SITRANS

Remote Displays

SITRANS RD100

Operating Instructions   01/2011

Summary of Contents for SITRANS RD100

Page 1: ...SITRANS Remote Displays SITRANS RD100 Operating Instructions 01 2011 ...

Page 2: ...und version and in electronic version We encourage users to purchase authorized bound manuals or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Siemens Milltronics Process Instruments will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions While we have verified the contents of this manual fo...

Page 3: ...ration of SITRANS RD100 Remote Display The manual is designed to help you get the most out of your Remote Display and it provides information on the following Meter specifications Wiring diagrams Installation requirements Setup instructions If you have any questions comments or suggestions about the manual content please email us at techpubs smpi siemens com For the complete library of Siemens Mil...

Page 4: ... Mounting Standard wall mount Optional panel mounting kit does not provide NEMA 4X seal to panel 2 pipe mounting kit Entity Parameters Vmax 30 V Imax 175 mA Ci 0 µF Li 0 µH Pi 1 3 W Input 4 to 20 mA Maximum Input Current 30 V DC Maximum Voltage Drop 1 V at 20 mA Connections Screw terminal block Operating Temperature Range 40 to 85 C 40 to 185 F 40 to 40 C 40 to 104 F for Canadian installations Not...

Page 5: ...y 0 1 of span 1 count Conversion Rate 2 5 conversions per second Approvals Intrinsically Safe FM CSA Class I II III Division 1 Groups A to G T4 FM CSA Class I Zone 0 Group IIC Non incendive FM CSA Class I Division 2 Groups A to D FM CSA Class II and III Division 2 Groups F and G See RD100 Remote Display Approval Connections Control Drawing shipped with the unit and located on the Instruction Manua...

Page 6: ...985JU01 Mounting Wall Mounting Dimensions A 80 mm 3 15 C 60 mm 2 36 E 65 mm 2 56 B 140 mm 5 51 D 120 mm 4 72 F 20 mm 0 79 Wall mounting holes Ø 4 mm 0 16 Weight 340 g 12 oz SIDE VIEW wall mounting holes beneath cover screws FRONT VIEW B D F E A C ...

Page 7: ...s needed to allow for panel thickness Notes The optional panel mounting kit does not provide a NEMA 4X seal to panel Mounting brackets require 20 mm 0 8 clearance on either the top or the side of the meter for installation Allowable panel thickness 1 5 mm 3 2 mm 0 060 0 125 Mounting plate dimensions 163 3 mm x 102 9 mm x 3 2 mm 6 43 x 4 05 x 0 125 Panel cutout required 138 4 mm x 77 5 mm 5 45 x 3 ...

Page 8: ...ration control HI calibration control balance control factory adjust only DP2 DP3 DP1 S S black red S S S S loop jumper input signal PCB mounted to base of enclosure calibrated current source input signal PCB Field wiring is made to the input signal PCB which is mounted to the base of the enclosure power supply transmitter 4 20 mA loop jumper S Hazardous area Non hazardous area S S S remove when d...

Page 9: ...play PCB Electrostatic hazard Clean only with a moist cloth Protect enclosure from exposure to chemical solvents and excessive ultraviolet UV light such as sunlight display PCB component side calibrated current source S S DP2 DP3 DP1 The display PCB may be removed from the enclosure for bench calibration Loop jumper must be installed on input signal PCB to maintain loop Refer to Servicing display ...

Page 10: ...is labeled DP1 DP2 DP3 Place a jumper over both pins of DP1 for a display of 199 9 DP2 for 19 99 or DP3 for 1 999 Calibration LO and HI calibration controls are located to the left of the display see Calibrator connected to input signal PCB on page 6 1 Apply a signal equal to 4 mA and adjust the LO control to display the desired reading 2 Apply a signal between 16 and 20 mA and adjust the HI contr...

Page 11: ... 5 Restore enclosure cover to the base to prevent contamination of components Restoring display PCB to the loop 1 Loosen the four screws on the enclosure cover and remove the cover 2 Secure display PCB to enclosure using right side screw do not tighten screw to allow rotation of display PCB while accessing input signal PCB 3 Connect red wire to S terminal and black wire to S terminal as shown in C...