because SLC (Signaling Line 

Circuit) is shorted, SCI LED (yellow) illuminates, and the module 

communicates to the control panel the short status. The module also 

communicates to the control panel the open/short status of IDC, 

depending on the Subtype Setting described below.

 

 

SCI (Short Circuit Isolator) Function 

The module has a built-in short circuit isolator. SCI circuit prevents 

entire loop failure in the event of a short between L+ and L- on the loop. 

If a short is detected between L+ and L-, the yellow LED indicator is 

illuminated.  The line between Lin-  and Lout-  is disconnected 

automatically to isolate the short  circuit, and short circuit status is 

communicated to the control panel. Upon removal of the short condition, 

the module will automatically connect between Lin- and Lout- to restore 

the entire loop to the normal operating status. 

Polling LED (GREEN)

Input LED (RED)

SCI LED (YELLOW)

Address Setting Port

 

Figure 1 

 

 

 

 

 

 

 

 

 

 

Figure 2 

ZETA ALARMS LIMITED 

72-78 MORFA ROAD, SWANSEA, SA1 2EN 

  http://www.velocitydetection.com 

Make sure to turn the power off before commencing any wiring work. 

Otherwise it may cause electric shock or damage to equipment.

CAUTION

!

Do not disassemble, repair, or modify the products. It may cause a fire or 

electric shock.

CAUTION

!

Do not use the products outside the rated power supply voltage range 

specified in the Specifications. It may cause a fire or damage to 
equipment.

CAUTION

!