background image

 

Astra-45A 

Addressable hardwired  

fire manual call point  

 

 

 

 

 

 

 

 

User guide 

Manufacturer: 
ZAO NTC TEKO 

420108, Russia, Kazan,  
Gafuri str., 71  
Tel.:+7(843) 528-03-69 

[email protected] 
www.teko.biz

 

 

Made in Russia 

 

  

           

Rev. 45

А-v2_0_instr_en 

  
 

1  FUNCTION 

The  addressable  hardwired  fire  manual  call  point 
(further  “Call  Point”  or  “Astra-45A”,  “device”)  is  de-
signed to manually trigger a fire alarm by pressing the 
drive element (button), to generate a 

“Fire” notification 

and  to 

transmit  the  “Fire”  notification    via  Signaling 

Line  Circuit  (SLC)  through  Astra-A  RPA  to  Control 
Panels:  Astra 

–  812 Pro or Astra – 8945 Pro (version 

5_5 or version higher).  

Astra-45A  provides  isolation  of  the  SLC  section  in 
which  a  short  circuit  has  occurred  (Control  Panel  
version 5_5 and version higher).  
Astra 

– 45A is powered by Astra-A RPA. 

 

2  

SPECIFICATION

 

Power supply voltage, V ................................  7,5 - 27,6 
Dimensions, mm

.…………………………… 110×94×48 

Operating Conditions 

Temperature range, 

°

С

 ....................... from - 30 to + 55 

Relative air humidity

, % ...................... up to 93 at +40

°

С 

 

without moisture condensation 

3  DELIVERY  SET 

Delivery  set  includes:  unlock  key  (large) 

– 1 pc, push 

key (small) 

– 1 pc, labels – 2 pcs, 

fastening parts (dow-

els 

– 2 pcs, screws – 2 pcs), 

user guide 

– 1 pc

 

4  INDICATION

 

Status

 

 LED 

Standby mode 

x1 green  flash  with a period of 8-9 
sec. 

Fire alarm 

x1 red flash with a period of 2 sec.  

Fire test 

x1  red  flashes  with  a  period  of  2 
sec. during 20 sec.  

Power failure 

x3 red flashes with a period of 25 
sec. at a supply voltage below 8 V 

Power failure 
SLC1 or SLC2 

x1 yellow flashes with a period of 3 
sec. at a short circuit or voltage 
below 8 V on the supply line L1 or 
L2 

Data lines 
SLC1 or SLC2 
failure  

x2 yellow flashes with a period of 3 
sec. at Data lines SLC1 or SLC2 
short circuit  

Circuit break 

Any possible variant from the table 

Command 
receiving from 
Laser pointer 
(LP) 

x1 red switching on for 2-5 sec 

5  ADDING TO THE SYSTEM 

1) 

Connect the RPA  to the Control Panel using RS-

485 interface.  
2)  Add the Astra-RPA to the Control Panel according to 
the user guide of the Control Panel Astra-812 Pro  or the 
PKM Astra Pro or Pconf-Pro PC built-in. Install the device 
at the selected location (see point 8, actions 1)-5)). 

Note: 
 It  is  recommended  to  install  all  Call  Points

 

before 

registration,  because  their  registration  is  carried  out 
using the Astra-942 (L P) and supplied separately. 
 

3) Run the Control Panel mode of Device Adding in the 
RPA  through  Astra  Pro  PKM  or  the  Control  Panel 

“Astra-812  Pro”  menu  in  accordance  with  the  Control 
Panel manual. 
It takes 60 sec to register a device. 
4) Run the registration Astra 

– 45A mode: 

-  press the lower button on the LP 
and hold it until the beam appears  