background image

CPU 1511-1 PN  

(6ES7511-1AK00-

0AB0)  

 

___________________

___________________

___________________

___________________

___________________

___________________

___________________

 

SIMATIC 

S7-1500 

CPU 1511-1 PN  

(6ES7511-1AK00-0AB0) 

Manual 

 

  

01/2013 

A5E31264526-AA 

Preface 

 

 

Documentation guide 

 

1

 

Product overview 

 

2

 

Wiring 

 

3

 

Interrupts, diagnostics, error, 

and system messages 

 

4

 

Technical specifications 

 

5

 

Dimensional drawing 

 

A

Содержание CPU 1511-1 PN

Страница 1: ..._________ ___________________ ___________________ ___________________ SIMATIC S7 1500 CPU 1511 1 PN 6ES7511 1AK00 0AB0 Manual 01 2013 A5E31264526 AA Preface Documentation guide 1 Product overview 2 Wiring 3 Interrupts diagnostics error and system messages 4 Technical specifications 5 Dimensional drawing A ...

Страница 2: ... only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens p...

Страница 3: ...tion should be paid Note on IT security Siemens offers IT security mechanisms for its automation and drive product portfolio in order to support the safe operation of the plant machine We recommend that you inform yourself regularly on the IT security developments regarding your products You can find information on this on the Internet http support automation siemens com You can register for a pro...

Страница 4: ...Preface CPU 1511 1 PN 6ES7511 1AK00 0AB0 4 Manual 01 2013 A5E31264526 AA ...

Страница 5: ...th front panel 12 2 2 2 Front view of the module without front panel 14 2 2 3 Rear view of the module 15 2 3 Mode selector switch 15 2 4 Functions 16 2 4 1 PROFINET IO 16 2 4 2 PROFIenergy 17 2 4 3 Memory reset 17 2 4 4 Restoring the factory settings of the CPU 19 3 Wiring 21 4 Interrupts diagnostics error and system messages 25 4 1 Status and error display of the CPU 25 5 Technical specifications...

Страница 6: ...Table of contents CPU 1511 1 PN 6ES7511 1AK00 0AB0 6 Manual 01 2013 A5E31264526 AA ...

Страница 7: ...511 1 PN and are available on the Internet Table 1 1 Documentation for CPU 1511 1 PN Topic Documentation Most important contents System description S7 1500 Automation System http support automation siemens com WW view en 59191792 system manual Application planning Installation Wiring Commissioning Power supplies http support automation siemens com WW view en 57251228 device manual Properties of th...

Страница 8: ...ers http support automation siemens com WW view en 59193566 function manual Basics Electromagnetic compatibility Lightning protection Housing selection Memory concept Structure and use of the CPU memory http support automation siemens com WW view en 59193101 function manual Setup Function principle Use Cycle and response times Cycle and response times http support automation siemens com WW view en...

Страница 9: ... 1 PN 6ES7511 1AK00 0AB0 Manual 01 2013 A5E31264526 AA 9 Product overview 2 2 1 Properties Order number 6ES7511 1AK00 0AB0 View of the module The following figure shows a CPU 1511 1 PN Figure 2 1 CPU 1511 1 PN ...

Страница 10: ...lity by means of PROFINET IO IRT and PROFIdrive interface The functionality supports speed controlled axes positioning axes and external encoders Integrated control functionality Universal PID controllers or 3 point controllers with integrated tuning Integrated temperature controller Integrated system diagnostics System diagnostics is automatically generated and consistently displayed Integrated s...

Страница 11: ...re update Integrated system diagnostics PROFINET IO RT PROFINET IO IRT PROFIenergy Media redundancy I device IO controller Web server Trace Isochronous mode Integrated controller Standard Motion Control Reference You can find additional information on Integrated security access protection under Protection in the S7 1500 Automation System system manual http support automation siemens com WW view en...

Страница 12: ...511 1 PN with front panel front Note Removing and fitting the front panel The front panel can be removed and replaced during runtime without affecting operation Note Temperature range for display To increase the service life of the display the display switches itself off before the permitted operating temperature is reached When the display cools down again it automatically switches itself on agai...

Страница 13: ...tp support automation siemens com WW view en 59191792 System Manual CPU display chapter Removing and replacing the front cover is described in the section on handling the front cover Locking the front cover You can lock the front cover to protect your CPU against unauthorized access You can attach a security seal or a padlock with a diameter of 3 mm to the front cover Figure 2 3 Locking latch on t...

Страница 14: ... and connection elements of the CPU 1511 1 PN behind the front panel LEDs for the current operating mode and diagnostic status of the CPU Display connection Slot for the SIMATIC memory card Mode selector switch LEDs for the 2 ports of the PROFINET interface X1 MAC address PROFINET interface X1 with 2 port switch Connection for power supply Fixing screw Figure 2 4 View of the CPU 1511 1 PN without ...

Страница 15: ...e bus connector Fixing screw Figure 2 5 View of the CPU 1511 1 PN back 2 3 Mode selector switch Use the mode selector to set the CPU operating mode The following table shows the position of the switch and the corresponding meaning Table 2 1 Mode selector switch settings Position Meaning Explanation RUN RUN mode The CPU is executing the user program STOP STOP mode The CPU is not executing the user ...

Страница 16: ...ss to IO devices via Industrial Ethernet The PROFINET IO device operating mode enables the operation of S7 stations as intelligent PROFINET IO devices on Industrial Ethernet UDP and RT or IRT are used to configure the cyclic IO data traffic for PROFINET IO communication General properties of PROFINET IO PROFINET IO has the following properties and functions Real time communication Isochronous real...

Страница 17: ... reading the data from the SIMATIC memory card Options You have the following options for resetting the memory of the CPU Using the mode selector switch Using the display Using STEP 7 V12 Procedure using the mode selector switch Proceed as follows to reset the CPU memory using the mode sselector switch 1 Set the mode selector switch to STOP Initial result The RUN STOP LED lights up yellow 2 Set th...

Страница 18: ...s performed Memory object response to memory reset The following table gives an overview of which memory objects are retained and which are initialized upon memory reset Table 2 2 Retentive characteristics of the memory objects Memory object Contents Actual values of the data blocks instance data blocks Initialized Bit memories timers and counters Initialized Certain retentive tags from technology...

Страница 19: ... LED lights up yellow Perform a reset to factory settings when there is no SIMATIC memory card inserted as follows 1 Set the mode selector switch to STOP Initial result The RUN STOP LED lights up yellow 2 Set the mode selector switch to the MRES position Hold the mode selector switch in this position until the RUN STOP LED lights up in yellow for the 2nd time and remains lit this takes three secon...

Страница 20: ...y settings group 3 Select the Retain IP address option button to retain the IP address or the Reset IP address option button to delete the IP address 4 Click Reset 5 Click OK to confirm the security prompt Result The CPU is set to STOP mode and is reset to factory settings Retentive characteristics of the memory objects The properties of the CPU are set to the following values Table 2 3 Properties...

Страница 21: ...the factory state of the CPU The following table shows the terminal assignment for a 24 V DC power supply Table 3 1 Terminal assignment 24 V DC power supply View Signal name Pin assignment 1L 24 V DC 2L 24 V DC 1M Ground 2M Ground 1L and 2L and 1M and 2M are jumpered internally Make sure that the current is limited to 10 A If the CPU is supplied by a system power supply the 24 V supply connection ...

Страница 22: ...191792 Assignment of MAC addresses The CPU 1511 1 PN has a PROFINET interface with two ports The PROFINET interface itself has a MAC address and each of the two PROFINET ports has its own MAC address There are therefore three MAC addresses in total for the CPU 1511 1 PN The MAC addresses of the PROFINET ports are needed for the LLDP protocol for example for the proximity detection function The num...

Страница 23: ...lock diagram of CPU 1511 1 PN DFNSODQH EXV DFNSODQH EXV LQWHUIDFH PRGXOH OHFWURQLFV QWHUQDO YROWDJH VXSSO LVSOD YROWDJH VXSSO FRQQHFWLRQ OHFWULFDO LVRODWLRQ 581 6723 05 6 PRGH VHOHFWRU VZLWFK 9b 6 0 7 0HPRU DUG 31 3 6ZLWFK 1 31 3 0 17 581 6723 5525 1 7 5 3 1 7 5 3 Figure 3 1 Block diagram CPU 1511 1 PN ...

Страница 24: ...Wiring CPU 1511 1 PN 6ES7511 1AK00 0AB0 24 Manual 01 2013 A5E31264526 AA ...

Страница 25: ...l find additional information on Diagnostics and System messages in the System diagnostics http support automation siemens com WW view en 59192926 function manual 4 1 Status and error display of the CPU LED display The figure below shows the CPU 1511 1 PN LEDs RUN STOP LED yellow green LED ERROR LED red LED MAINT LED yellow LED LINK RX TX LED for X1 P1 port yellow green LED LINK RX TX LED for X1 P...

Страница 26: ... LED off A diagnostic event is pending LED green LED off LED yellow Maintenance demanded for the plant The affected hardware must be replaced within a short period of time Maintenance required for the plant The affected hardware must be replaced within a reasonable time period LED green LED off LED flashes yellow Firmware update successfully completed LED yellow LED off LED off CPU is in STOP mode...

Страница 27: ...g LED off There is no Ethernet connection between the PROFINET interface of the PROFINET device and the communication partner No data is currently being sent received via the PROFINET interface There is no LINK connection LED flashes green The LED flashing test is performed LED green There is no Ethernet connection between the PROFINET interface of your PROFINET device and a communication partner ...

