TSD-5150
OPTICAL SMOKE AND HEAT DETECTOR
( MULTISENSOR ) FOR INTRUDER ALARM SYSTEM
Installation & Operation Manual
Yayın Tarihi:
17/10/2018
Rev:01
Important Warnings
General
✓
Before using the device read this manual carefully. Keep it just in case of necessity.
✓
Abide all the rules and precautions stated in the manual. Follow all the instructions one by one.
✓
Keep the devices away from water and moisture
Conditions
Do not energize the device above or below the given limits of extreme hot or cold conditions,
Temperature
:
Between
-
10°C and +
70
°C
Relative Humidity:
%95 RH max
Service
Do not try to fix the device on your own. Removal of cover may end up with electricity shock.
In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical
interventions have to be done by technicians of company.
Malfunctions that require technical service
In case of any malfunction or below conditions contact with your authorized service,
✓
When Mains cable or the plug is harmed,
✓
Contact of device with a fluid,
✓
Exposure of rain and water,
✓
Fell down of device or harmed outer cover,
✓
Serious performance fall on the device,
✓
Depending on the instructions stated in manual, if your device not working properly
Contact with your authorized service in such terms.
Maintenance on your own
Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any
defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have
to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are
allowed for cleaning
Transportation
Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions
that caused by improper transportation is not under warranty.
Human and Environmental Health
This device contains no chemical or biological elements that could harm human condition.
General Features
✓
Advanced smoke detection algorithm that minimizes false alarms
✓
Detector can
generate an alarm at 55 ° C if constant temperature is selected. (A2S)
✓
Rejection of transient signals that can be detected as alarms
✓
Adaptive intelligent protection by constantly sampling the environment
✓
Dust algorithm and warning to understand that it is getting polluted and unable to detect
✓
Easy to clean smoke chamber
✓
Ability to connect an remote indicator
✓
Two leds used for status indicators
✓
15s start time
✓
Three sensitivity settings via panel
✓
The logic of working on the panel and / or
✓
Can only work as heat and smoke detectors only through the panel
✓
Compatible with TFA-0120 Universal Detector Base
Technical Features
Power Input
10V(min)
–
18V(max)
Average Current Consumption
10mA (@12V)
Contact Output
NC 1A-10W
Humidity
-10
C ~ +70
C (14
F ~ 158
F)
Ebatlar (mm)
Ø110, h42
Dimensions (mm)
White Color, ABS Plastic
Used Cable Cut
0.4mm ² ~ 1.5mm ²
Weight (incl. Base / excluding base)
184 gr / 126 gr
Start Time
15 sn
Indicator Leds
Blue Led
Red Led
When the unit is first energized for
15 s, while sampling the
environment
Blinks for 5s period
X
Any error condition
(dust or power failure)
Blinks for 1s period
X
In normal operating condition
Blinks for 20s period
X
In alarm condition
X
It is constantly lit
Terminals
Number 1
Negative (-) power input
Number 2
Alarm panel ZONE GND
Number 3
Alarm panel ZONE input
Number 4
Positive (+) power input
Number 5
Earth connection
Warning:
Do not attempt to remove the electronic board from its plastic case. The electronic board is
closed for your safety. Users should avoid from interference.