background image

Wiring Instructions for the 

2900 Series FIREGUARD

®

Combination Door Closer-Holder and Releasing Device

with Integral Smoke Detector

CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE.

For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com 

CAUTION

INSTALLER: LEAVE INSTRUCTION with building owner.

Wire 12- smoke detector unit to appropriate 
power supply and fire alarm

Refer to data sticker for proper input voltage 
and current specifications

9- Companion units are designed to work with 
12- smoke detector units (12-2960, 12-2990,
12-2980) only

Wire companion unit to 12- smoke detector 
unit as shown on wiring diagram if required

Do not disconnect any existing wires on 
smoke detector unit’s terminal strip

Energize power supply. Current draw
.1 AMP per 12- unit.

Open door(s) to hold-open point.
Door(s) should hold open

Depress On/Off test switch on circuit
board. Doors should close and latch

Adjustment of spring power may be 
necessary to ensure proper latching

Depress On/Off test switch to
reactivate hold open latch
assembly(s)

A7408B

1

1. DISCONNECT ALL POWER BEFORE BEGINNING 

INSTALLATION TO PREVENT ELECTRICAL SHOCK AND 
EQUIPMENT DAMAGE.

2. INSTALLER MUST BE A TRAINED, EXPERIENCED 

SERVICE PERSON.

3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL 

ELECTRICAL CODES, ORDINANCES AND REGULATIONS.

4. MAXIMUM WIRE SIZE IS 18AWG.

Wiring 12- Units with and without 9- Companion Unit

9- Companion Unit
(If required)

Field wiring by others

Wire nut

On/Off Test switch

Yellow

Red

Black

Yellow

Black

Black

Terminal strip for
power input wiring

Red

Yellow

Smoke 
detector 
unit

12- Smoke Detector Unit

9

1112

14

3 7

RED LED/
Reset Switch

Data
Sticker

Opening
for
surface
or
concealed
wiring

Line

Neutral

Earth Ground

120VAC

Power

Supply

*120VAC
Circuit Board
shown

Self 
resetting
fuse

Wire the appropriate Power Supply
to circuit board. Power is either
120VAC or 24VDC/VAC depending
on circuit board supplied.

When 24VDC/VAC board is supplied,
wire 24VDC/VAC power supply to
+ and - terminals on circuit board.

*CAUTION:

 Refer to data  

sticker on circuit board for  
proper input voltage required.

Do 

NOT

 wire 120VAC power  

to 24VDC/VAC circuit board.

Earth ground connection is required 
when 120VDC power is used

*120VAC 

wiring shown

Circuit board 120VAC
or 24VAC/DC
(120VAC shown)

Remove jumper and install
output connector assembly
(Part No. 63-2868) required
for this option

User supplied normally
closed momentary switch

Wiring Optional Remote Push Button

Содержание 2900 Series FIREGUARD

Страница 1: ...ION TO PREVENT ELECTRICAL SHOCK AND EQUIPMENT DAMAGE 2 INSTALLER MUST BE A TRAINED EXPERIENCED SERVICE PERSON 3 ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL ELECTRICAL CODES ORDINANCES AND REGULATIONS 4 MAXIMUM WIRE SIZE IS 18AWG Wiring 12 Units with and without 9 Companion Unit 9 Companion Unit If required Field wiring by others Wire nut On Off Test switch Yellow Red Black Yellow Black Black Term...

Страница 2: ... for remote detector interconnect applications Terminals 8 9 and 10 may be field configured to a dry form contact by cutting jumper between terminal 11 and 12 Terminal 10 is Common 9 is N C and 8 is N O If this is done Aux is lost solenoid power must be supplied by a separate source Terminals 15 and 4 provide interconnections to other detectors See diagram Pg 4 Up to five smoke detectors may be in...

Страница 3: ...a feature that detects when a smoke sensing chamber requires cleaning due to dirt and dust The need for cleaning is indicated by the flashing of the Red LED light once per second Normal Supervisory Operation Red LED flashes once every 8 seconds Dirty Chamber needs cleaning Red LED flashes once every second Smoke Detection Red LED is continuously illuminated To clean the smoke detector assembly fol...

Страница 4: ...5 4 10 Remote Detector N O C Relay 4 Use terminals 4 and 15 to wire detectors in parallel See 1 2 and 3 Use terminal 10 to signal remote detectors with relay contact only See 4 and 5 Five detectors maximum Accessory wire pack 63 3212 needed for unit interconnection ...

Страница 5: ...ousing by inserting crimped terminal end into housing body until crimped terminal snaps into position Use accessory wire pack 63 3212 15 Earth ground to track green wire 24VDC 0 15A Max to external alarm Power Supply Board 1 2 Alarm Circuit Trouble Circuit EOL RES Alarm Panel 24VDC Solenoid 24VDC 0 15A Max to external alarm 4 3 2 1 5 6 7 11 10 9 8 12 13 14 1 2 Power Supply Board 15 4 3 2 1 5 6 7 1...

Страница 6: ...ical data sheet Do not overload circuits 5 Wires are added to header housing by inserting crimped terminal end into housing body until crimped terminal snaps into position Use accessory wire pack 63 3212 15 24VDC 0 15A Max to external alarm bell horn etc Power Supply Board 1 2 24VDC Latch 4 3 2 1 5 6 7 11 10 9 8 12 13 14 Connect to power source 24VAC DC or 120VAC Power supply board and power sourc...

Страница 7: ...ay not reach the smoke detector and alarm it A detector may not detect a fire developing on another level of a building For this reason detectors should be located on every level of a building Smoke detectors have sensing limitations Photoelectric detectors sense smoldering fires better than flaming fires Ionization detectors offer a broad range of fire sensing capability but they are better at de...

Страница 8: ...oor stop Rotate cam until switch roller is on lower section of cam and approximately 1 32 from bottom of incline Cam should be positioned so when door closes roller on switch will ride up incline of cam operating the switch Tighten one set screw in cam with hex key and pull door closed 4 Pull door open to desired hold open position When switch roller travels down to bottom of incline door closer w...

Отзывы: