background image

GB.TBLZ49.091201

We reserve the right to alter specifications without notice.

www.swegon.com     1

150

146

180

27

85

154

35

Smoke detector installation TBLZ-2-49-a  
GOLD/COMPACT

1. General

Smoke detector TBLZ-1-49-a is used to measure smoke 
gases in ventilation ducts. It consists of an optical detector 
mounted in an adapter system in which both the tube and 
enclosure are designed for optimum airflow through the 
detector. The system meets all fire safety requirements at 
air speeds between 0.2m/s and 20m/s. The smoke detec-
tor is used together with a control unit (installed in equip-
ment cubicle ELQA or separate equipment cubicle for 
smoke function) for controlling fans, smoke and combus-
tion gas dampers.

Accessories

Use an installation bracket when installing on circular or 
insulated ducts.

2. Function

When combustion gas is detected the LED on the detector 
lights red and the alarm signal is forwarded to the control 
unit.
If the smoke detector becomes dirty, it becomes more sen-
sitive and switches to alarm mode more slowly. To prevent 
false alarms if dirty, the detector is equipped with a service 
alarm (green LED). This indicates that the detector requires 
cleaning.

3. Technical Data

Detector type 

 

Optical

Operating voltage 

24VDC (from control unit)

Power consumption: 

 

In-operation 

 

Max 0.04mA

Service alarm 

 

~ 13mA

Combustion gas alarm  ~ 50mA
Ambient
temperature 

 

-20°C to +50°C

Humidity 

 

Max 99% rH

Degree of protection 

IP54

Weight 

  800g

Dimensions

Venturi tube length of 600 mm or 1500 mm.

(All dimensions are given in mm)

4. Maintenance

When the smoke detector becomes dirty, it becomes more 
sensitive and may trigger the service alarm. This can be 
delayed by vacuuming the detector once a year.

Summary of Contents for TBLZ-1-49-a GOLD

Page 1: ...cket when installing on circular or insulated ducts 2 Function When combustion gas is detected the LED on the detector lights red and the alarm signal is forwarded to the control unit If the smoke detector becomes dirty it becomes more sen sitive and switches to alarm mode more slowly To prevent false alarms if dirty the detector is equipped with a service alarm green LED This indicates that the d...

Page 2: ...he duct see example of inter fering sources below in the direction of airflow is the same as 3 x the duct s hydraulic diameter Nearest location after an interfering source must be at least 5 x the duct s hydraulic diameter MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh MIN 5xdh GX MIN 3xd h GX MIN 5xdh GX MIN 3xd h GX GX MIN 3xdh G...

Page 3: ...tector on the duct Secure the detector box at 3 points at the markings of the arrows Important IMPORTANT The direction arrows see the shape of the detector s base or the top of the housing must point in the same direction as the air flow in the duct End plug Stop screw Seal 5 Flow indicator The detector is equipped with an indicator a red plastic tab which when the detector is correctly installed ...

Page 4: ...resistance is 2 2kΩ from the control unit Check that the control unit is OK by installing the 2 2kΩ resistor in the smoke detector output on the control unit Use a voltmeter to check that 21 24 VDC with the cor rect polarity is in terminal 1 and terminal 2 10 8 9 The installation bracket is supplied flat The installation bracket is easy to bend shape so that it fits circular or flat ducts Secure t...

Reviews: