Installation Manual

 

 

 

 

Type

DR-UPS40 DIN rail peripheral

 

DR-UPS40   

DC INPUT

24-29V  

40A   

BATTERY IN/OUT

0

~

40A   

 

 

Introduction 

DR-UPS40 is a DIN rail periphera

l

 

 

for

   

the UPS module. 

Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a 
heat source 

2

The  appropriate  mounting  orientation  for  the  unit  is  vertical,  the  TB1  terminals  at  the  bottom.  Mounting 

orientations other than that, such as upside down, horizontal, or table-top mounting, is not allowed. 

 
 
 
 
 
 

 

 

3

Use copper wire only, and recommended wires are shown as below. 

AWG 

18 

16 

14 

12 

10 

 

 

 

 

 

Rated Current of 
Equipment (Amp) 

7A 

10A 

15A 

20A 

30A 

40A 

55A 

 

 

 

 

Cross-section of 
Lead(mm

2

 ) 

0.8 

1.3 

2.1 

3.3 

5.3 

8.4 

13.3 

 

 

 

 

Note: 1. Current each wire carries should be de-rated to 80% of the current suggested above when using 

5 or more wires connected to the unit. 

2. The maximum allowable wire cross-sectional area for the terminal of the TB2 is 12AWG/3.3mm

3. The maximum allowable wire cross-sectional area for the terminal of the TB1 is 6AWG/13.3 

 

 

 

 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely  fixed  to  prevent  poor  contact.  If  the  power  supply  possesses  multi-output  terminals,  please  make 
sure each contact is connected to wires to prevent too much current stress on a single contact.   

4

Use wires that can withstand temperatures of at least 80°C, such as UL1007. 

5

Recommended wire strapping length is 5mm (0.197”). 

6

Recommended screwdriver is 4mm, slotted type. 

7

The recommended torque setting for terminals is 10kgf-cm(9Lb-in). 

TB1 

TB2 

18kgf-cm (15.5Lb-in) 

5kgf-cm (4.4Lb-in) 

 
 
 
 
 
 