SITOP power flexi 

A5E38522987, 11.2016 

 

 

 

 

SITOP  power flexi

 

6EP1353-2BA00 

 

 

 

Betriebsanleitung 

A5E38522987 

Operating Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

https://support.industry.siemens.com

 

 

 

 

 

 

 

 

 

Summary of Contents for SITOP power flexi

Page 1: ... Siemens AG 2016 1 8 SITOP power flexi A5E38522987 11 2016 SITOP power flexi 6EP1353 2BA00 Betriebsanleitung A5E38522987 Operating Instructions https support industry siemens com ...

Page 2: ...mens Niederlassung bzw über die Homepage http www siemens de sitop Technische Änderungen jederzeit vorbehalten In Zweifelsfällen gilt der deutsche Text Note These operating instructions cannot claim to cover all details of the product nor to provide for every possible contingency to be met in connection with installation operation or maintenance For more information please contact your local Sieme...

Page 3: ... bei Volllast und 230V 75 Einschaltstrombegrenzung 25 C serienmäßig bei 230V 32A 0 8A2 s Netzseitig empfohlener LS Schalter 6A Charakteristik C Eingangsstrom bei 120 230V 2 2 1 3A Leistungsaufnahme 138W Gewicht 0 75kg Ausgangsgrößen Ausgangsgleichspannung Auslieferzustand 24V 1 Nennspannung einstellbar mittels Schraubendreher an Potentiometer UA Gerätevorderseite Position siehe Seite2 im Bereich 3...

Page 4: ... 0 52VDC X2 2 X2 3 Sense Senseleitungs Anschluss Ermöglicht die Kompensation von Spannungsabfällen infolge Leitungswiderständen Maximale Spannungsausregelung 0 5V je Leitung Weitere Hinweise siehe Abb 2 Sense Leitungs Anschluss Seite 7 X2 4 Sense X2 5 UH Klemme derzeit nicht belegt ohne Funktion X2 6 Power Good Power Good Signal Potentialfreier Relaiskontakt ist geschlossen wenn die Ausgangsspannu...

Page 5: ...Limitation of inrush current 25 C standard at 230 V 32A 0 8A2 s Recommended circuit breaker on supply side 6A characteristic C Input current at 120 230 V 2 2 1 3A Power consumption 138 W Weight 0 75kg Output variables DC output voltage As delivered conditions 24 V 1 rated voltage adjustable by means of screwdriver at potentiometer UA front of device For position see page2 in the range 3 to 52 V Ri...

Page 6: ...voltage of 0 to 52 VDC X2 2 X2 3 Sense Sense cable connection enables compensation of voltage drops due to cable resistance Maximum voltage correction 0 5 V per cable More details see figure 2 sense connection page 7 X2 4 Sense X2 5 UH Terminal not assigned at the present time without any function X2 6 Power Good Power good signal floating relay contact is closed if the output voltage is within th...

Page 7: ...s Anschluss 1 max Spannungsausregelung 0 5V je Leitung d h der Lastleitungsquerschnitt ist so zu wählen das der Spannungsabfall bei Volllast je Leitung max 0 5V beträgt 2 bei Verwendung eines Schaltelements in der Lastleitung müssen Lastleitung und Sense Leitung gemeinsam weggeschaltet werden Note for connecting sense line 1 max voltage correction 0 5 V per load line so ensure that less than 0 5V ...

Page 8: ...er flexi A5E38522987 11 2016 Siemens AG Österreich AT 1210 Vienna Austria All rights reserved Liefermöglichkeiten und technische Änderungen vorbehalten Availability and technical specifications subject to change without prior notice ...