background image

1

LUXA 103-100 DE WH

1030012

LUXA 103-101 DE WH

1030013

307343

Motion detector

EN

1.  Basic safety information

Danger of death through electric shock or fire!

¾

¾

Installation should only be carried out by a 

qualified electrician!

WARNING

 

The device conforms with EN 60669-2-1 if installed 
correctly

2.  Proper use

 

Motion detector for automatic lighting control dependent 
on presence and brightness; LUXA 103-101 DE: suitable 
for automatic lighting and HVAC control

 

Suitable for ceiling installation (false ceilings) indoors

 

Suitable for toilets, small rooms, workplaces, offices, etc.

Disposal

¾

†

Dispose of the device in an environmentally sound manner 
(electronic waste)

3.  Device description

Sensor unit

Power supply unit

3 potentiometers for setting 

time delay (TIME), bright-

ness value (LUX) and detec-

tion area (metres);

additional setting of HVAC 

time (TIME 2) in the case of 

LUXA 103-101 DE

red LED

4.  Installation and connection

 

!

Secure device with an upstream type C circuit breaker  

(EN 60898-1) with a maximum of 10 A.

 

!

Secure device with an upstream type C circuit breaker  

(EN 60898-1) with a maximum of 6 A (HVAC channel 2).

Installing the motion detector

 

L

Installation height: 2 – 3 m

 

L

Cable length: 100 cm

 

L

Motion detector requires clear line of sight to people 

¾

†

Disconnect power source

0FF

230V

¾

†

Create a ceiling opening of Ø 65 mm

=65

Ø

6 - 8 m m

5 0 - 6 0 m m

¾

†

Screw open and flip open the power supply unit

¾

†

Connect power supply unit and sensor unit according to the 

wiring diagram

 

L

Recesses in the power supply unit can be adjusted to the 

cable diameter (min. Ø 3 - max. Ø 12.5 mm)

Ø 3 - Ø 6 mm 

Max. Ø 12.5 mm 

 

!

ATTENTION

: the network connector must be firmly in place

¾

†

Push the power supply unit through the ceiling opening 

and attach the sensor with tensioned springs in the ceiling

Ø

= 65

¾

†

Connect motion detector to power supply

Reviews: