background image

Ultra Low Flow AQUAMIST Nozzles

Type ULF AM24

Automatic (Closed)

Page 1 of 2 

SEPTEMBER 2018 

TFP2224

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Ultra Low Flow AQUAMIST 

Nozzles Type ULF AM24 are closed 

(automatic) nozzles intended for use 

with engineered, water-mist systems. 

They are low-pressure nozzles that 

utilize a single fluid jet impinging on a 

diffuser to produce a spray having a 

range of water droplet sizes suitable 

for the control of Class A fires.
It is recommended that the end user be 

consulted with respect to the suitabil-

ity of the materials of construction and 

finish for any given corrosive environ-

ment. The effects of ambient tempera-

ture, concentration of chemicals, and 

gas/chemical velocity should be con-

sidered, at a minimum, along with the 

corrosive nature to which the nozzles 

may be exposed.

NOTICE

The Type ULF AM24 AQUAMIST 

Nozzles described herein must be 

installed and maintained in compliance 

with this document, as well as with the 

applicable standards of the NATIONAL 

FIRE PROTECTION ASSOCIATION 

(NFPA), in addition to the standards 

of any authorities having jurisdiction. 

Failure to do so may impair the per-

formance of these devices.
The design of individual water-mist 

systems can vary considerably, 

depending on the characteristics and 

nature of the hazard and the basic 

purpose of the water-mist system. 

Because of these variations, the design 

of water-mist systems for fire protec-

tion must only be performed by expe-

rienced designers who thoroughly 

understand the limitations as well as 

capabilities of such systems.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Technical  

Data

Discharge Coefficient

K = 9,2 LPM/bar

1/2

 (0.64 GPM/psi

1/2

)

Thread Connection

1/2 in. NPT

Response Time Index

Quick Response

Finish

Natural Brass 

Chrome Plated 

Pure White 

Signal White

Temperature Ratings

Refer to Table A

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Inlet Strainer . . . . . . . . . . . . . . . . . . . . . .  Copper

Orifice Insert . . . . . . . . . . . . . . . . . . . . . . .Bronze

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . . Beryllium Nickel w/TEFLON

Ejection Spring . . . . . . . . . . . . . .  Stainless Steel

Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass

Diffuser . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Loading Screw  . . . . . . . . . . . . . . . . . . . . .Bronze

The smallest waterway (orifice) diam-

eter of the Orifice Insert is nominally 

4,4 mm (0.172 in.). The diameter of the 

Inlet Strainer perforations is nominally 

3,2 mm (0.125 in.).

Design 

Criteria

Obtain guidance for the design of a 

water-mist system that utilizes the 

TYCO Type ULF AM24 AQUAMIST 

Nozzles from the Technical Services 

department.

The Type ULF AM24 can only be 

installed in non-recessed applications.

Installation

The TYCO Type ULF AM24 AQUAMIST 

Nozzles must be installed in accor-

dance with this section.

General Instructions

Do not install any bulb type nozzle if 

the bulb is cracked or there is a loss 

of liquid from the bulb. With the nozzle 

held horizontally, a small air bubble 

should be present. The diameter of 

the air bubble is approximately 1,6 mm 

(1/16 in.) for the 57°C (135°F) to 2,4 mm 

(3/32 in.) for the 93°C (200°F) tempera-

ture ratings.
A leak-tight 1/2 inch NPT nozzle joint 

should be obtained by applying a min-

imum-to-maximum torque of 9,5 to 

19,0 N·m (7 to 14 lb-ft). Higher levels 

of torque can distort the nozzle inlet 

and cause leakage or impairment of 

the nozzle.
For flush installations, use the Style 20 

Escutcheon.

Step 1.

 Install the Type ULF AM24 

Nozzle in the pendent position as 

shown in Figure 1.

Step 2.

 With pipe-thread sealant 

applied to the pipe threads, hand-

tighten the nozzle into the nozzle fitting.

Step 3.

 Tighten the nozzle into the 

nozzle fitting using only the W-Type 6 

Nozzle Wrench, refer to Figure 2. With 

reference to Figure 1, apply the wrench 

to the Nozzle Wrench Flats.

Reviews: