background image

EVO250DC

Whole House Heat Recovery Unit 

for domestic and commercial use

with Low Energy DC Motors

Optional - Remote LCD 

Installation, Operating and Maintenance 

     Instructions

Page 5

Commissioning

1. The commissioning must only be carried

out by a suitably qualified person.

2. Prior to starting the commissioning pro-

cedure, ensure that the ductwork con-

nections and airflow directions match 

one of the options 1 or 2, shown on page

4.  Check that the drain connection is on

the correct side.

3. Before making any adjustments, ensure 

that the air valves or grilles are fully open.

4. Please see separate "LCD Control Panel

Commissioning Instructions" for details

on commissioning and user operations

..

WARNING : With the control board panel 

removed, 230 volt live connections are 

accessible.

Cleaning and Maintenance

WARNING: The unit uses a 230V  supply and contains rotating mechanical parts.

•    Before carrying out any maintenance or cleaning operations the mains electrical supply MUST be dis-

     connected

.

The air filters and heat exchanger of the Vectaire EVO250DC should be cleaned regularly by a

suitably qualified person (the frequency of cleaning will vary depending on the installation environment). Filters should

be replaced after a maximum of 3 cleaning cycles.

Filters:

    Remove the filter covers on the front panel.

   Slide out the filters by pulling out the tabs

   Clean the filters carefully using a vacuum cleaner, replace in the slots and refit the filter covers 

Heat Exchanger:

   Firstly remove filters as described above

   Remove the screws securing the front panel and carefully lift off.  Using the plastic strap fitted, carefully pull 

     out the heat exchanger

   Caution: if this is done during cold weather, the heat exchanger may contain water.  It is advisable to have a 

     plastic bowl available to avoid spillage.

   Lightly clean the faces of the heat exchanger with a vacuum cleaner.  Replace the heat exchanger carefully, 

     by sliding the assembly back into the cabinet.

   Replace the front cover by hooking the top edge into the slots in the cabinet and secure in place using the 

     screws.

Finally, replace the filters as above.

Never use water or any other fluids to clean the heat exchanger.

•    

Return the heat exchanger and filters to their original position.

•    

Replace the front cover and ensure it is securely located at the top before tightening all screws.

•    

Power to the unit can now be restored.

Filter Replacement

Filters should be replaced annually or after a maximum of 3 cleaning cycles.

Replacement filters are available from Vectaire - call us on +44 (0) 1494 522333 or via [email protected]

Vectaire Ltd, Lincoln Road, Cressex Business Park, High Wycombe, Buckinghamshire, HP12 3RH

Tel: +44 (0)1494 522333.  Fax: +44 (0)1494 522337.  Email: [email protected]

EVO250DC LCD 160119

E & O.E

Reviews: