TFT HAND HELD AUTOMATIC
PRESSURE CONTROL NOZZLES

ULTIMATIC, MID-MATIC & HANDLINE

INSTRUCTIONS FOR INSTALLATION, SAFE OPERATION AND MAINTENANCE

WARNING

Read instruction manual before use. Operation of this nozzle without understanding the manual 
and receiving proper training can be dangerous and is a misuse of this equipment. Call 800-348-
2686 with any questions.

WARNING

This instruction manual is intended to familiarize fi refi ghters and maintenance personnel with 
the operation, servicing and safety procedures associated with the Ultimatic, Mid-Matic and 
Handline fi re fi ghting nozzles.

WARNING

This manual should be kept available to all operating and maintenance personnel.

TASK FORCE TIPS, INC.

MADE IN USA • www.tft.com

3701 Innovation Way, Valparaiso, IN 46383-9327 USA

800-348-2686 • 219- 462-6161 • Fax 219-464-7155

MID-MATIC

ULTIMATIC

HANDLINE

Summary of Contents for Ultimatic

Page 1: ...erous and is a misuse of this equipment Call 800 348 2686 with any questions WARNING This instruction manual is intended to familiarize firefighters and maintenance personnel with the operation servic...

Page 2: ...H SALT WATER 4 0 NOZZLE CONTROLS 4 1 FLOW CONTROL 4 1 1LEVER TYPE FLOW CONTROL 4 1 2TWIST SHUTOFF 4 1 3TIP ONLY NOZZLES 4 2 PATTERN AND FLUSH CONTROL 4 2 1PATTERN CONTROL 4 2 2FLUSH CONTROLS 5 0 USE O...

Page 3: ...ing sizes or connector styles can be specified at time of order Ultimatic Mid Matic and Handline nozzles are available in several models Some common models are shown in figure 1 CAUTION Nozzle must be...

Page 4: ...onnect or discharge 2 Preconnect or discharge 3 Preconnect or discharge 4 Preconnect or discharge 5 Preconnect or discharge 6 Preconnect or discharge 7 Foam Lines Orange Red Yellow White Blue Black Gr...

Page 5: ...rt approximate flows can be calculated using conventional hydraulics DANGER An inadequate supply of nozzle pressure and or flow will cause an ineffective stream and can result in injury death or loss...

Page 6: ...5 entitled Reach Trajectory Data of Hand Held Nozzles 3 2 USE WITH SALT WATER Use with salt water is permissible provided nozzle is thoroughly cleaned with fresh water after each use The service life...

Page 7: ...orted to verify operation in accordance with TFT test procedures Consult factory for the procedure that corresponds to the model and serial number of the nozzle Any equipment which fails the related t...

Page 8: ...ou TFT shall have no obligation under this limited warranty if the equipment is or has been misused or neglected including failure to provide reasonable maintenance or if there have been accidents to...

Page 9: ...approximate and do not reflect losses in preconnect piping FLOW GPM 75 PSI ULTIMATIC 100 PSI ULTIMATIC 75 PSI 100 PSI ULTIMATIC 125 Flow Chart 45M 45M 45M 60M 60M 60M 75M 75M 75M 8 6 24 41 21 34 17 3...

Page 10: ...S 100 PSI MID MATIC 75 PSI 100 PSI 75 PSI MID MATIC 250 202 104 221 96 174 90 198 79 155 80 179 69 218 112 194 100 215 91 Flow Nozzle Reaction Chart MID MATIC Flow Nozzle Reaction Chart MID MATIC 7 BA...

Page 11: ...80 307 330 352 375 395 20 44 108 135 165 191 219 247 275 Note For Nozzles with Serial TFT H465101 and or Manufactured after 12 01 2003 HANDLINE Flow Nozzle Reaction Chart 1 Number on top in each box i...

Page 12: ...grabber is free of debris 3 Coupling is tight and leak free 4 Valve operates freely through full range and regulates flow 5 OFF position does fully shut off and flow is stopped 6 Nozzle flow is adequa...