background image

S-RA1

Smoke Control Damper - AAsingle

Handbook

Summary of Contents for A-S-RA1

Page 1: ...S RA1 Smoke Control Damper AAsingle Handbook ...

Page 2: ...2 31 S RA1 Table of Contents Overview 3 Technical Parameters 5 Diagrams 7 Dimensions Weights 13 Ordering Code 15 Product Handling 16 Installation 18 Electrical Parameters 23 Operation Manual 29 ...

Page 3: ...ication Resistivity rating for damper installed on the duct E600 120 ved i o S1000 Cmod AAsingle Types of Activation B230 Smoke control damper with an activation mechanism with a Belimo actuator 230V AC and auxiliary switches B24 Smoke control damper with an activation mechanism with a Belimo actuator 24V AC DC and auxiliary switches B24 W Smoke control damper with an activation mechanism with a B...

Page 4: ... galvanized sheet metal rubber PE tapes and foil galvanized steel fasteners The manufacturing processes of these materials agree with local regulations The product does not contain dangerous materials Product Parts P6 P4 P7 P5 P3 P1 P2 A1 A1 2 A1 1 S RA1 GE1 S RA1 Legend P1 Damper casing P2 Damper blade P3 Actuator P4 Inspection lid P5 Communication unit only for BST0 activation type P6 Holder for...

Page 5: ...ess than 95 3K5 EN 60721 3 3 Product protected from Weather rain and water from other sources Condensation Cannot form on the product Icing Cannot form on the product Access for Inspection The inspection is possible through the grille when available or through an inspection opening on the damper body Connection and actuator accessible from outside Maintenance Maintenance is not necessary A dry cle...

Page 6: ...proven Duration 60 s 90 Operational reliability Cmod 20 000 cycles modulated Fire resistance E600 120 ved i o S1000 Cmod AAsingle Resistivity depends on installation method and situation integrity E maintenance of the cross section under E mechanical stability under E smoke leakage S Durability of response delay AA Automatic Activation Opening closure time proven Duration 60 s 90 Durability of ope...

Page 7: ...40 45 50 55 25 30 35 40 45 50 55 S RA1 B230 Pressure drop A weighted sound power level in dB A 300 500 1000 m h 100 200 300 l s 20 50 100 Pa Size 160 Size 180 Size 200 Size 250 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 S RA1 B230 Pressure drop A weighted sound power level in dB A 1000 2000 3000 m h 200 500 1000 l s 10 20 50 Pa Size 280 Size 315 Size 400 Si...

Page 8: ...dB A 50 dB A 55 dB A Size 200 0 Size 200 25 Size 200 50 Size 200 75 Size 200 100 S RA1 B24 SR Pressure drop A weighted sound power level in dB A 1000 2000 m h 250 500 750 l s 250 500 Pa 25 dB A 35 dB A 40 dB A 45 dB A 50 dB A 55 dB A Size 315 0 Size 315 25 Size 315 50 Size 315 75 Size 315 100 S RA1 B24 SR Pressure drop A weighted sound power level in dB A 2500 5000 7500 m h 400 800 1200 1600 2000 ...

Page 9: ...e 160 Size 180 Size 200 Size 250 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 S RA1 B230 Pressure drop A weighted sound power level in dB A 1000 2000 5000 m h 300 500 1000 l s 5 10 50 Pa Size 280 Size 315 Size 400 Size 450 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 S RA1 B230 Pressure drop A weighted sound power level ...

Page 10: ...0 dB A 55 dB A Size 200 0 Size 200 25 Size 200 50 Size 200 75 Size 200 100 S RA1 B24 SR Pressure drop A weighted sound power level in dB A 1000 2000 3000 m h 250 500 750 l s 100 200 300 400 Pa 25 dB A 35 dB A 40 dB A 45 dB A 50 dB A 55 dB A Size 315 0 Size 315 25 Size 315 50 Size 315 75 Size 315 100 S RA1 B24 SR Pressure drop A weighted sound power level in dB A 2000 4000 6000 8000 10000 m h 1000 ...

Page 11: ...s 20 50 100 Pa Size 160 Size 180 Size 200 Size 250 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 S RA1 B230 GE1 S RA1 Pressure drop A weighted sound power level in dB A 500 1000 2000 m h 200 300 500 l s 10 20 50 Pa Size 280 Size 315 Size 400 Size 450 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 25 30 35 40 45 50 55 S RA1 B230 GE1 S RA1 Pressu...

Page 12: ...dB A 45 dB A 50 dB A 55 dB A Size 200 0 Size 200 25 Size 200 50 Size 200 75 Size 200 100 S RA1 B24 SR GE1 S RA1 Pressure drop A weighted sound power level in dB A 500 1000 1500 m h 100 200 300 400 500 l s 250 500 750 Pa 25 dB A 35 dB A 40 dB A 45 dB A 50 dB A 55 dB A Size 315 0 Size 315 25 Size 315 50 Size 315 75 Size 315 100 S RA1 B24 SR GE1 S RA1 Pressure drop A weighted sound power level in dB ...

Page 13: ...A1 sold separately GE1 S RA1 is not part of the S RA1 delivery Inclusive grille S RA1 DN mm 100 125 140 150 160 180 200 225 250 280 315 355 400 450 500 560 630 R1 mm 40 28 20 15 10 0 10 23 35 50 68 88 110 135 160 190 225 R2 170 158 150 145 140 130 120 108 95 80 63 43 20 5 30 60 95 L1 270 290 340 400 450 520 L2 50 70 120 180 230 300 ...

Page 14: ... Grille m kg DN mm 100 125 140 150 160 180 200 225 250 280 315 355 400 450 500 560 630 S RA1 B230 B24 B24 SR 2 2 2 4 2 5 2 7 2 8 3 3 2 3 4 3 7 4 1 4 5 5 5 7 6 5 7 2 8 2 9 4 B24 W 2 3 2 5 2 6 2 8 2 9 3 1 3 3 3 6 3 8 4 2 4 6 5 1 5 8 6 6 7 4 8 3 9 5 BST0 3 3 2 3 3 3 5 3 6 3 8 4 4 2 4 5 4 9 5 3 5 8 6 5 7 3 8 9 10 2 Weights of S RA1 with GE1 S RA1 Accessory m kg DN mm 100 125 140 150 160 180 200 225 25...

Page 15: ...tuator B24 24V AC DC Belimo actuator B24 W 24V AC DC Belimo actuator wire connector for supply and communication unit B24 SR 24V AC DC Belimo actuator modulated 0 V 10 V BST0 230V AC supply and communication unit BKNE230 24 24V AC DC Belimo actuator Example of the Ordering Code S RA1 630 B24 SR Single compartment smoke control damper with nominal diameter 630 mm Activated by a 24 V modulated Belim...

Page 16: ...oke control damper with the forklift crane or manually Place the damper into the duct until the casings stop 4 Fixing the damper Note Make sure to continually check the alignment of the damper against the duct connection when performing the next steps Fix the damper to the duct using suitable self tapping screws through the duct installations in connection area Verify there is no skewing of the da...

Page 17: ...17 31 S RA1 2 1 1 2 3 4 5 6 i 2 F1 F1 1 2 F1 Legend for Product Handling 1 Smoke control damper S RA1 2 Connected metal ductwork F1 Screw M4 13 mm ...

Page 18: ...ing inspection must be considered during damper placement The minimum distance between the smoke control damper bodies installed in separate ducts must be 200 mm refer to Standard EN 1366 2 The minimum distance between the smoke control damper and the wall or ceiling must be 75 mm If the grilles are not original accessories there must be a minimum clearance between the damper blade in its open pos...

Page 19: ...ction surfaces 2 Follow instructions in Product Handling section 3 Perform damper s functionality check see Operation Manual section CAUTION Make sure that the closest hanger is placed not further than 150 mm from the duct connection If the hanger system is longer than 1 5 m fire resistant insulation is necessary see hanger manufacturer instruction Make sure that it is always possible to access th...

Page 20: ...2 2 1 A1 1 2 1 2 mm Y1 2 mm Y2 2 DMV 1 F1 2 1 F1 A1 F1 Y2 Y1 Y1 Legend for installation DMV 1 Smoke control damper S RA1 2 Connected metal ductwork A1 Extension with grille GE1 S RA1 sold separately F1 Screw M4 13 mm Y1 Y2 Cutting planes ...

Page 21: ...on surfaces 2 Follow instructions in Product Handling section 3 Perform damper s functionality check see Operation Manual section CAUTION Make sure that the closest hanger is placed not further than 150 mm from the duct connection If the hanger system is longer than 1 5 m fire resistant insulation is necessary see hanger manufacturer instruction Make sure that it is always possible to access the s...

Page 22: ...150 L2 2 2 mm Y D1V mm A1 2 1 F1 F1 F1 2 Y 1 2 Y 1 2 Y 1 A1 2 Y 1 A1 Legend for installation D1V 1 Smoke control damper S RA1 2 Connected metal ductwork A1 Extension with grille GE1 S RA1 sold separately F1 Screw M4 13 mm Y Cutting plane ...

Page 23: ... Handling section Electrical Parameters for Type of Activation and Actuator T NVF PC A DN mm 100 125 140 150 160 180 200 225 250 280 315 355 400 450 500 560 630 S RA1 B230 AC 230 V 50 60 Hz 7 VA BEN230 B24 AC 50 60 Hz DC 24 V 6 VA BEN24 B24 W AC 50 60 Hz DC 24 V 6 VA BEN24 ST B24 SR AC 50 60 Hz DC 24 V 6 5 VA BEN24 SR BST0 AC 230 V 50 60 Hz 19 VA BEN24 ST BKNE230 24 Notes T NVF PC A Activation Typ...

Page 24: ... When the power supply is connected to wires 1 and 2 the actuator moves to the CLOSED position Notes CAUTION Main power supply voltage Parallel connection of more actuators possible when the power consumption and switching threshold is observed Legend for Activation Type B230 1 blue 2 brown 3 white S1 violet S2 red S3 white S4 orange S5 pink S6 grey The Belimo BE230 actuator has wires without colo...

Page 25: ...n When the power supply is connected to wires 1 and 2 the actuator moves to the CLOSED position Notes CAUTION Main power supply voltage Parallel connection of more actuators possible when the power consumption and switching threshold is observed Legend for Activation Type B24 1 black 2 red 3 white S1 violet S2 red S3 white S4 orange S5 pink S6 grey The Belimo BE24 actuator has wires without colour...

Page 26: ...pply is connected to wires 1 and 2 the actuator moves to the CLOSED position Notes CAUTION Main power supply voltage Parallel connection of more actuators possible when the power consumption and switching threshold is observed Combination of power supply voltage and safety extra low voltage not permitted at the both auxiliary switches Legend for Activation Type B24 W The actuator has connection pl...

Page 27: ...UTION Main power supply voltage Parallel connection of more actuators possible when the power consumption and switching threshold is observed Operating range Y DC 0 2 10 V Input Impedance 100 kΩ Position feedback U DC 2 10 V Position feedback U note Max 0 5 mA Position accuracy 5 Legend for Activation Type B24 SR 1 black 2 red 3 white 5 orange S1 violet S2 red S3 white S4 orange S5 pink S6 grey Th...

Page 28: ...ctuator to the desired position Two LEDs in the device indicate the function status LED Status Function Yellow Flashing Damper moves OPEN Yellow On Damper OPEN Green Flashing Damper moves CLOSED Green On Damper CLOSED Yellow and Green Flashing at double frequency Fault Yellow and Green Off Power failure Notes CAUTION Main power supply voltage Parallel connection of more actuators possible when the...

Page 29: ...0 0 Damper Inspection CAUTION Never perform inspection when there is air flowing in the duct connected to the smoke control damper Do not change the dampers or their structure without the approval of the manufacturer The actuator keeps the dampers on stand by during their life cycle The operator obeys the applicable regulations and standards to do regular checks of the dampers The recommended mini...

Page 30: ... of the sealings If necessary correct the defects and record the results where applicable 8 Do a functional test of the damper open and close refer to the Smoke Damper Functionality Check chapter 9 Confirm the operation of the damper with the control system a Monitor the physical performance of the damper b Monitor the signals of the end positions c If necessary correct and record the defect where...

Page 31: ...Systemair DESIGN 2022 02 17 Handbook_S_RA1_en GB Original instructions ...

Reviews: