SL8SA- INSTRUCTIONS 

Page 1 of 4 

 

CONTROLLER MOUNTING: 

The  controller  enclosure  must  be  firmly  attached  to  a  nearby  solid  fixture  by  either  the  two  mounting  lugs  or  direct 
attachment  though  the  controller.  If  mounting  through the controller ensure the power cord is disconnected from the 
mains  supply  then  remove  the  enclosure  front  cover  by  turning  the  four  corner  locks  so  each  arrow points to the ‘O’ 
marked on the front cover. Insert two mounting screws diagonally through the oval holes in the enclosure, refit front 
cover and turn the four corner locks to the ‘I’ position.

 

The

 

power cable is 1.8m long and should be plugged directly into a general power outlet, not into an extension lead. 

 

CIRCULATING PUMP: 

The solar circulating pump plugs into the right hand 240Vac socket marked as SOLAR PUMP. The left hand 240Vac 
socket marked as AUXILIARY supplies 240Vac at all times. The maximum combined current is 10 AMPS 2400W. 
 

TEMPERATURE SENSORS: 

The solar pool sensor must be fitted into the suction line of the solar boost pump, preferably in a position out of direct 
sunlight.  The  aux  pool  sensor  must  be  fitted  into  the  suction  line  before  the  pool  pump  (filtration  pump).  It  is 
recommended that a 14.5mm hole be drilled in the PVC pipe, this can be carried out using a Dontek PD01 grinding drill 
or a small pilot hole can be drilled and a 14.0mm drill-bit used spinning in a counter clockwise direction to minimize the 
chance of shattering pipe. Insert the grommet into the pipe and gently push in the black sensor barb. The green solar 
pool  sensor  plug  is  to  be  fitted  to  the  plug  socket  marked  POOL.  The  aux  pool  sensor  plugs  into  the  socket  marked 
RELAY1 (Black to NO, White stripe to C). 
Roof sensor must be fitted into a small piece of rubber collector material away from the main collector but on the same 
aspect. Keep in mind that it is of the utmost importance to keep the roof sensor cable as short as possible as this will 
assist  in  the  longevity  of  the  sensor  and  controller  in  the  event  of  electrical  storm  activity  and  power  surges.  Sensor 
cables 

must not be run parallel to power cables

 

and run lengths should be less than 50m. Cable ties should be used to 

fasten  the  sensor  cable  to  the  cold  water  inlet  pipe  making  sure  that  the  ties  are  approximately  10mm  from  PVC 
fittings. Cable ties should be tightened only firm, over tightening can cause breaks in the outer PVC if not careful. If the 
cable  is  to  be  run  under  ground  a  conduit  must  be  used  to  protect  the  wire  and  there  is  to  be  no  cable  joins  within, 
conduit ends 

must

 be sealed to prevent water ingress

. Any excess cable should be removed and re-fitted ensuring that 

the wire ends are tinned with solder. 

The sensor plug is to be fitted to the right hand socket marked ROOF. 

 

FLOW SWITCH

The flow switch must be fitted after the pool/spa valve into the pool return line, the arrow on the flow switch indicates 
the direction of water flow. The green plug will go into the FLOW socket on the controller. 
 

HEATER INTERLOCK: 

The  heater  interlock  cable  connects  in-series  to  the  existing  internal  flow  or  pressure  switch  inside  the  heater, 
connection  varies  depending  on  model,  contact  heater  manufacturer  for  details,  maximum  switching  capability  of  the 
controller is 5 AMP at 32VAC MAX! If the heater exceeds this then the 240V switching option is to be fitted. 
The green plug on the heater interlock cable connects to the socket marked RELAY2 (NO/C). 
 

OPTION - IHP: 

An optional IHP connects to the DATA socket of the controller; ensure to match the colours to avoid damage. Do not 
run near 240Vac wiring. 

 
DESCRIPTION: 

The Solar is for heating the pool only and will operate as a standalone system. If water flow is detected by the flow 
switch then the aux pool temperature sensor is used; and if there is no solar gain the aux heater will be enabled if 
within the selected timeframe of heat demand and only if the pool temperature is below the aux limit setting. 
If there is solar gain available then the heater will run in conjunction with the solar but will turn off when the roof 
temperature exceeds 15°C above the solar temperature limit setting. When the flow switch detects that water flow has 
stopped going into the pool then the heater is enabled to heat the spa to the higher temperature limit as set at the aux 
heater. 
 

SOFTWARE SETTINGS:

 

To enter the SETTINGS MENU push either the 

Up or Down

 buttons and the following will be displayed; 

 

SETTINGS MENU 

1) MANUAL MODE 

 
Use 

Up or Down

 buttons to scroll to the option you wish to change. Press the 

Enter

 button to select the currently 

displayed menu item. 
 
All menu items are shown below; 
 

SETTINGS MENU 

1) MANUAL MODE 

2) TEMPERATURES 

3) AUX. HEATER 

4) MODE 

5) SYSTEM SETUP 

6) SAVE & EXIT 

 