background image

CUBE

LT

User Manual

Summary of Contents for CUBE LT

Page 1: ...CUBELT User Manual...

Page 2: ...DESIGNED AND MADE IN CANADA...

Page 3: ...e 28 Temperature Adjustment 29 Adjusting the Alarm Sound Level 29 Settings 30 Screen Unlock 32 Control with a Device on the Same Network 32 Remote Connection 33 Maintenance 34 Cleaning the Water Chill...

Page 4: ...ce which may occur as a result of use or misuse NOTE Provides special information to facilitate maintenance or clarify impor tant instructions WARNING DO NOT operate the unit through an electrical out...

Page 5: ...he rooms where the appliance is installed must be between 10 C and 38 C 50 F 100 F CAUTION If service is required contact an authorized service agent DO NOT place objects or sit on system modules Inst...

Page 6: ...wine cellar is adequately insulated and sealed against humidity before installing the CUBELT Conditions In The Wine Cellar The CUBELT wine cellar cooling system is a system designed to maintain a tem...

Page 7: ...ts 1 2 3 The CUBELT is a split cooling system made up of three components It allows the noisy element the compressor to be placed at a distance from the wine cellar 1 CUBELT CONTROL BOX 2 CUBELT WATER...

Page 8: ...water of the building Very ecological and safe it uses no refrigerant gas and therefore always recirculates the same water It is normally installed in a garage or mechanical room CONTROL BOX Voltage__...

Page 9: ...nt or condo without a mechanical room WATER CHILLER Voltage____________________________________________ Amperage_______________________________________ Power Consumption_______________________ Cooling...

Page 10: ...metry it may be necessary to install more than one RC4LT they are then connected in series on the communication and water supply level RC4LT DIFFUSER Power Communication_________________ Cooling Power...

Page 11: ...or U0 22 with LOW E protection CAUTION Insulation under a concrete slab does not count as floor insulation Unless the slab of the wine cellar is independent from the rest of the building and has a th...

Page 12: ...tem Indeed assuming that the system is a heat pump THE RC4LT This unit seeks to remove heat from the wine cellar so it will need to be located at the hottest location in the wine cellar the ceiling De...

Page 13: ...2 PIPE 2X INSULATED PEX 1 2 PIPE ETHERNET RJ45 CAT6 RC4 LT CONTROL BOX CUBE LT WA TER CHILLER CUBE LT ETHERNET WALL PLATE LINKED TO INTERNET SOCKET NEMA 5 15R 2P DEDICATED CIRCUIT DRAIN ROUGH IN A B C...

Page 14: ...of the unit and at least 5 8 thick at the loca tion of the unit Provide an opening of maximum 2 x 10 tangent with the middle of the location of the unit for the passage of the tubes Generally two hol...

Page 15: ...ever generate condensation if the humidity in the house is well managed the P trap would thus end up drying up C 2 6 50 150 At the ceiling in the wine cellar leave between 2 and 6 of tubing hanging fr...

Page 16: ...sed Install an RJ45 network socket connected to the internet near the device The CUBELT uses a wired connection to connect to the internet E Have a professional install a NEMA 5 15R 2 pole electrical...

Page 17: ...dust could damage the device and reduce the cool ing capacity of the system In the event that construction steps are required following the installation of the system please unplug the device before s...

Page 18: ...ll the radiator module on the support plate Be careful not to trap the tubes when rotating the module 4 Secure the radiator in place with two 8 flat head wood screws long enough to anchor into the nai...

Page 19: ...that the connection with the tubes is above the condensation pan Otherwise take care to insulate the PEX and fitting to avoid condensa tion 6 Install a connector at the end of the RJ45 wire and conne...

Page 20: ...orient that surface toward the back of the wine cellar When putting the housing back in place make sure the tubes are not kinked Once the wood box is in place turn the support fins to hold it in posit...

Page 21: ...1 At the desired location of the control box install the mounting plate 60 from the floor 60 1524 2 Using the two openings behind the control box embed the unit on the two hooks of the support plate...

Page 22: ...ing hole is located in the middle under the device 4 Install the power supply bracket under the unit on the right side of the unit The bracket is in stalled with two wood screws directly to the wall 5...

Page 23: ...clos est to the wall RJ45 outlet identified by an icon showing three bottles of wine Connect the RJ45 cable connected to the inter net to the control box The internet connector is identified by a pla...

Page 24: ...of its packaging and install the cover on top of the unit The hood allows you to choose the direction of hot air exit Orient the hot air out let so that the heat emitted easily dissipates into the ro...

Page 25: ...e floor of the water chiller The tube closest to the side of the control box connects to one of the two pipes coming from the RC4LT in the wine cellar The highest outlet of the water chiller con nects...

Page 26: ...ging the appliance it is important not to start the system if the wine cellar has not yet been completed door missing seal missing etc or if work that can generate a lot of dust remains to be done joi...

Page 27: ...and stop a few times during filling A water level sensor inside the tank ensures that the pump stops when there is water missing CAUTION To prevent the formation of algae or other contaminants in the...

Page 28: ...three times to make sure the system is full of water You should be able to put a minimum of 3 8 liters 1 gal of water in the system 3X 7 Replace the two tank caps 8 Close the door and lock the front...

Page 29: ...djusted with the control box not the water chiller The water chiller has a 2 minutes delay be fore starting to protect the compressor 10 Now that the installation is complete go around the components...

Page 30: ...ble Just touch the screen to restart the display After touching the screen it is normal to have about 3 seconds delay before the display appears A B C D E F G H I J A Wine cellar temperature B Current...

Page 31: ...o change the temperature set point in the wine cellar Click on the arrows to the right of the temperature display The current temperature display will then change to show the setpoint Click on the ico...

Page 32: ...Language In the Settings menu select the language tab on the left of the screen Then click on the desired display language To re turn to the main screen Click on the X in the upper right corner Temper...

Page 33: ...In the Settings menu select Connection tab in the left of the screen You can then enter an email address and or a tele phone number to receive alerts in the event of failures of your system Check the...

Page 34: ...rowser of your device and enter the following address http ip_address 4500 cube Which would give for example for the screen presented here http 192 168 2 253 4500 cube It is possible to control your C...

Page 35: ...XXXX 2 To create your account send the following information to info thewinesquare com Name Serial number of the device Email address to associate with the account Phone number to reach you In the fol...

Page 36: ...he appliance is located 1 Open the plastic grid of the upper part 2 Take out the filter 3 Clean the filter in warm water 4 Replace the filter Maintenance Cleaning the Water Chiller Filter NOTE The gri...

Page 37: ...does through the cork However the system should not lose more than a few milliliters per year However during the first filling it is normal to have to add water after a few days During fill ing micro...

Page 38: ...water level sensor inside the tank ensures that the pump stops in the event of a lack of water WARNINGTo prevent the formation of algae or other contaminants in the system Always use sterile water suc...

Page 39: ...the left tube 5 Put the section of the tube coming from the wine cellar in the bucket 6 Using a compressor limited to 15psig inject air into the tubing connected to the control box 7 Inject air until...

Page 40: ...e situation The blue circle corresponds to the first level of warning At this stage the system is only informing you of a situation for which it is taking action In this situation the system does not...

Page 41: ...ve cold water loop pump Error 009 X Cellar temperature sensor is faulty Error 011 Low level in the cold water tank Error 012 X Manque d eau dans le r servoir d eau froide Error 016 X Disconnected cold...

Page 42: ...ble is properly connected to the control box and to the RC4LT electronic card 2 Using an RJ45 cable tester check that the communication cable works well be tween the RC4LT and the control box The temp...

Page 43: ...s faulty It communi cates with the system but it sends erroneous data The system is therefore no longer able to know the temperature of the cellar and to control it The system will stop cooling until...

Page 44: ...intenance section of this manual The water level in the cold water tank is insufficient to allow the system to operate The system shuts down until the situation is corrected This error only occurs if...

Page 45: ...til the situation is cor rected ERROR 016 SOLUTION 1 Replace the water loop temperature sensor in the control box To do this contact your The Wine Square product retailer The fan inside the control bo...

Page 46: ...your The Wine Square product dealer to identify the source of the prob lem The temperature inside the wine cellar has reached the critical point of 24 C In this situation the system stops to prevent...

Page 47: ...of the system ERROR 022 SOLUTION 1 Contact your The Wine Square product dealer to identify the source of the prob lem The water chiller temperature sensor is damaged In this situation the water coolin...

Page 48: ...mperature in the wine cellar no cold air comes out of the RC4LT unit 1 Check that the construction of the wine cellar meets the minimum system require ments 2 Check if the humidity in the house is nor...

Page 49: ...ses this is due to a poorly insulated hose Remove the case from the RC4LT 2 Look for the source of the water drops Here are the most common problems Poorly insulated hose Leak Clogged condensate pump...

Page 50: ...s If this difference is significant it may be necessary to cheat the temperature demand to obtain the desired value That is to say if it is noted for example that the temperature in the cellar is 16 C...

Page 51: ...e tempera ture If not look for a pinched hose that would prevent water flow 4 Stop and restart the control box a few times to try to get rid of any air bubbles that may have formed in the pump or wate...

Page 52: ...50 APPENDICES...

Page 53: ...he control box An RJ45 network wire with minimum 23AWG wire between the RC4LT loca tion and the control box location Wood blocking at the location of the control box One NEMA 5 15R 2 pole receptacle a...

Page 54: ...re barrier vapour barrier on all surfaces Wood blocking for glass installation Wood blocking for racking installation Low voltage wires for the installation of lighting Pictures of the walls and ceili...

Page 55: ...53 PARTS LIST...

Page 56: ...rdinateur 7 CUBLT M 0007 Steel Box Boite de m tal 8 CUBLT M 0008 Holding Plate Plaque support 9 CUBLT M 0009 Electronic Plate Plaque lectronique 10 CUBLT M 0010 Main Board Carte principale 11 CUBLT M...

Page 57: ...tion Tray Bac de condensation 5 CUBLT M 0021 RC4LT Box Bo tier RC4LT 6 CUBLT M 0022 Radiator Monting Plate Plaque du radiateur 7 CUBLT M 0023 Condensation Pump Pompe condensats 8 CUBLT M 0024 PCB Hold...

Page 58: ...56 NOTES...

Page 59: ...isfaction If you need help or have any problems with your CUBELT air conditioning system please contact the members of the tech nical support team for assistance Canada USA 1 844 888 5522 info thewine...

Page 60: ...WWW THEWINESQUARE COM The Wine Square 2022 All rights reserved R0 0...

Reviews: