SICAM FCM Current-Transformer Adapter, Accessory
E50417-X8950-C590-A2, Edition 06.2018

              Page  1

SICAM FCM Current-Transformer Adaptor
Manual

s

The current-transformer (CT) adaptor is delivered with SICAM FCM as an optional accessory and can be ordered with
separate MLFB numbers 6MD2320-0AA10-1AA0 for 1 A and 6MD2320-0AA20-1AA0 for 5 A.
The CT adaptor acts as an interface between the primary CT and SICAM FCM to convert the secondary value of 1A/5A into
a IEC 60044-8 standard conform low power signal, which is measured in SICAM FCM.
Installation Procedure

s

Before installing the CT adaptor, make sure that SICAM FCM is powered-off.  To install the CT adaptor with the SICAM
FCM, execute the following procedure:
1. Replace the 4 rear screws with the 4 threaded bolts in the order (diagonal to each other).  Secure the 4 screws and

reuse in assembling CT adaptor to SICAM FCM.

NOTE
The maximum torque required for tightening the 4 thread bolts to SICAM FCM is 0.35 Nm.

2. Carry out the electrical connections of the 3 current inputs, 3 voltage inputs, 1 digital input, 2 digital outputs, 1 RS485

interface (Modbus RTU), 1 auxiliary power supply connection on the rear side of SICAM FCM.

3. Carry out all the necessary electrical connections of the cable assembly as per the following color coding of the wires.

Colour Coding

Description

Brown

Connect cores to terminal 13 (I

1

), 14 (I

1

N) of SICAM FCM

Blue

Connect cores to terminal 15 (I

2

), 16 (I

2

N) of SICAM FCM

Orange

Connect cores to terminal 17 (I

3

), 18 (I

3

N) of SICAM FCM

NOTE
When terminating the connector; ensure that the wires of the cable assembly are not twisted.

4. Fix the CT adaptor to SICAM FCM by using the 4 SICAM FCM screws with a maximum torque of 0.35 Nm.
5. Connect the cable assembly to the CT adaptor.
6. Before installing the primary CT wires at the CT adaptor, ensure that the primary CTs are short-circuited to avoid safety

problems.

NOTE
The 4 threaded bolts and the cable assembly are delivered with the CT adaptor.

NOTE
Always ensure the polarity when installing the primary CT cable and also follow the direction information as
mentioned on the adaptor card.

Figure 1-1 Components of the Current-Transformer Adaptor SICAM FCM

Cable Assembly

Threaded Bolt

CT Adaptor PCB

Summary of Contents for SICAM FCM

Page 1: ...e 3 current inputs 3 voltage inputs 1 digital input 2 digital outputs 1 RS485 interface Modbus RTU 1 auxiliary power supply connection on the rear side of SICAM FCM 3 Carry out all the necessary electrical connections of the cable assembly as per the following color coding of the wires Colour Coding Description Brown Connect cores to terminal 13 I1 14 I1N of SICAM FCM Blue Connect cores to termina...

Page 2: ... A 1 5 A 3 Storage temperature range 40 C to 85 C Accuracy range 1 A 0 4 A to 8 A 5 A 0 4 A to 50 A Humidity range 0 to 95 non condensing Frequency 50 Hz 60 Hz Altitude above sea level Maximum up to 2000 m Thermal overload 100 A for 1 s Rated output 225 mV Consumption per phase and ground path 0 1 VA at ΙN 1 A 0 5 VA at ΙN 5 A 1 3 Safety 1 4 Dimensions Characteristics Specifications Characteristic...

Page 3: ...lausgänge 1 RS485 Schnittstelle Modbus RTU 1 Hilfsspannungsversorgungsverbindung auf der Rückseite des SICAM FCMs her 3 Stellen Sie alle erforderlichen Verbindungen des Kabelsatzes gemäß folgender Farbcodierung der Leiter her Farbcodierung Beschreibung Braun Adern an Klemme 13 I1 14 I1N am SICAM FCM anschließen Blau Adern an Klemme 15 I2 16 I2N am SICAM FCM anschließen Orange Adern an Klemme 17 I3...

Page 4: ...ereich 40 C bis 85 C Genauigkeitsbereich 1 A 0 4 A bis 8 A 5 A 0 4 A bis 50 A Feuchtebereich 0 bis 95 nicht kondensierend Frequenz 50 Hz 60 Hz Höhe über dem Meeresspiegel Maximal bis 2000 m Thermische Überlast 100 A für 1 s Nennlast 225 mV Verbrauch pro Leiter und Erdungspfad 0 1 VA bei ΙN 1 A 0 5 VA bei ΙN 5 A 1 3 Sicherheit 1 4 Maße Merkmale Spezifikationen Merkmale Spezifikationen Dielektrikum ...

Reviews: