APS 400 Network Reader 

Configuration tool for APS 400 system modules 

User’s guide 

© 2004 – 2017, TECH FASS s.r.o., Czech Republic, www.techfass.cz, [email protected] 

(released on 2017/05/18, valid for build 1.0.6333.27347) 

Summary of Contents for APS 400

Page 1: ...0 Network Reader Configuration tool for APS 400 system modules User s guide 2004 2017 TECH FASS s r o Czech Republic www techfass cz techfass techfass cz released on 2017 05 18 valid for build 1 0 6333 27347 ...

Page 2: ... 3 3 Program options 4 4 Communication with network modules 4 4 1 Communication conditions 4 4 2 Connection parameters 4 4 3 Configurable modules 5 5 Configurable parameters 5 5 1 Operating mode 5 5 2 Internal reader configuration 7 5 3 Keypad function 7 5 4 WIEGAND interface configuration 8 5 5 Input output 3 function 8 6 Other program operation options 9 6 1 Connecting and disconnecting a module...

Page 3: ...APS 400 Network Reader can be used only with network modules with firmware version 2 70 or higher The system controller must be equipped with firmware version 227 or higher The communication with the network modules connected to the APS BUS is realized via the APS nServer NET program communicating with relevant MCA 168 system controller Pic 1 APS 400 Network Reader program ...

Page 4: ...of the APS 400 Network Reader program with the network modules is realized via the APS nServer NET program It is necessary to set up a correct connection to the MCA 168 system controller in the APS nServer NET program first Note Description of the APS nServer NET program installation and configuration is not a part of this manual detailed information are available at www techfass cz 4 2 Connection...

Page 5: ... providing own IDs reading determines the overall function of a module If a module is intended to work as a standard APS 400 module it is necessary to use the Standard operating mode system module Modules providing own IDs reading can also be configured in the WIEGAND reader mode in which the code of read ID is sent in one of selected formats using its WIEGAND output 5 1 1 Standard operating mode ...

Page 6: ...technology their format is defined by the internal reader configuration chapter 5 2 The user configuraiton of HID Proximity media format is used in all operating modes Table 2 IDs format in WIEGAND operation mode If the reader module features a keypad the key code is sent immediately after a key press as a 4 bit burst the highest bit comes first the values are binary encoded The key codes sent dif...

Page 7: ...onfiguration check the appropriate checkbox Set the indexes of the first and last used data bit Note User configuration of HID Proximity IDs reading requires a deeper knowledge of the issue therefore we recommend leaving the setting to an installation company 5 3 Keypad function Setting up the keypad function is only enabled where it is meaningful The keypad function setting can be set to one of t...

Page 8: ... bits 34 bits Parity bits cut off in front and at the back 32 bits 37 bits Parity bits cut off in front and at the back 35 bits 42 bits Parity bits cut off in front and at the back 40 bits 44 bits Last 4 bits cut off 40 bits 56 bits Data bytes reversed 56 bits Table 4 Accepted formats of read WIEGAND data standard configuration To enable user configuration check the appropriate checkbox Set the in...

Page 9: ... are indicated by grey color It is possible to command the controller to try to establish communication with a specific address in the network or to stop communicating with a specific address Relevant commands are available in the context menu after right clicking at the relevant address in the Network status area 6 2 HW address setting For problem free communication at the APS BUS it is necessary...

Page 10: ... set and the controller attempts to start the communication with a module at given address The second option is reading a confirmation ID at a reader in the HW address setting mode In the Set HW address dialog fill in the known ID of the confirmation card tag that will be used for the HW address setting After that select an unoccupied HW address in the Required HW address field from the range 1 64...

Page 11: ...x Note If a device occupies multiple addresses at the communication line and the upgrade file is a NML file it is necessary to connect and upload the license to every address the module occupies The procedure of uploading new FW to a device at a communication line is supported since the network modules FW version 2 73 The NIO 22 module does not support this function When uploading FW to a multi ad...