background image

Cod: 0060300000-A

VENTILATION FAN

WARNING

READ AND SAVE THESE INSTRUCTIONS

Installer: Leave this manual with the homeowner.

CAUTION

CLEANING & MAINTENANCE

OPERATION

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the 

manufacturer at the address or telephone number listed in the warranty.

2. Before servicing or cleaning the unit, switch power off at service panel and lock the service discon-

necting means to prevent power from being switched on accidentally. When the service disconnect-

ing means cannot be locked, securely fasten a prominent warning device, such as a tag, to the 

service panel.

3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with all 

applicable codes and standards, including fire-rated construction codes and standards.

4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) 

of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s 

guideline and safety standards such as those published by the National Fire Protection Association 

(NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers 

(ASHRAE), and the local code authorities.

5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

6. Ducted fans must always be vented to the outdoors.

7. Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupt-

er) - protected branch circuit (ceiling installation only).

8. This unit must be grounded.

1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4. Please read specification label on product for further information and requirements.

MODEL:  PCD80XHP

See “Connect Wiring Diagram” for details.

Time delay knob

Humidity sensor knob

T

H

OFF

30%

45%

60%

80%

60min

20min

40min

OFF

5min

The control box, located inside the fan housing, has two settings:

(1) The time delay knob sets the amount of time that the fan will continue to run at high speed 

after switch  is turned OFF, or the RH% limit is reached. It is adjustable from 5 to 60 

minutes. Once the set time has elapsed, the fan will run at the Low speed. The time delay 

setting is de-activated when set between OFF-5 mins (factory set to OFF). NOTE: for 

humidity sensing applications, the fan will continue to run for 5 minutes after humidity is 

below the RH% limit, even if the time delay knob is set between OFF-5 mins.

(2) The humidity sensor knob sets the RH% limit at which the fan will automatically operate at 

high speed. The humidity sensor is de-activated when set between OFF-30% .

For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dusting brush attach-
ment.
The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the motor with the 
exact service motor. The impeller should also be replaced.

Operation Sequence

1. Turn power ON. The fan will run at low speed (40 CFM)and the humidity sensor will start sensing .

2. Turn switch  ON. The fan will run at high speed(80 CFM) and will override the humidity sensor.

3. Turn switch  OFF. The fan will continue to run at high speed until the time delay has elapsed (if enabled), and then will automatically change back 

to low speed.

HUMIDITY SENSOR OPERATION

The fan runs continuously at a low speed and automatically boosts up to high speed when the relative humidity (RH%) in the room exceeds the RH% 

limit set with the humidity sensor knob. If the fan continuously responds to changing environmental conditions (too sensitive), the RH% limit may need 

to be adjusted.

Summary of Contents for PCD80XHP

Page 1: ...age and noisy and or unbalanced impellers keep drywall spray construction dust etc off power unit 4 Please read specification label on product for further information and requirements MODEL PCD80XHP See Connect Wiring Diagram for details Time delay knob Humidity sensor knob T H OFF 30 45 60 80 60min 20min 40min OFF 5min The control box located inside the fan housing has two settings 1 The time del...

Page 2: ...ected outwards from the cooking equipment element closest to the fan See instruction sheet for clarification 2 Two ways to connect ductwork to a factory shipped unit SENSITIVITY ADJUSTMENT The H limit has been factory set for most shower applications However if the fan is in a tub area or is being used for moisture control the H may need to be increased toward 80 If the fan is responding too often...

Page 3: ...UNIT BLACK BLK SWITCH BOX POWER SUPPLY 120V AC GROUND GRD WHITE WHT FAN RECEPTACLE WIRE PANEL SWITCH BROWN BRN FAN BRN BLK BLK LINE IN WHT WHT GRD UNIT SWITCH BOX GRD SWITCH 3 Enlarge ceiling opening to 9 1 2 by 9 1 2 leave ductwork and wiring in place 4 Connect wiring according to the wiring diagram Re install wire panel 5 Fan Mounting Mount with additional mounting holes The interior of the fan ...

Page 4: ... of its products that our exhaust fans will be free from defects in materials and workmanship for a period of Six 6 years from the date of original purchase THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF SUITABILITY FOR A PARTICULAR PURPOSE During this five year period S P will at its option repair returned products or parts or provide replace...

Reviews: