background image

Cod: 0060300000-A

VENTILATION FAN

WARNING

READ AND SAVE THESE INSTRUCTIONS

Installer: Leave this manual with the homeowner.

CAUTION

CLEANING & MAINTENANCE

OPERATION

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the 

manufacturer at the address or telephone number listed in the warranty.

2. Before servicing or cleaning the unit, switch power off at service panel and lock the service discon-

necting means to prevent power from being switched on accidentally. When the service disconnect-

ing means cannot be locked, securely fasten a prominent warning device, such as a tag, to the 

service panel.

3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with all 

applicable codes and standards, including fire-rated construction codes and standards.

4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) 

of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s 

guideline and safety standards such as those published by the National Fire Protection Association 

(NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers 

(ASHRAE), and the local code authorities.

5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

6. Ducted fans must always be vented to the outdoors.

7. Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupt-

er) - protected branch circuit (ceiling installation only).

8. This unit must be grounded.

1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4. Please read specification label on product for further information and requirements.

For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dusting brush attach-
ment.
The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the motor with the 
exact service motor. The impeller should also be replaced.

MODEL:  PCD80XHP

See “Connect Wiring Diagram” for details.

Time delay knob

Humidity sensor knob

Operation Sequence

1. Turn power ON. The fan will run at low speed (40 CFM)and the humidity sensor will start sensing .

2. Turn switch  ON. The fan will run at high speed(80 CFM) and will override the humidity sensor.

3. Turn switch  OFF. The fan will continue to run at high speed until the time delay has elapsed (if enabled), and then will automatically change back 

to low speed.

HUMIDITY SENSOR OPERATION

The fan runs continuously at a low speed and automatically boosts up to high speed when the relative humidity (RH%) in the room exceeds the RH% 

limit set with the humidity sensor knob. If the fan continuously responds to changing environmental conditions (too sensitive), the RH% limit may need 

to be adjusted.

T

H

OFF

30%

45%

60%

80%

60min

20min

40min

OFF

5min

The control box, located inside the fan housing, has two settings:

(1) The time delay knob sets the amount of time that the fan will continue to run at high speed 

after switch  is turned OFF, or the RH% limit is reached. It is adjustable from 5 to 60 

minutes. Once the set time has elapsed, the fan will run at the Low speed. The time delay 

setting is de-activated when set between OFF-5 mins (factory set to OFF). NOTE: for 

humidity sensing applications, the fan will continue to run for 5 minutes after humidity is 

below the RH% limit, even if the time delay knob is set between OFF-5 mins.

(2) The humidity sensor knob sets the RH% limit at which the fan will automatically operate at 

high speed. The humidity sensor is de-activated when set between OFF-30% .

Summary of Contents for PCDXP Series

Page 1: ...age and noisy and or unbalanced impellers keep drywall spray construction dust etc off power unit 4 Please read specification label on product for further information and requirements For quiet and efficient operation long life and attractive appearance lower or remove grille and vacuum interior of unit with the dusting brush attach ment The motor is permanently lubricated and never needs oiling I...

Page 2: ...ousing to the joist through the holes on the lower mounting flange d Screw the hanger bar onto the joist through the hole PLAN THE INSTALLATION ROOF CAP with built in damper ROUND DUCT WALL CAP with built in damper Purchase separately POWER CABLE INSULATION Place around and over Fan Housing Seal gaps around Housing FAN HOUSING ROUND ELBOW S Seal duct joints with tape Keep duct runs short 1 Do not ...

Page 3: ...air flow 4 Install DUCT AND BLOWER ASSEMBLY Hole Hole Hole a Install duct from the inside of the housing Fix the duct by the tab b Fix the BLOWER ASSEMBLY to the housing by 3 screws RETROFIT INSTALLATION 1 Remove wire panel and blower assembly before installation 2 Fold mounting ears flat against housing Blower assembly Wire panel 3 Enlarge ceiling opening to 9 1 2 by 9 1 2 leave ductwork and wiri...

Page 4: ... PARTICULAR PURPOSE During this five year period S P will at its option repair returned products or parts or provide replacement products or parts without charge for any product or part which is found to be defective under normal use This warranty does not cover normal maintenance and service or any parts that have been subject to misuse negligence accident improper maintenance or repair faulty in...

Reviews: