FLOOR STAND TYPE AIR CONDITIONER

( Cooling and Heating )

INSTALLATION

MANUAL

APV48Q0AN

 APV48QOAN_E_IM_00000  2008.10.20  11:5 PM  Page 17

                                                                                              Air Marketing Group LLC 
141 Kinderkamack Rd, Park Ridge, NJ 07656  Tel: 201-782-1782  Fax: 201-782-1783 Web: www.amgair.com Email: [email protected]

 

Summary of Contents for APV48Q0AN

Page 1: ...ÑOL FRANÇAIS FLOOR STAND TYPE AIR CONDITIONER Cooling and Heating INSTALLATION MANUAL APV48Q0AN Air Marketing Group LLC 141 Kinderkamack Rd Park Ridge NJ 07656 Tel 201 782 1782 Fax 201 782 1783 Web www amgair com Email info amgair com ...

Page 2: ...witch the unit off and disconnect it from the power supply In order to prevent electric shocks fires or injuries always stop the unit disable the protection switch and contact SAMSUNG s technical support if the unit produces smoke if the power cable is hot or damaged or if the unit is very noisy Always remember to inspect the unit electric connections refrigerant tubes and protections regularly Th...

Page 3: ...power is sufficient to ensure the operation of any other domestic appliance connected to the same electric lines Always verify that the cut off and protection switches are suitably dimensioned Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring diagram included in the manual Always verify that electric connections cable entry ...

Page 4: ...marks Part Name ø9 52mm 3 8 inch ø19 05mm 3 4 inch Wire of sensor 2 strand 8 9 10 11 12 13 Pipe band Putty Drain plug Cover hole No Part Name Screw The type and quantity may differ depending on the specifications Cable tie Air Marketing Group LLC 141 Kinderkamack Rd Park Ridge NJ 07656 Tel 201 782 1782 Fax 201 782 1783 Web www amgair com Email info amgair com ...

Page 5: ...f the outdoor unit do not disturb the neighborhood Take special care not to cause any inconvenience to your neighbors when installing the unit on the borderline with your neighborhood A place where strong wind does not head against the air outlet of the outdoor unit If a strong wind heads directly against the air outlet at the time of cooling operation a safety device can be operated Do not instal...

Page 6: ...e of electric wires from to the indoor outdoor unit Size of electric input wires Switch Fuse APV48Q0AN 1ø 208 230V 60Hz 50 A 30 A 30 A 2 0mm2 0 75mm2 4mm2 Electric power specification CAUTION Be sure to use the wires and switches or fuses of power distribution board are qualified and fulfill the specifications Be sure to install knife switch or circuit breaker on the power distribution board The e...

Page 7: ...t wires are purchased by the user separately 3 Connect the electric wires to each terminal on the indoor and outdoor unit respectively When connecting 3Phase 4wires 380V AC OUTDOOR SIDE Power terminals on the outdoor unit Connector Blue Brown Blue Brown Knife switch or automatic circuit breaker NFB Electric input wires Indoor outdoor unit connecting wire Wire of sensor A Air Marketing Group LLC 14...

Page 8: ...nel of the outdoor unit 2 Disconnect the connector A R L connection from the outdoor unit 3 Connect the electric input wires R S T to each terminal R S T and input wires N L to each terminal N L of the electric box on the outdoor unit respectively Input wires are purchased by the user separately 4 Connect the electric wires to each terminal on the indoor and outdoor unit respectively OUTDOOR SIDE ...

Page 9: ...akage of refrigerant 4 Be sure to insulate the pipe with appropriate insulation material 5 Insert the drain hose into the drain pipe and connect them by tying them to the cable tie to prevent any water leakage 6 After completion of the installation check the connecting area for any gas leakage 7 Wind a finish tape when the wiring of the refrigerant pipe the unit and the drain piping are completed ...

Page 10: ...fficult 3 You may use the spring inserted into the gas pipe instead of the bender to bend the pipe 4 When you bend the pipe using the spring hold the pipe with both hands to prevent any distortion and secure a minimum bending radius of more than 100mm Tightening of Connection Parts Align the center of the connection piping and tighten the flare nut by turning it with hand Then tighten it again usi...

Page 11: ...nward 2 If there is any foreign substance in the drain plate it may clog the drain pipe Therefore be sure to remove the foreign substance inside after installation 3 After completion of installation be sure to pour water into the drain pan and then check the draining condition There is no problem in draining when the draining is completed within 20 seconds Foamed Polyethylene Insulator Vinyl Chlor...

Page 12: ...old gauge clockwise Make sure that pressure gauge show 0 1MPa 76cmHg after about 30 minutes This procedure is very important in order to avoid gas leak Turn off the vacuum pump Remove the hose of the low pressure side of manifold gauge 5 Set valve cork of both liquid side and gas side of packed valve to the open position 6 Mount the valve stem nuts and the service port cap to the valve and tighten...

Page 13: ...pressure gauge Check whether the low pressure side is within the range of 8 2 9 3kg cm2 G outside temperature 35 C Stop operation Close the gas pipe side valve and loosen the pressure gauge connected Then open the gas pipe side valve again Tighten the cap of each valve using a specified tool OUTDOOR UNIT Gas pipe side Liquid pipe side CAUTION Always use R410A refrigerant to avoid damage of the uni...

Page 14: ...2 Is the drain hose properly connected 3 Is the insulation of the piping in good condition 4 Is grounding properly made Insulation Indoor connection area Outdoor connection area Indoor and outdoor unit connection Drain hose Air Marketing Group LLC 141 Kinderkamack Rd Park Ridge NJ 07656 Tel 201 782 1782 Fax 201 782 1783 Web www amgair com Email info amgair com ...

Page 15: ...ng the electronic contactor as it is very dangerous This is very dangerous as the protective device does not work 3 Be sure to perform the test operation after installation It is easy to start the test operation in winter if you increase the sensor temperature to 23 C 25 C by holding the indoor temperature sensor Cooling operation When the outdoor temperature is below zero do not test operation fo...