P/N 315-086275-3

Operation

The 

 Model ZN-31U Dual Contact Zone mod-

ule is designed to provide two detector line circuits incor-

porating  contact  type  devices  and  a  similar  output  for

zone trouble. The contact type devices may be manual

stations,  waterflow  switches,  thermal  detectors,  relay

contacts, etc.
Upon  operation  of  any  shorting  type  device  installed  in

the detection circuit, the system will lock into alarm condi-

tion,  initiating  the  start  of  the  sequential  functions  de-

signed into the system, such as ringing alarm bells, oper-

ating  coded  alarm  transmitters,  closing  doors,  shutting

down fans and equipment, recalling elevators, etc. In ad-

dition to the sys-tem alarm, the red LED alarm lamp on

the face of the module for the particular zone under alarm

will be illuminated. The module also provides a current-

limited output signal for the zone under alarm for activat-

ing a supplementary alarm relay module or annunciator

module. The zone alarm indicating circuits and signaling

lamps are reset from the system control panel.
The yellow LED trouble lamps (one for each circuit) will il-

luminate should a break occur in the detector lines. Such

a condition will initiate a system Trouble signal. The yel-

low LED Trouble Indicators will be extinguished upon res-

toration of circult integrity or upon receipt of any system

alarm.

Note:

In the event of an AC power failure and standby

battery operation, the LED Trouble Indicator is not operative.

Both red and yellow LEDs can be lamp tested from the

system control panel.

Installation

1. Mount  the  module  to  the  horizontal  mounting

brackets in the control enclosure.

2

.

Install the Model JA-5 (5 in long) bus connector cable

assembly between receptacle P2 of the module and

receptacle P1 of the module or control panel immedi-

ately preceding it in the bus.

Note:

If the preceding module is on another row in the enclosure, a JA-24

(24 in long) bus connector cable assembly will be required.

3. Modules are to be bus-connected from right to left. For

two-row enclosures, the modules in the lower row are to

be connected from left to right. Succeeding rows are to

be alternately connected, right to left, left to right, etc.

4. If a module is the last module in the system, install either

a JS-30 (30 in long) or JS-64 (64 in long) bus connector

assembly from the unused receptacle of the last module

to terminal 41 of the CP-35 control panel. This completes

the module supervision circuit.

5. Wire  the  circuit(s)  as  described  in  the  CP-35  Control

Panel Instruction Manual, (P/N 315-085063), 

Installation

and Wiring.  

Refer to the Wiring illustration.

Note: 

If a zone is not used, the EOL device should be connected to the

alarm initiating circuit

 

terminals 2 and 3 (Zone 1) or 4 and 5 (Zone 2) of the

module.

6. If  a  supplementary  relay  module,  annunciator,  or  other

output module is used, then the alarm outputs, terminals

1 (Zone 1) and 6 (Zone 2), should be connected to these

units.

Wiring Test

Refer to the CP-35 Control Panel Instruction Manual, 

Installa

-

tion and Wiring.

Troubleshooting

Refer to 

Troubleshooting the System, 

in the Instruction

Manual for the Control Panel (P/N 315-085063).
1. An open or high line resistance will cause trouble.
2. Check open lines for 5.6K ohms end of line device (EL-31),

approximately 6mA supervisory current.

Fire Safety

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN

Operation and Installation Instructions

Model ZN-31U

Dual Contact Zone Module