The Series TY-B, 5.6 and 8.0 K-factor
Upright and Pendent Intermediate
Level Sprinklers described in this data
sheet are automatic sprinklers of the
“standard response” 5 mm  frangible
bulb type. They are “standard spray”
sprinklers intended for use in fire sprin-
kler systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on NFPA requirements). Both
the Pendent and Upright Sprinklers
produce a hemispherical water distri-
bution pattern below the deflector.

Intermediate Level Sprinklers are pri-
marily designed for use in rack storage
sprinkler systems,  where their ther-
mally sensitive elements must be
shielded from the water spay of higher
elevation sprinklers which could oper-
ate earlier during a fire. Intermediate
Level Sprinklers are also used in appli-
cations such as beneath open gridded
catwalks.

Corrosion resistant  coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.

WARNINGS

The Series TY-B Sprinklers described
herein must be  installed and  main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.

The owner is responsible for maintain-
ing their fire protection system and de-
vices in  proper operating  condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

Model/Sprinkler
Identification
Numbers

TY3153 -

Upright 5.6K, 1/2"NPT

TY3251 -

Pendent 5.6K, 1/2"NPT

TY4153 -

Upright 8.0K, 3/4"NPT

TY4251 -

Pendent 8.0K, 3/4"NPT

Technical
Data

Approvals

UL and C-UL Listed.
FM and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K = 5.6 GPM/psi

1/2

(80,6 LPM/bar

1/2

)

K = 8.0 GPM/psi

1/2

(115,2 LPM/bar

1/2

)

Temperature Ratings

Refer to Table A

Finishes

Sprinkler: Refer to Table A

Physical Characteristics

Frame

. . . . . . . . . . . . Bronze

Button

. . . . . . . .

Brass/Copper

Sealing Assembly . . . . . . . . . .

. . . . . . Beryllium Nickel w/Teflon†

Bulb

. . . . . . . . . . . . . . Glass

Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Copper
Shield

. . . . . . . . .

Plated Steel

D

uP

on

t

R

eg

is

tere

d

T

rad

ema

rk

Series TY-B — 5.6 and 8.0 K-factor
Upright and Pendent Intermediate Level Sprinklers
Standard Response

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

Page 1 of 6

TFP351

FEBRUARY, 2002

Customer Service/Sales:

Tel: (215) 362-0700 / (800) 523-6512

Fax: (215) 362-5385

TFP351 (3-5.1)

OBSOLETE

Summary of Contents for CENTRAL TY-B Series

Page 1: ...tion of chemicals and gas chemical velocity should be con sidered as a minimum along with the corrosive nature of the chemical to which the sprinklers will be exposed WARNINGS The Series TY B Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the standar...

Page 2: ...IES TY B UPRIGHT TY4153 AND PENDENT TY4251 SPRINKLERS INTERMEDIATE LEVEL SPRINKLERS 8 0 K FACTOR 3 4 INCH NPT SCREW SHIELD UPRIGHT SHIELD MODEL S2 SHIELD FIELD ASSEMBLED SEE INSTALLATION SECTION 2 3 16 55 6 mm PENDENT WRENCHING FLATS NOMINAL MAKE IN 7 16 11 1 mm 1 2 NPT O RING 60 3 mm FACTORY ASSEMBLED UPRIGHT 1 2 NPT 11 1 mm MAKE IN NOMINAL 7 16 2 3 8 3 1 2 88 9 mm DIA FLATS WRENCHING 3 1 2 88 9 ...

Page 3: ...d Coated Wax Coated and Wax over Lead Coated Sprinklers are noted to be FM Approved the sprinklers are FM Approved as Corrosion Resistant Sprinklers 150 F 66 C Maximum Ceiling Temperature With Zinc Plated Shield N A Not Available TABLE A LABORATORY LISTINGS AND APPROVALS WAX OVER LEAD COATED LEAD COATED WAX COATED 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 N A K 5 6 1 2 NPT PENDENT TY3251 135 F 57 C ...

Page 4: ...ield past the threads Step 2 Roll the O Ring over the sprin kler threads until it seats against the Shield Step 3 With pipe thread sealant ap plied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 4 Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench Ref Figure 3 With reference to Figure 1 or 2 the W Type 6 Sprinkler Wrench is to ...

Page 5: ...hip with Tyco Fire Products or for products and components which have been subject to misuse improper installation corro sion or which have not been installed maintained modified or repaired in ac cordance with applicable Standards of the National Fire Protection Associa tion and or the standards of any other Authorities Having Jurisdiction Mate rials found by Tyco Fire Products to be defective sh...

Page 6: ...41 C MAX 8 WAX OVER LEAD 286 F 141 C MAX 543 8 0K UPRIGHT 3 4 NPT 533 5 6K UPRIGHT 1 2 NPT TY3153 TY4153 P N 57 XXX X XXX 360 F 182 C 155 F 68 C 360 155 TEMPERATURE RATING 135 F 57 C 135 1 SPRINKLER TABLE C PART NUMBER SELECTION SERIES TY B PENDENT SPRINKLERS MODEL S2 PENDENT SHIELD O RING MUST BE SEPARATELY ORDERED 175 F 79 C 286 200 F 93 C 200 286 F 141 C 175 NATURAL BRASS 9 MODEL SIN CHROME PLA...

Reviews: