OPU-D42-W50 operation terminal for TLR-D42 base units 

Features 

 

Temperature control for 2-pipe and 4-pipe fan coil systems. 

 

Automatic fan control for three stage fans.  

 

Control for heating, cooling and fan only operation 

 

 Cost saving option with Economy functionality and set point limitation 

 

 For large rooms: Master – Slave option: One terminal may drive up to 8 base units in parallel.  

 

 Password protected programmable user and control parameters 

 

 External sensor or open contact for remote control, external heat – cool change or auto-changeover 
on supply or outdoor temperature with selectable activation limits 

 

 One terminal may control up to 8 base units in parallel mode 

Deluxe Version: 

 

Clock and time schedule functions 

 

Blue backlight for LCD 

 

Infrared remote controller option:  
With special features for Boost and delayed switching on or off 

Ordering 

A working controller consists of one operation terminal and at least one base unit.  

Item name 

Item code 

Function 

Type 

Key-data 

TLR-D42-24 

40-11 0085 

24VAC 

Base unit 

Fan coil controller with:  
1 TI int or ext 
3 DO (Relay) Fan control 
2 AO (0-10VDC) PI control 
1 DO HEAT/COOL 

TLR-D42-230 

40-11 0086 

230VAC 

OPU-D42 

40-10 0166 

Standard 

Operation 
terminal (2x4”) 

OPU-D42-D 

40-10 0167 

Deluxe 

Accessories

 

 

 

 

OPR-1 

40-50 0001 

 

2xAAA bat 

Infrared remote controller 

S-Tn10-2 
SD-Tn10-12-2 
SD-Tn10-20-2 
SDB-Tn10-12 
SDB-Tn10-20 
SRA-Tn10 
SOB-Tn10 

40-20 0001 
40-20 0002 
40-20 0003 
40-20 0051 
40-20 0004 
40-20 0005 
40-20 0059 

Flying lead sensor with 2 m cable 
Flying lead duct sensor 12cm immersion depth, 2m cable 
Flying lead duct sensor 20cm immersion depth, 2m cable 
Duct sensor with housing, 12cm immersion depth 
Duct sensor with housing, 20cm immersion depth 
Room sensor 
Outdoor sensor 

Selection of actuators, fans and sensors 

Temperature Sensors: Use only our approved NTC sensors to achieve maximum accuracy.   
Modulating Actuators: Choose actuators with an input signal type of 0-10VDC. The current on the output is 
limited to 10mA. 
Fan motors:  Observe power limits and startup currents. Note: startup currents may be a multiple of the rated 
current of a fan. Verify with the fan supplier if unclear.  

Installation Terminal 

1. 

Install the mounting plate to the electrical connection box. Make sure that the nipple with the front 
holding screw is facing to the ground. Make sure the screw heads do not stand out more than 5 mm 
of the surface of the mounting plate.  

2. 

Connect the wires of the terminals to the communication wires according wiring diagram 

3. 

Slide the two latches located on the top of the front part into the hooks of the mounting plate.  

4. 

Lower the front part until located flat on the wall and the mounting plate is not visible anymore. Make 
sure the connection cable does not get into the way. 

5. 

Tighten the front holding screw to secure the front part to the mounting plate.  

Connection base to terminal 

 

Max. Distance: 200m (565 ft.) 

 

Normal twisted pair copper wires maybe used for wiring in an EMC-save environment. In an 
impaired EMC environment use only shielded cables. The operating voltage must comply 
with the requirements for safety extra-low voltage (SELV) as per EN 60 730. 

 

1 terminal may drive up to 8 base units. See wiring for parallel connections. Total wire 
distance should not exceed 200 m.  

 

Conductor resistance will influence external temperature reading. 450 Ω will result in an 
increase of 1°C (2°F). Compensate using UP-08 if external temperature is used to control 
unit. 

Technical Specification 

Power Supply 

Operating Voltage 

5V DC ±10% 

 

Power Consumption 

30mA max 

 

Electrical Connection 

Terminal Connectors 

 

Deluxe type only: 
Power backup for real time clock 

 
Min 48h if charged for 24h 

Signal Inputs 

Temperature Inputs 

 

 

Range 
Accuracy 

0…50 °C (32…122 °F) 
0.5°C, 1°F 

Communication  
Base - Terminal 

Communication Type 
Cable Type 
Max Distance 

Digital: peer to peer 
Use twisted pair copper wire 0.8…2.5 mm

2

 

(AWG18…AWG13) 200m (650ft) use shielded wire 
in an EMC challenged environment. Conductor 
resistance must be compensated if external sensor 
is used 

Environment 

Operation 
Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0…50 °C (32…122 °F) 
<95 % r.H. non-condensing 

 

Transport & Storage 
Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25…70 °C (-13…158 °F) 
<95 % r.H. non-condensing 
class 2M2 

Standards 

 

conformity 
EMC Directive 
Low Voltage Directive 

2004/108/EC 
2006/95/EC 

 

Product standards Automatic electrical 
controls for household and similar use 
Special requirement on temperature 
dependent controls 

 
EN 60 730 –1 
 
EN 60 730 – 2 – 9 

 

Electromagnetic compatibility for  
domestic sector 

Emissions: EN 60 730-1 
Immunity: EN 60 730-1 

General Terminal  Safety Class 

III (IEC 60536) 

 

Degree of Protection 

IP30 to EN 60 529 

 

Material: Cover, back part 
Mounting Plate 

ABS plastic (UL94 class V-0) 
Galvanized Steel 

 

Color 

White RAL 9003 

 

Dimensions (H x W x D) : OPA :  
OPU : 

88 x 88 x 24 mm (3.5 x 3.5 x 0.9 in) 
112 x 73 x 18 mm (4.4 x 2.9 x 0.8 in) 

 

Weight including package:  
OPA-D42, OPU-D42 
OPA-D42-D, OPU-D42-D 

 
180 g (6.3 oz) 
190 g (6.7 oz) 

Power Failure 

All the parameters and set points are memorized and don’t need to be reentered. The clock will need to be reset.  

Status LED 

The status LED is located on the base unit between the two low power terminal connector groups. The status LED 
may display the following feedback:  
No light:  

No power or unit is damaged 

Blink every 1s:   Error, terminal – base unit do not match or signal is not clear. 
Blink every 2s:   Normal communication, base unit detected 
Blink every 5s:   Base unit operates normal, no terminal detected 

Error messages 

Err1:

 

Error temperature sensor. The internal temperature sensor may be damaged or not present.  

Err2:

 

External input for heat / cool auto-change-over missing or damaged.  

FP:

 

Frost protection is active. 

Wiring Diagram 

 

 
Dimensions Terminal 

 

 

73 (2.9) 

15 

(0.6) 

11

2 (4.

4)

 

OPU 

3  

(0.1) 

TLR-D42 Base unit

 

1      2     3     4 

 

OPU-D42(-D)

 

10 
T1 

11 
T2 

12 
T3 

13 
T4 