background image

 

 

PLC-16.PCI 

Users Manual 

 

 

 

 

 

Part # 8011 

Sealevel Systems, Inc. 

Telephone: 864.843.4343 

155 Technology Place Fax: 

864.843.3067 

Liberty, SC 29657 USA 

www.sealevel.com 

 
 

 

Summary of Contents for PLC-16.PCI

Page 1: ...PLC 16 PCI Users Manual Part 8011 Sealevel Systems Inc Telephone 864 843 4343 155 Technology Place Fax 864 843 3067 Liberty SC 29657 USA www sealevel com ...

Page 2: ...ASSIGNMENTS 8 OPTIONAL TERMINAL BLOCK KIT KT108 9 DIRECT HARDWARE CONTROL 10 READING THE INPUTS 10 READING THE OUTPUTS 10 WRITING THE OUTPUTS 10 REGISTER DESCRIPTION 11 SPECIFICATIONS 12 ENVIRONMENTAL SPECIFICATIONS 12 MANUFACTURING 12 POWER CONSUMPTION 12 PHYSICAL DIMENSIONS 12 APPENDIX A TROUBLESHOOTING 13 APPENDIX B HOW TO GET ASSISTANCE 14 APPENDIX C SILK SCREEN 15 APPENDIX D COMPLIANCE NOTICE...

Page 3: ...onitoring of off board switch closures relays or for any other general purpose monitoring needs The PLC 16 PCI is optimized for 24V DC AC usage What s Included The PLC 16 PCI is shipped with the following items If any of these items is missing or damaged contact the supplier PLC 16 PCI Adapter Sealevel SeaIO Software CD Optional Cables Accessories KT108 Includes CA185 HD44 M F Cable and TB08 PLC t...

Page 4: ...also adds entries to the system registry that are necessary for specifying the operating parameters for each driver An uninstall option is also available to remove SeaIO files and registry INI file entries from the system Windows NT Card Installation After accomplishing the above steps bring up the Control Panel and double click on the SeaIO Devices icon To install a new card click Add Port Repeat...

Page 5: ...section Using the test software if you wish to do so at this time To set up Linux to automatically load the driver refer to a Linux manual concerning your specific distribution for help Physical Installation The adapter can be installed in any 5V PCI expansion slot Do not install the Adapter in the machine until the software has been fully installed 1 Turn off PC power Disconnect the power cord 2 ...

Page 6: ...uts Eight Type Non polarized optically isolated from each other and from the computer Voltage Range 5 to 24V DC or AC Relay Outputs Number of outputs Eight Contact Rating 2A carry current bifurcated gold clad silver palladium Contact Arrangement SPDT Single Pole Double Throw Form C Contact Resistance Initial 100 milliohms maximum Contact Life mechanical 10 million operations minimum Contact Life e...

Page 7: ...n the output of the opto isolator goes low 0 volts and the signal is read as a low logic level binary 0 by the PC When the input signal is too low to turn on the opto isolator the output goes high and the port bit is read by the PC as a high logic level binary 1 The input impedance of each isolated input is 1K ohms The opto isolator requires approximately 3 mA to turn on The maximum input current ...

Page 8: ... Closed NC and a Common The relays are all de energized at power on Data to the relays is latched by a write to the base 2 address On off status of the relays can be read back by a read at the base 2 address The above is a schematic representation of the Output Bit D0 The NC contact would be Pin 1 on the HD44 N0 would be Pin 31 and the Common would be Pin 16 5 V 2 5 4 1 3 HD 44 1 16 31 Output Bit ...

Page 9: ...accessed as well as each input of the optically isolated input circuit to be represented as a unique pin on the connector The following table shows the correlation between pins on the HD44 and their specific function HD44 Pin Assignments Input Port A Bit P1 D0 9 10 D1 11 12 D2 13 14 D3 23 24 D4 25 26 D5 27 28 D6 29 30 D7 40 41 Output Port C Bit Normally Closed Common Normally Open D0 K1 1 16 31 D1...

Page 10: ...on Sealevel s PCI and ISA legacy products and provides a direct connection to Sealevel s TB02 37 pin Terminal Block The following table shows the correlation between pins on the CA184 option cable connectors and their specific function Input DB37 Female Port A Bit Input D0 3 22 D1 4 23 D2 5 24 D3 6 25 D4 7 26 D5 8 27 D6 9 28 D7 10 29 Output DB37 Male Port C Bit Normally Closed Common Normally Open...

Page 11: ...n of the PLC 16 PCI is the KT108 Terminal Block Kit which features the CA185 HD44 M F and the TB08 Terminal Block adapter This adapter groups the common connections of the PLC 16 PCI into groups of four The following is the silkscreen for the TB08 Note that the connections are labeled for ease in wiring and troubleshooting ...

Page 12: ...ory as FINDPCI EXE Each system motherboard organizes its physical PCI slots according to the current PCI specification There is not a fixed order or number of slots for each motherboard To determine which resources correspond to which PCI card you may want to add the cards one at a time and run FINDPCI EXE after each card is added Each PCI slot will have a corresponding BUS DEVICE and FUNCTION num...

Page 13: ...upts prior to changing or setting states This will help prevent inadvertent or un expected interrupts from occurring When using the high and low level interrupts a change in state of the input must occur before the interrupt can be cleared The device providing the input to Base 0 bit D0 must do this PAD0 7 Port A Base 0 Input port PCD0 7 Port C Base 2 Output port IRC0 1 Interrupt Mode select Base ...

Page 14: ...densing Manufacturing All Sealevel Systems Printed Circuit boards are built to UL 94V0 rating and are 100 electrically tested These printed circuit boards are solder mask over bare copper or solder mask over tin nickel Power Consumption Supply line 5 VDC Rating 380mA Physical Dimensions Board Length 4 90 inches 12 446m Board Height including Goldfingers 4 20 inches 10 668m Board Height excluding G...

Page 15: ...f any should be identified 2 Configure your Sealevel Systems adapter so that there is no conflict with currently installed adapters No two adapters can occupy the same I O address 3 Make sure the Sealevel Systems adapter is using a unique IRQ While the Sealevel Systems adapter does allow the sharing of IRQs many other adapters i e SCSI adapters on board serial ports do not The IRQ is typically sel...

Page 16: ...provides an FAQ section on its web site Please refer to this to answer many common questions This section can be found at http www sealevel com faq asp 4 Sealevel Systems maintains a web page on the Internet Our home page address is http www sealevel com The latest software updates and newest manuals are available via our web site 5 Technical support is available Monday to Friday from 8 00 a m to ...

Page 17: ...Appendix C Silk Screen Sealevel Systems PLC 16 PCI Page 15 Appendix C Silk Screen 4 2 4 9 ...

Page 18: ...pense EMC Directive Statement Products bearing the CE Label fulfill the requirements of the EMC directive 89 336 EEC and of the low voltage directive 73 23 EEC issued by the European Commission To obey these directives the following European standards must be met EN55022 Class A Limits and methods of measurement of radio interference characteristics of information technology equipment EN55024 Info...

Page 19: ...ned from Sealevel Systems before returned merchandise will be accepted Authorization is obtained by calling Sealevel Systems and requesting a Return Merchandise Authorization RMA number The Customer agrees to insure the Product or assume the risk of loss or damage in transit to prepay shipping charges to Sealevel and to use the original shipping container or equivalent Warranty is valid only for o...

Reviews: