B200S-LF-WH, B200S-LF-IV

Low Frequency Intelligent Sounder Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BEFORE INSTALLING

Read System Sensor’s 

Applications Guide for System Smoke Detectors

 

(SPAG91), which provides detailed information on sensor spacing, placement, 
zoning, wiring, and special applications. This manual is available from System 
Sensor. NFPA 72 and NEMA guidelines should be observed. The National Fire 
Alarm Code, NFPA 72, requires effective January 1, 2014, that audible appli-
ances installed in sleeping areas produce a low frequency alarm signal that 
shall be a square wave or provide equivalent awakening ability with a funda-
mental frequency of 520 Hz +/– 10%.

NOTE:

 Select Series sounder bases are not compatible with remote test ca-

pable Select Series detectors.

NOTICE:

 This manual should be left with the owner/user of this equipment.

IMPORTANT:

 The detector used with this base must be tested and maintained 

regularly following NFPA 72 requirements. The detector should be cleaned at 
least once a year.

GENERAL DESCRIPTION

The B200S-LF-WH and B200S-LF-IV sounder bases are used with addressable 
detector heads. For a list of compatible sensors, refer to the System Sensor 
website at www.systemsensor.com. Refer to the appropriate manual for more 
information on sensors.

The B200S-LF-WH/B200S-LF-IV low frequency sounder base generates a low 
frequency tone around 520 Hz. Studies have shown that low frequency au-
dible devices that operate around 520 Hz are more effective in waking indi-
viduals in sleeping areas.

The sounder base is capable of producing a variety of tone patterns, includ-
ing the distinctive three-pulse temporal pattern (ANSI Temporal 3) fire alarm 
signal now required by NFPA 72 for commercial and residential applications. 
The B200S-LF-WH/B200S-LF-IV offers maximum flexibility in configuration 
and operation to meet or exceed the requirements of UL268 and UL464 for 
Continuous, Temporal 3 and March time patterns. The temporal 4 pattern 
meets all requirements of UL268 and UL2075, as well as, private mode setting 
of UL 464.

The B200S-LF-WH/B200S-LF-IV can be commanded by the Fire Alarm Con-
trol Panel (FACP) to adopt the address of the attached sensor head, but as 
a unique device type on the loop. By using the address, the FACP can com-
mand an individual sounder base to activate, or a group of sounders in a suite 
or other multi-room configuration. The command set from the panel can be 
tailored to the specific event, allowing selection of volume, tone, and group. 
The device offers two volume levels: 75 dBA and 85 dBA. The available tones 
are Continuous, ANSI Temporal 3, ANSI Temporal 4, and March Time. In ad-
dition, some panels will offer the ability to command a custom tone pattern. 
Refer to the appropriate FACP manual for more information.

SPECIFICATIONS

Base Diameter: 

6.875" (17.46 cm)

Base Height (less sensor): 

2.0" (5.08 cm)

Weight: 

0.6 lb. (272 gm)

Operating Temperature Range:  Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com
Operating Humidity Range: 

10% to 93% relative humidity (non-condensing)

External Supply Electrical Ratings

External Supply Voltage: 

16 to 33 VDC (VFWR)

Standby Current: 

550 μA maximum VDC

Alarm Current: 

High volume setting:  70 mA maximum @ 33.0 VDC 

Low volume setting:  15 mA maximum @ 33.0 VDC

 

 

90 mA maximum @ 24.0 VDC 

 

20 mA maximum @ 24.0 VDC

 

 

140 mA maximum @16.0 VDC 

 

25 mA maximum @ 16.0 VDC

SLC Electrical Ratings

SLC Operating Voltage: 

15 to 32 VDC

SLC Standby Current: 

300 μA maximum (base only, refer to applicable sensor specification)

Sound Output

High Volume: 

Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)

Low Volume: 

Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)

In addition, the B200S-LF-WH/B200S-LF-IV is equipped with the circuitry to 
recognize the System Sensor synchronization protocol, enabling the sounder 
base to be used as a component of the general evacuation signal – producing 
an NFPA 72 compliant Temporal 3 pattern in synchronization with other 
System Sensor notification devices. This requires connection to a power 
supply capable of generating the System Sensor synchronization pulses, a 
FACP NAC output configured to System Sensor synchronization protocol, or a 
separate synchronization module. 

The sounder base is intended for use with intelligent systems. In addition to 
being connected to the SLC, the sounder base requires a connection to either 
24 VDC constant power or a NAC circuit, depending on the FACP and intended 
use. The connections for 24V constant/NAC power and the communication 
loop are isolated to prevent electrical interaction between them. 

When connected to a NAC, power is supervised via the NAC circuit supervi-
sion while in standby mode (EOL resistor required for Class B operation). 
When activated, the B200S-LF-WH/B200S-LF-IV provides supervision of NAC 
power. (See Figure 5.) 

When using a FACP equipped with a “sounder base standby power monitor-
ing” mode and constant 24 V power, power supervision EOL devices (super-
vision relays and resistors) should not be used. (See Figure 4.) In this case, 
the B200S-LF-WH/B200S-LF-IV will provide supervision in both standby and 
alarm/active mode. Refer to FACP installation documentation to determine if 
this mode is available. If your FACP does not support this mode or you choose 
not to use it, power supervision relays and EOL resistors are required to pro-
vide supervision in standby mode.

NOTE:

 If the FACP’s “sounder base standby power monitoring” mode is en-

abled, connecting B200S-LF-WH/B200S-LF-IV low frequency sounder bases 
to the NAC will result in power supervision failure when in standby. Only 
connect B200S-LF-WH/B200S-LF-IV low frequency sounder bases to constant 
24 V power in this case. Refer to the FACP manual for maximum allowable 
number of units per loop.

NOTE:

 For NFPA72 Installations, the Temporal 3 tone at high volume should 

be used for public mode evacuation. The use of other tone styles and low 
volume level will be at the discretion of the local Authority Having Jurisdic-
tion (AHJ).

NOTE:

 When not used as a supplementary evacuation system, the external 24 

VDC supply shall be treated as a component of the main power supply system 
and shall fall under the requirements of the main power supply system per 
NFPA 72.

I56-4

15

1-00

5

This model is compatible with System Sensor Models MDL, MDL3R, MDLW, MDL3W and SYNC-1

  

I56-4151-005 

 

 02/01/2018

firealarmresources.com

Summary of Contents for B200S-LF-WH

Page 1: ...g External Supply Electrical Ratings External Supply Voltage 16 to 33 VDC VFWR Standby Current 550 μA maximum VDC Alarm Current High volume setting 70 mA maximum 33 0 VDC Low volume setting 15 mA maximum 33 0 VDC 90 mA maximum 24 0 VDC 20 mA maximum 24 0 VDC 140 mA maximum 16 0 VDC 25 mA maximum 16 0 VDC SLC Electrical Ratings SLC Operating Voltage 15 to 32 VDC SLC Standby Current 300 μA maximum b...

Page 2: ...ble smoke sensor as described in the installation manual for the sensor CAUTION Do not over tighten mounting plate screws this may cause mounting plate to flex TAMPER RESISTANT FEATURE NOTE Do not use the tamper resist feature if the removal tool is to be used This detector base includes a tamper resist feature that prevents its removal from the base without the use of a tool To activate this feat...

Page 3: ...NAL REMOTE ANNUNCIATOR MODEL RA400Z 100Z E O L A SEPARATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE THE SYNCHRONIZATION PULSES HORN HORN STROBE UL LISTED COMPATIBLE CONTROL PANEL UL LISTED 24V POWER SUPPLY WHEN USING 24V CONSTANT POWER AUX POWER ADDITIONAL POWER SUPERVISION RELAYS AND MODULES WILL BE REQUIRED FOR PROVIDING SUPERVISION WHEN THE SOUNDER BASES ARE INACTIVE CLASS A OPTIONAL WIRING...

Page 4: ...tial or incidental damages for breach of this or any other Warranty expressed or implied whatsoever even if the loss or damage is caused by the Company s negligence or fault Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other ri...

Reviews: