BEFORE USING THE PRODUCT

Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and warnings before 
using this product. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.

 

 DANGER

Never use this product in locations where flammable gas or ignitable substances are present.

  

INSTALLATION WARNING

When installing, ensure that work is done in accordance with the instruction manual. When installation is improper, there is

    risk of electric shock and fire.

Installation shall be done by Service personnel with necessary and appropriate technical training and experience. There is a 

    risk of electric shock and fire.

Do not cover the product with cloth or paper etc. Do not place anything flammable around. This might cause damage, 

    electric shock or fire.

  WARNING on USE

Do not touch this product or its internal components while circuit in operation, or shortly after shutdown. You may receive a 

    burn.

While this product is operating, keep your hands and face away from it as you may be injured by an unexpected situation.

For products with no cover, do not touch them as there are high-voltage and high temperature parts inside. Touching them

    might cause injury such as electric shock or burn.

There are cases where high voltage charge remains inside the product. Therefore, do not touch even if they are not in 

    operation as you might get injured due to high voltage and high temperature. You might also get electric shock or burn.

Do not make unauthorized changes to this product nor remove the cover as you might get an electric shock or might damage

    the product. We will not be held responsible after the product has been modified, changed or dis-assembled.

Do not use this product under unusual condition such as emission of smoke or abnormal smell and sound etc. Please stop

    using it immediately and shut off the product. It might lead to fire and electric shock. In such cases, please contact us. Do not
    attempt repair by yourself, as it is dangerous for the user.

Do not operate and store these products in environments where condensation occurs due to moisture and humidity. It might 

    lead fire and electric shock.

Do not drop or apply shock to this product. It might cause failure. Do not operate these products mechanical stress is 

    applied.

When necessary, this products is to be repaired only by us or our authorized agents. It is important that this product cannot 

    be used in hazardous environments (facilities such as nuclear power control system or life support equipment) without our
    written consent.

 

 CAUTION on MOUNTING

Confirm connections to input/buffer output and signal terminals are correct as indicated in the instruction manual before 

    switching on.

This product can only be connected to the specified power supply, and ambient temperature and ambient humidity should be 

    kept within specifications, otherwise the product will be damaged.

Input line/buffer output, please use the wires as short and thick as possible.

Do not use this product in special environment with strong electromagnetic field, corrosive gas or conductive substances and 

    direct sunlight, or places where product is exposed to water or rain.

Mount this product properly in accordance with the instruction manual, mounting direction and shall be properly be

    ventilated.

Please shut down the input and ensure that the internal voltage of the product is low when connecting this product.

When installing in environment where conductive foreign, dust and liquid may be present, please consider penetration of 

    above foreign material in the power supply by installing filter, to prevent trouble or malfunction.

Please check the connector is locked securely, and be careful the harness does not come off the connector after connecting.

1/12

A285-04-01

ZBM-AC Series

Instruction Manual

Summary of Contents for ZBM-AC Series

Page 1: ...emission of smoke or abnormal smell and sound etc Please stop using it immediately and shut off the product It might lead to fire and electric shock In such cases please contact us Do not attempt rep...

Page 2: ...hydrogen sulfide sulfur dioxide etc there is possibility that they might penetrate the product and lead to failure When used in environments where there is conductive foreign matter or dust there is p...

Page 3: ...ss applied directly to the product Please keep away from direct sunlight For long term storage temperature and humidity the following conditions shall be used as a guideline Temperature range 5 30 Hum...

Page 4: ...ed failure risk by foreign material Safety standard certification IEC UL EN CSA 62368 1 IEC EN62477 1 OVC Support hold up time for SEMI F47 1 3 Applications Applications Usage FA Robot controller Secu...

Page 5: ...e diameter 3 5mm Must be connected to Chassis Conductor of the equipment by electrically conductive spacer 4 Mounting hole hole diameter 3 5mm 5 RS Ready Signal 6 STB STBY Standby output voltage Optio...

Page 6: ...Sensing Photo coupler Photo coupler RS RS Signal Circuit Bulk Capacitors Rectifier Filter Circuit Switching Circuit Control Circuit STB STB STBY output Input Buffer output Option model S Input Voltag...

Page 7: ...ction 6 1 below 6 1 Wiring for power supply and buffer module For the harness that connects the power supply and this product it is necessary to use harness with withstand voltage of 400V or higher eq...

Page 8: ...of the standby power supply for signals is 24Vtyp 22 8V 25 2V and the maximum output current is 0 2A The ground of the standby power supply terminal for signals is the STB terminal The STB terminal is...

Page 9: ...een signal and terminal each for 1 minute When testing withstand voltage set current limit of withstand voltage test equipment at 10mA Signal terminal 20mA The applied voltage must be gradually increa...

Page 10: ...Insert the spacer Max 8 of height more than 8mm to lift the product And use all mounting holes for the product installation 1 Mounting Holes size 4 holes 3 5mm Allowable area by metal pieces is 9mm fr...

Page 11: ...unting holes for Chassis connection is shown with mark in below figure 9 Wiring Method 1 The input buffer output load line and signal line shall be separated and use all lines as thick and short as po...

Page 12: ...rect 3 Check if the wire size is not too thin 4 Check if the output current and output power does not over specifications Option model S 5 Audible noise can be heard during Dynamic Load operation Opti...