background image

P/N 315-093616-4

Figure 1

MSI-51B / MSI-53B

INTRODUCTION

The 

SIEMENS

 Models MSI-51B and MSI-53B

Manual Stations are addressable devices contain-

ing advanced control panel communication tech-

nology. This technology, which provides two

direction communication with the control panel,

produces an Intelligent Initiating Device.

OPERATION

This manual station housing has a pull down lever

that locks in position after releasing a spring

loaded switch (See Figure 3). To indicate the

manual station is activated, the pull down lever

remains down and locked until the station is reset.

The 

MSI-51B and MSI-53B

 are reset by opening

the hinged housing cover with an Allen key and

then closing and locking the cover.
The MSI-53B Manual Station is an addressable

station the same as the MSI-51B, but it also has a

nonaddressable 2nd Stage Key Switch.
1. Locate the opening on the 

MSI-51B and

MSI-53B

 cover that allows access to the

programming points on the MSI-51B and

MSI-53B  printed circuit board. (Refer to

Figure 1.)

2. The manual stations are programmed by using

the 

SIEMENS

 Model FPI-32 Programmer/Tester.

Connect the MSI-51B and MSI-53B to the

Programmer/Tester by using the cable provided

with the Programmer/Tester.

NOTE:

The connection from the FPI-32 to the

MSI-51B and MSI-53B is not polarity

sensitive. However, connection from the

Control Panel to the MSI-51B and MSI-53B is

polarity sensitive.

Installation and Programming Instructions

MODELS MSI-51B / MSI-53B

Manual Stations

+

+

_

_

TO NEXT

ADDRESSABLE

DEVICE

EARTH GROUND

NOTE:

RECOMMENDED WIRE SIZES

18 AWG MIN

14 AWG MAX

WIRE LARGER THAN 14 AWG

CAN DAMAGE THE CONNECTOR

1

2

3

FROM CONTROL PANEL

OR PREVIOUS DEVICE

MSI-51B

+

+

+

+

_

_

_

_

TO NEXT

ADDRESSABLE

DEVICE

EARTH GROUND

N. O. KEY SWITCH CONTACT

1A @ 250V

3A @ 125V

NOTE:

RECOMMENDED WIRE SIZES

18 AWG MIN

14 AWG MAX

WIRE LARGER THAN 14 AWG

CAN DAMAGE THE CONNECTOR

1

2

3

FROM CONTROL PANEL

OR PREVIOUS DEVICE

TO NEXT 2 STAGE DEVICE

FROM CONTROL PANEL OR

PREVIOUS 2 STAGE DEVICE

PIGTAIL LEADS

MSI-53B

Figure 2

Wiring Information

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN

Fire Safety