Страница 28: ...Interrupts diagnostics error and system messages 4 1 Status and error display of the CPU CPU 1511 1 PN 6ES7511 1AK00 0AB0 28 Manual 01 2013 A5E31264526 AA ...

Страница 29: ...and display elements Number of buttons 6 Mode selector switch 1 Installation type mounting Rail mounting possible Yes Wall direct mounting possible No Supply voltage Type of supply voltage 24 V DC Low limit of permitted range DC 19 2 V High limit of permitted range DC 28 8 V Reverse polarity protection Yes Input current Current consumption rated value 0 7 A Inrush current max 1 9 A rated value I t...

Страница 30: ...loating point arithmetic typ 384 ns CPU blocks Number of blocks total 2000 DB Number max 2000 number range 1 to 65535 Size max 1 MB FB Number max 1998 number range 1 to 65535 Size max 150 KB FC Number max 1999 number range 1 to 65535 Size max 150 KB OB Size max 150 KB Number of free cycle OBs 100 Number of time of day interrupt OBs 20 Number of time delay interrupt OBs 20 Number of cyclic interrup...

Страница 31: ...table Yes S7 timers Quantity 2048 Retentivity Adjustable Yes IEC timers Quantity Unlimited limited only by work memory Retentivity Adjustable Yes Data areas and their retentivity Total retentive data area including timers counters bit memories max 128 KB for bit memories timers counters DBs and technological data axes usable retentive memory 88 KB Bit memory Number max 16 KB Number of clock memori...

Страница 32: ...ions max 32 Address space per module Number of I O submodules 5 Hardware configuration Modules per rack max 32 CPU 31 modules Rack number of rows max 1 Number of DP masters Via CM 4 a maximum of 4 CMs CPs PROFIBUS PROFINET Ethernet can be inserted in total Number of IO controllers Integrated 1 PtP CM Number of PtP CMs The number of PtP CMs you can connect is only limited by the available slots Tim...

Страница 33: ...nication Yes Web server Yes Media redundancy Yes Interface hardware RJ 45 Ethernet 100 Mbps Yes Autonegotiation Yes Autocrossing Yes Industrial Ethernet status LED Yes Number of connections Number of connections max 96 Number of connections reserved for ES HMI Web 10 Number of connections via integrated interfaces 64 Protocols PROFINET IO controller Services PG OP communication Yes S7 routing Yes ...

Страница 34: ...n component set for PROFINET IO on the number of IO devices and on the quantity of configured user data with RT for send cycle of 250 µs 250 μs to 128 ms for send cycle of 500 µs 500 μs to 256 ms for send cycle of 1 ms 1 ms to 512 ms for send cycle of 2 ms 2 ms to 512 ms for send cycle of 4 ms 4 ms to 512 ms with IRT and high performance option for send cycle of 250 µs 250 μs to 4 ms for send cycl...

Страница 35: ...Yes Data length max 1472 bytes DHCP No SNMP Yes DCP Yes LLDP Yes Web server HTTP Yes standard and user defined pages HTTPS Yes standard and user defined pages Media redundancy Changeover time on line interruption typ 200 ms Number of ring nodes max 50 Slots SIMATIC Memory Card required Yes Isochronous mode Isochronous mode application synchronized up to terminal Yes Constant bus cycle time Yes S7 ...

Страница 36: ...0 Interrupts diagnostics status information Diagnostic indicator LED RUN STOP LED Yes ERROR LED Yes MAINT LED Yes Connection display LINK TX RX Yes Supported technology objects Motion Yes Speed controlled axis Number of speed controlled axes max 6 a total of up to 6 axes speed controlled axis positioning axis external encoders are supported Positioning axis Number of positioning axes max 6 a total...

Страница 37: ...ation min 0 C Vertical installation max 40 C display 40 C the display is switched off at an operating temperature of typically 40 C Configuring Programming Programming language LAD Yes FBD Yes STL Yes SCL Yes Know how protection User program protection Yes Copy protection Yes Block protection Yes Access protection Password for display Yes Protection level Read only Yes Protection level Read write ...

Страница 38: ...Technical specifications CPU 1511 1 PN 6ES7511 1AK00 0AB0 38 Manual 01 2013 A5E31264526 AA ...

Страница 39: ...udes a dimensional drawing of the module on a mounting rail and a dimensional drawing with the front panel open Always observe the specified dimensions for installation in cabinets control rooms etc Dimensional drawings for CPU 1511 1 PN Figure A 1 Dimensional drawing of CPU 1511 1 PN front and side views ...

Страница 40: ...Dimensional drawing CPU 1511 1 PN 6ES7511 1AK00 0AB0 40 Manual 01 2013 A5E31264526 AA ෘ a Figure A 2 Dimensional drawing of CPU 1511 1 PN side view with front panel open ...

Отзывы: