background image

These instructions are written in accordance with the installa-
tion guidelines of NFPA 72, National Fire Alarm Code, and
CAN/ULC-S524, The Installation of Fire Alarm Systems.

Detector Device Storage

DO NOT install this detection device until all construc-
tion is completed.

DO NOT store this detection device where it can be con-
taminated by dirt, dust, or humidity.

When using this detector with a protective

detector guard such as the DGH-11 from Siemens Indus-
try, Inc., or the STI 8100IS, be sure to install per the in-
structions supplied with the guard and set the ASD set-
ting to duct detector per the detector programming in-
structions located on page 2 of this document.

HFP-11 DETECTOR PLACEMENT

Although no specific spacings are set for the detectors used
for a clean air application, use 30 foot center spacing (900 sq
ft) from NFPA Standard 72 and CAN/ULC-S524, if practical, as
a guide or starting point for a detector installation layout. This
spacing, however, is based on ideal conditions–smooth ceil-
ing, no air movement, and no physical obstructions. In some
applications, therefore, considerably less area is protected ad-
equately by each smoke detector. This is why it is mandatory
to closely follow the installation drawings. In all installations
place the detector on the ceiling, a minimum of 6 inches from
a side wall, or on a wall, 4 to 6 inches from the ceiling.

If you have any questions regarding detector placement, fol-
low the drawings provided or approved by Siemens Industry,
Inc., or by its authorized distributors. This is extremely impor-
tant! The detector placements shown on these drawings were
chosen after a careful evaluation of the area that is protected.
Such factors as air currents, temperature, humidity, pressure,
and the nature of the fire load were carefully considered. Es-
pecially noted were the room or area configuration and the
type of ceiling (sloped or flat, smooth or beamed). Siemens
Industry, Inc.’s extensive experience in the design of the sys-
tem assures the best detector placement by following these
drawings. Sound engineering judgment by qualified person-
nel must be followed.

Fire Print Detectors And Nuisance Alarms

The neural network within each Model HFP-11 FirePrint detector
is optimized to reject the most common nuisance alarms for its
selected FirePrint Application; e.g. Parking Garage or Health Care.
If the detector is exposed to an excess level of smoke or aerosol
for an extended period of time, the detector is programmed to
make the “safe decision” and signal an alarm condition. Because
the amplitude and duration of deceptive phenomena are un-
bounded, the rule of thumb is to keep detectors as far as practi-
cal from sources that can produce an unusually large quantity of
smoke for about a minute. This effort during placement of detec-
tors within a FirePrint Application enhances the ability of FirePrint’s
deceptive phenomena rejection. Avoid close proximity of detec-
tors to smoke sources such as oil burners, electric heaters, kitch-
ens, garages, and areas of 

high relative humidity where con-

densation may occur.

Air Currents

Before a detector can sense a fire, the products of combustion
or smoke must travel from the fire to the detector. This travel
is especially influenced by air currents; therefore, consider air
movement when designing the system. While combustion
products tend to rise, drafts from hallways, air diffusers, fans,
etc., may help or hinder the travel of combustion products to
the detector. When positioning a detector at a particular loca-
tion, give consideration to windows and doors, both open and
closed, to ventilating systems, both in and out of operation,
and to other factors influencing air movement. Do not install a
detector in the air stream of a room air supply diffuser. It is
better to position a detector closer to an air return.

The distance that products of combustion or smoke travel
from a fire to the detector is not usually the shortest linear
route. Combustion products or smoke usually rise to the ceil-
ing, then spread out. Average ceiling heights of 8 to 10 feet
do not abnormally affect detector response. High ceilings, lo-
cated in churches, warehouses, auditoriums, etc., do affect
detector response and should be considered.

Special Ceiling Construction Factors
Ceiling obstructions change the natural movement of air and
combustion products.  Depending on the direction of smoke
travel, joists and beams can slow the movement of heated air
and smoke, while pockets between them can contain a re-
duced level of smoke. Take obstructions created by girders,
joists, beams, air conditioning ducts, or architectural design
into consideration when determining area protection.  Refer
to the Initiating Devices chapter of NFPA Standard 72 for Lo-
cation and Spacing requirements for specific types of con-
struction; e.g. beam, suspended, level, sloped and peaked
ceilings.

Figure 1
HFP-11 and HFPT-11

FirePrint Detector / FirePrint Thermal Detector

Installation Instructions

Model HFP-11 / HFPT-11

Siemens 

Siemens 

Siemens 

Siemens 

Siemens Industry

Industry

Industry

Industry

Industry,,,,, Inc.

 Inc.

 Inc.

 Inc.

 Inc.

Building 

Building 

Building 

Building 

Building T

TT

TTec

ec

ec

ec

echnologies Di

hnologies Di

hnologies Di

hnologies Di

hnologies Division

vision

vision

vision

vision

P/N 315-033290-11

Summary of Contents for HFPT-11

Page 1: ...tion Because the amplitude and duration of deceptive phenomena are un bounded the rule of thumb is to keep detectors as far as practi cal from sources that can produce an unusually large quantity of smoke forabout a minute This effort during placement of detec torswithinaFirePrintApplicationenhancestheabilityofFirePrint s deceptive phenomena rejection Avoid close proximity of detec tors to smoke s...

Page 2: ...r the FS 250 Manual P N 315 049353 OPERATION LED Indicators The Model HFP 11 HFPT 11 contains an LED indicator ca pable of flashing either one of three distinct colors green yellow or red During each flash interval the microprocessor based detector checks the following For smoke in its sensing chamber That its smoke sensitivity is within the range indicated on the nameplate label h s a l F r o l o...

Page 3: ...which can be selected using the Touch Screen STEP 4 Touch the box labelled Sensitivities This will highlight the box reverse video to indicate that it has been selected STEP 5 Select the Execute option by pressing the button with the lit green triangle pointing to the Execute Tab The system reads all device sensitivities for the module loop or device and displays it on the PMI PMI 2 screen This se...

Page 4: ...Notify facility personnel that the system is being serviced so that any alarm soundings can be ignored during the pe riod of service CLEANING PROCEDURE See Figure 3 1 Notify the proper personnel that the fire alarm system is being serviced P N 315 033290 11 Siemens Industry Inc BuildingTechnologies Division Florham Park NJ Siemens Canada Limited 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Reviews: