background image

TEMPEST HVLS

6- Blade High Volume Low Speed Fan

IOM-TEMPEST-0412221

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Summary of Contents for ADVANCING VENTILATION TORNADO HVLS

Page 1: ...TEMPEST HVLS 6 Blade High Volume Low Speed Fan IOM TEMPEST 0412221 INSTALLATION OPERATION AND MAINTENANCE MANUAL ...

Page 2: ... rated construction Failure to comply could result in personal injury electric shock death fire and or property damage Before attempting installation servicing or cleaning unit switch power off at the service panel and lock the service disconnecting means to prevent power from being switched on accidentally Pour réduire le risque d incendie de choc électrique ou de blessures observer les points su...

Page 3: ...es utiliser à des fins autres que celles prévues par le fabricant This unit has an unguarded impeller Do not use in locations readily accessible to people or animals Cet appareil possède une roue sans surveillance Ne pas utiliser dans des endroits facilement accessibles pour les personnes ou les animaux Use this unit only in the manner intended by the manufacturer If you have questions contact the...

Page 4: ...Work Site 9 5 Mounting Method 1 Unistrut 10 Mounting Method 2 Angle Iron 12 16 Mounting Method 3 I Beam 17 Mounting Method 4 Purlins 18 19 6 Hanging the Fan 20 21 7 Installing Guy Wires 22 23 8 Installing Blades 24 27 9 Electrical 28 32 10 Troubleshooting 33 35 1 1 User Servicing Instructions 36 37 ...

Page 5: ...c Cap 5 16 18 x 3 4 12 Zinc Split Lock Washer 5 16 6 BTN Cap Screw 10 32 X 3 8 Upper Yoke x2 Blade Boomerang Bracket x6 IDFC Controller x1 Reference Controller Brochure for additional hardware Hardware Packet 2 Blade Assembly Hardware Packet 3 Extra Hardware 5 Gripple Fasteners 4 15 Guy Wires 1 5 Safety Cable Gripple Packet 1 Bolt GR5 1 2 13x3 1 2 1 Bolt GR5 1 2 13 x 2 1 2 3 Zinc Flat Washer 1 2 3...

Page 6: ...e Secures the fan to the structure and allows the fan to hang in a vertical direction C Extension Bar Extends the fan from the ceiling to reach optimum operating height D Chassis Housing for the motor and gear reducer E Blade Provides air movement F Wingtip Fence Improves air movement efficiency by reducing drag A B C D E F ...

Page 7: ... than 15 of its diameter to any object or its path If this is an issue mounting extension bars and smaller fans are available from S P 2 3 Fire Suppression Systems and Fan Placement If installing Fans in a location where fire sprinklers are in place do not interfere with their correct operation Fans should be located in the center of each sprinkler quadrant and no less than 3 feet below the sprink...

Page 8: ...y Cables These are supplied with every fan You must install safety cable for warranty to be in effect 3 4 Guy Wires While in operation a fan can sway due to minor imbalance or because of wind Since the mounting system is capable of swiveling it will not stop fan movement so it is important that the guy wires be installed properly Proper installation includes the angle and tension of the guy wires ...

Page 9: ...oving equipment when measured from the center of the fan to the equipment The spacing between multiple fans should be no less than 2 5x the fans diameter when measured from the center of the fans 4 2 Electrical Installation To reduce the risk of electrical shock wiring should be performed by a qualified electrician Incorrect assembly can cause electric shock or damage the motor and controller The ...

Page 10: ...rom Building Structure All mounting instructions assume that the building structure from which the fan will be hung is of sound construction undamaged and capable of supporting loads of up to 650 lbs 295 kg It is the sole responsibility of the customer to verify that the building s structure is adequate for fan installation S P recommends consulting with a structural engineer prior to fan installa...

Page 11: ...tructure du toit à chaque extrémité Fasten the unistrut to the roof structure mounting points at each end with customer supplied Grade 5 hardware as shown Fixez l unistrut aux points de fixation de la structure du toit à chaque extrémité avec le matériel de qualité 5 fourni par le client comme illustré ATTENTION Do not tighten the hardware until the upper yoke has been mounted to the unistrut Grad...

Page 12: ... de faisceaux WARNING AVERTISSEMENT Do not install the fan from a single purlin truss or bar joist Ne pas installer le ventilateur à partir d une seule panne botte ou solives Unsupported angle iron spans should not exceed 12 3 7m Non pris en charge travées de fer d angle ne doit pas dépasser 12 pi 3 7 m Do not install motor and hub assembly directly on angle iron Ne pas installer moteur et moyeu d...

Page 13: ...r if span is longer than 8 If the angle iron span is 8 2 4m or less proceed to step 5 6a on the following page If the angle iron span is longer than 8 2 4m it is necessary to use double angle irons Locate the center of the angle iron length Drill 9 16 1 4cm diameter hole through the center of the vertical wall of the angle iron Drilling through a total of four angle irons Place two drilled angle i...

Page 14: ... d 4 1 2 Nylock Nut Do not install the fan from a single purlin truss or bar joist Ne pas installer le ventilateur à partir d une même purlin botte ou solives The angle irons must be fastened to the roof structure at each end Les cornières doivent être attachés à la structure de toit à chaque extrémité Fasten the angle irons to the roof structure mounting points at each end with customer supplied ...

Page 15: ...stall the fan from a single purlin truss or bar joist Ne pas installer le ventilateur à partir d une même purlin botte ou solives The angle irons must be fastened to the roof structure at each end Les cornières doivent être attachés à la structure de toit à chaque extrémité Fasten the angle irons to the roof structure mounting points at each end with customer supplied Grade 5 hardware as shown Fix...

Page 16: ...3 Nylock Nut The angle irons should be aligned with the innermost holes of the upper yoke Les fers angulaires doivent être alignés avec les trous les plus à l intérieur de la culasse supérieure After attaching upper yoke to the angle irons tighten all the bolts securing the angle irons to the roof structure to 90 ft lb 122 N m using a 3 4 socket with torque wrench Après l avoir fixée culasse supér...

Page 17: ...ng Plate Hardware purchased separately a 4 1 2 13x2 1 2 GR 5 Bolt b 8 1 2 Flat Washer c 4 1 2 13 Nylock Nut d 2 Clamping Plate Install the Clamping Shims only if the thickness of the I beam flange exceeds 3 8 1cm The mounting holes of the shim are closer to one side than the other Make sure this side is facing the I beam Installez les cales de serrage que si l épaisseur de la semelle de la poutre ...

Page 18: ...des of the plate for each bolt 5 12 Pre Drill Angle Iron Brackets Holes Your angle iron should be cut to allow 1 2 1 27 cm clearance between the end of the angle iron and the purlin you are mounting to Drill one 9 16 1 4 cm diameter hole centered vertically exactly 1 2 54 cm from the edge on both ends of the vertical wall of the angle iron Drill a second hole exactly 3 7 6 cm inward from the first...

Page 19: ... of the purlin brackets 5 15 Attach Upper Yoke to Angle Iron Attach the upper yolk to the angle irons using the provided 1 2 grade 5 bolts washers and nylock nuts See section 5 7 Attach Upper Yoke to Angle Iron to continue installation Purlin Bracket Hardware per set supplied a 2 1 4 Formed Steel Purlin Bracket b 2 1 4 Steel Purlin Backplate c 16 1 2 13 1 3 4 GR 5 Bolt d 16 1 2 Nylock Nut e 32 1 2...

Page 20: ...d a 2 1 2 13x 3 1 2 GR 5 Bolt b 4 1 2 Flat Washer c 2 1 2 13 Nylock Nut Cable End Detail The safety cable is a critical safety feature of the fan and must be installed correctly Le câble de sécurité est une caractéristique de sécurité essentielle de la soufflante qui doit être installé correctement WARNING AVERTISSEMENT 6 2 Secure Upper Safety Cable Secure the safety cable to the I beam or angle i...

Page 21: ... ne pas installer le ventilateur à la fois horizontalement et verticalement entraînera une usure inégale du roulement du moteur et du roulement de la boîte de vitesses ce qui peut entraîner des dommages ou une durée de vie raccourcie Ne pas installer le niveau annulera la garantie du fabricant WARNING AVERTISSEMENT 6 3 Attach the Motor to extension tube Attach the lower yoke on the chassis to the ...

Page 22: ...stration on page 23 1 Slide the unlooped end of the guy wire through the eye hook 2 Feed the wire through the loop on the other end of the wire 3 Pull tight so the wire tightens on the eye hook Attach each guy wire to the loop on the mid section of the motor 1 Slide the gripple fastener as supplied over the opposite end of the wire 2 Feed the end of the guy wire through the guy wire loop on the fa...

Page 23: ... a Beam Clamp b Eye Hook c Gripple Wire Loop Gripple Maximum Angle Gripple Hook Tab Motor 45 Maximum Guy Wire a b c Make certain all electrical cords are not obstructed by guy wires Assurez vous que tous les câbles électriques ne soient pas obstruées par des haubans WARNING AVERTISSEMENT a Gripple Hook Tab b Guy Wire c Gripple Fastener a c b ...

Page 24: ...24 8 INSTALLING BLADES 8 1 Attach Blades to Hub Slide blade onto struts until blade holes and strut holes are aligned ...

Page 25: ...Zinc Split Lock Washer 5 16 ATTENTION Upon completion of the mechanical installation of the fan and before powering on spin the fan around multiple times by hand to ensure all brackets are clear from contact with other parts on the fan Thoroughly inspect the hub the bolts and brackets within the hub to guarantee clear and proper rotation If you find that the fan has a bracket that is hitting anoth...

Page 26: ... 4 c 12 Zinc Split Lock Washer 5 16 Top of Blade To reduce the risk of personal injury do not bend the blade brackets when installing the brackets balancing the blades or cleaning the fan Do not insert foreign objects in between rotating fan blades Pour réduire le risque de blessure ne pas plier les crochets lame lors de l installation les crochets l équilibre entre les lames ou de nettoyer la ven...

Page 27: ...ter blade has been securely attached to the strut Fasten wingtip to blade using a 10 32 X 5 8 Button Cap 8 INSTALLING BLADES 8 3 Wingtip Assembly Wingtip Hardware Kit supplied a 6 10 32x3 8 BTN Cap Screw Wingtip Wingtip Blade BTN Cap Screw ...

Page 28: ...ctor to be connected to an ungrounded conductor of power supply conductor of fan identified for equipment grounding to be connected to an equipment grounding conductor S P is not liable for any voltage disturbances with explicit reference to electronic magnetic interference EMI Voltage disturbance refers to transient overvoltage voltage unbalance voltage swells rapid voltage change flicker superim...

Page 29: ...s at the fan controllers disconnect L1 L2 L3 Wait three 3 minutes for capacitors to discharge to safe voltage levels Darkened display LEDs are NOT an indication of safe voltage levels Failure to do so many result in personal injury or death DO NOT DISASSEMBLE THE MOTOR OR ITS ONBOARD DRIVE Doing so greatly increases the risk of shock Les contrôleurs de ventilateur contiennent des condensateurs à h...

Page 30: ...ilateur For use with manufacturer supplied motor and drive only Not for use with other speed control devices Pour utilisation avec le moteur fourni par le fabricant et le lecteur uniquement Ne pas utiliser avec d autres appareils de contrôle de vitesse To avoid a short circuit be very careful not to get metal chips in the control Pour éviter un court circuit faire très attention de ne pas obtenir ...

Page 31: ...hrough the top plate of the chassis and directly in to the motor electrical box See wiring diagrams below 9 3 Input Power Cable Wiring Schematics IMPORTANT Grounding of the incoming power on the motor is required NOTE S P Suggests using a field supplied fused disconnect switch 1 Phase Voltage 120V 1Ph 230V 1Ph Motor wire can be ran through the wire hole on the chassis then alongside or within the ...

Page 32: ...to a Fire Alarm Panel If the installation of the fan is required to be wired to a fire alarm emergency shut off an external relay will have to be placed by a fire suppression specialist between the voltage line feed and the fan s Power Supply ...

Page 33: ...controller and from the controller to the supply b Do not run your controller and sensitive equipment on the same power line c Install properly sized EM RFI filter d Contact Customer Service at 1 800 961 7370 5 LED indicator is not blinking in normal fashion Please contact S P customer service to resolve issue WARNING AVERTISSEMENT Electrical Shock Hazard RISQUE D ÉLECTROCUTION Risk of fire electr...

Page 34: ...s Is the input voltage correct Fix incorrect wiring Is the fan making any noise End of troubleshooting Yes Yes Yes No No No Check splices and wiring at the controller Is the Wiring correct No Fix incorrect wiring No Yes Yes No Check controller wiring sheet Is the wiring correct Fix incorrect wiring No Yes Check all brackets and bolts Ensure bolts are torqued to the proper rating and brackets are f...

Page 35: ...he fan motor Under volt may be occurring a line reactor may need to be placed to reach correct voltage Vibration 8 Blinks Second Check all brackets and bolts Ensure bolts are torqued to the proper rating Overtemp 7 Blinks Second If multiple fan diameters are being used make sure the correct blades are on the motor Verify that no external disturbances are occurring with the blades No LED Light If i...

Page 36: ...hock or injury to persons during cleaning and user maintenance Risque d incendie de choc électrique ou de blessures lors du nettoyage et de l entretien par l utilisateur Disconnect the appliance from the power supply and allow sufficient time for electrical discharge before servicing Débranchez l appareil de l alimentation électrique et laisser suffisamment de temps pour la décharge électrique ava...

Page 37: ...37 11 USER SERVICING INSTRUCTIONS Maintenance Log Replacement Part List Date Maintenance Performed Replacement Parts Required Part No Description ...

Page 38: ...38 NOTES ...

Page 39: ...39 NOTES ...

Page 40: ......

Reviews: