background image

Landis & Staefa Division

CC1N7714E

June 14, 1999

1/4

7

714

Photoresistive Detectors

QRB...

QRB1...A

 with large flange

QRB1...A

 with small flange

QRB1...B

QRB3...

and clamp

and clamp

with plug

with flange and clamp

Photoresistive  flame detectors for use with Landis & Staefa burner  controls,
for the supervision of oil flames in the visible light spectrum.
The flame detectors are used  primarily in  connection with burner controls for
small burners.

The QRB... and this  data  sheet  are  intended for use by OEMs  which  integrate
the flame detectors in their products.

The QRB... are designed for the supervision of yellow-burning oil flames.

Photoresistive detector

For use with burner controls type

QRB...

LAL..., LOA...

For QRC... blue-flame detectors, refer to data sheet 7716.

Compact photoresistive detector with infused two-wire thermoplastic cable.
The flame detector  is  available with normal or high  sensitivity and with or without
flange / clamp or soft plastic plug (refer to «Type summary»).

Flame detector without soft plastic plug.
This type of detector is fitted with the help of a securing flange.
A guide groove in the  securing  flange and a  cam on the detector clamp ensure
vibration-free  mounting and  make certain that the detector  is always correctly sited
towards the flame.

Securing  flange with 22 mm spacing for use with
the

QRB1...1

Securing  flange with 36 mm spacing for use with
the

QRB1...2

Clamp

Flame detector with soft plastic plug.
For  mounting this type of detector on the burner, all that is required is a hole with a
lateral groove (refer to «Dimensions»).
The  sealing and  securing ribs of the  soft  plastic plug hold the detector  firmly in the
hole.
The guide guarantees correct alignment of the photoresistive element with the flame.

The detector is supplied with a protective tube of 17 mm diameter.
This type of detector is always secured with a flange and a clamp (refer to
«Accessories»).

ISO 9001

Use

Mechanical design

QRB1...A

Accessories

QRB1...B

QRB3...

Summary of Contents for QRB Series

Page 1: ...high sensitivity and with or without flange clamp or soft plastic plug refer to Type summary Flame detector without soft plastic plug This type of detector is fitted with the help of a securing flange A guide groove in the securing flange and a cam on the detector clamp ensure vibration free mounting and make certain that the detector is always correctly sited towards the flame Securing flange wit...

Page 2: ...issible length of the detector cable Refer to Technical data Always run the detector cable separate from other cables especially from the ignition cable while observing the greatest possible distances The relevant national safety regulations must be complied with The detector should not be subjected to mechanical shocks The intensity of the radiation of light on site is checked by measuring the de...

Page 3: ...nding on the type of detector refer to Type summary When ordering please give type reference according to Type summary The QRB1 with plug is always supplied without flange clamp and vice versa QRB1 normal sensitivity standard casing length 50 mm visible cable length 200 mm stripped length 40 mm with terminating sleeves without plug without flange clamp QRB1A A020B40A QRB1 as above but with a small...

Page 4: ...ss of water are not permitted With this type of flame supervision the radiation of oil flames in the visible light spectrum is used for generating the flame signal The light sensitive element is a photoresistor When there is no light the detector s resistance is in the MΩ range Its resistance drops as the intensity of illumination increases kΩ range In contrast to the selenium photocell of the RAR...

Reviews: