Summary of Contents for AM KNQD Series

Page 1: ...DB68 06417A 00 DVM Boracay_IM_EN_DB68 06417A 00_16 09 22 indd 36 2016 9 22 11 29 08 ...

Page 2: ...l AM KNTD AM KNQD Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference DVM Boracay_IM_EN_DB68 06417A 00_16 09 22 indd 1 2016 9 22 11 29 09 ...

Page 3: ...s Step 7 Performing leak test Step 8 Wrapping the pipes with the insulation Step 9 Installing the drain hose Step 10 Optional Changing direction of the drain hose Step 11 Connecting the power and communication cables Step 12 Optional Extending the power cable Step 13 Setting an indoor unit address and installation option Step 14 Performing the final check Step 15 Providing information for user App...

Page 4: ...AMSUNG s technical support if the unit produces smoke if the power cable is hot or damaged or if the unit is very noisy Always remember to inspect the unit electric connections refrigerant tubes and protections regularly These operations should be performed by qualified personnel only The unit contains moving parts which should always be kept out of the reach of children Do not attempt to repair m...

Page 5: ...m power cable modification extension wiring and multiple wire connection It may cause electric shock or fire due to poor connection poor insulation or current limit override When extension wiring is required due to power line damage refer to Step 12 Optional Extending the power cable in the installation manual CAUTION Make sure that you earth the cables Do not connect the earth wire to the gas pip...

Page 6: ...orted or noise from being generated As far away as possible from fluorescent and incandescent lights so that the remote control can be operated well A place where the air filter can be replaced easily CAUTION Avoid the following places to prevent malfunction of the unit Where there is machine oil Salty environment such as the seaside areas Where sulfide gas exists Other special atmosphere areas Sp...

Page 7: ... attention to the weight of the indoor unit NOTE If you mount the plate to a concrete wall by using plastic anchors make sure that gaps between the wall and the plate created by projected anchor are less than 20 mm 3 If you fix the indoor unit to a window frame follow 4 to 6 4 Determine the positions of the wooden uprights to be attached to the window frame 5 Attach the wooden uprights to the wind...

Page 8: ...the cut edges 3 Remove the protection caps of the pipes and connect the assembly pipe to each pipe Tighten the nuts first with your hands and then with a torque wrench applying the following torque Torque wrench Flare nut Union Spanner Refrigerant oil Outer diameter mm Torque N m Torque kgf cm 6 35 14 18 140 180 9 52 34 42 350 430 12 70 49 61 500 620 15 88 68 82 690 830 NOTE If you want to shorten...

Page 9: ... type Unit mm Outer diameter A Flare tool for R410A clutch type Conventional flare tool Clutch type Wing nut type 6 35 0 0 5 1 0 1 5 1 5 2 0 9 52 0 0 5 1 0 1 5 1 5 2 0 12 70 0 0 5 1 0 1 5 1 5 2 0 15 88 0 0 5 1 0 1 5 1 5 2 0 5 Check if you flared the pipe correctly There are some examples of incorrectly flared pipes below Inclined Damaged Surface Cracked Uneven Thickness 6 Align the pipes and tight...

Page 10: ...e pipe hose and cables Then place the indoor unit on the installation plate 1 To avoid condensation problems place heat resistant poly ethylene foam separately around each refrigerant pipe in the lower part of the indoor unit 2 Wrap the refrigerant pipe and the drain hose in the rear of the indoor unit with the absorbent pad NOTE Wind the pipe and hose three times to the end of the indoor unit wit...

Page 11: ... t use the other drain hose hole block it with a rubber stopper 4 Pass the drain hose under the refrigerant pipe keeping the drain hose tight 5 Pass the drain hose through the hole in the wall Check if it slants downwards as seen in the picture NOTE The hose will be fixed permanently into position after finishing the installation and the gas leak test refer to page 12 for further details DO NOT WA...

Page 12: ...wer cable 1 L 2 N by 100 mm 100mm 6 Connect the earth cable to the plate on the evaporator as like the following picture Power earth cable 7 Connect F3 F4 for communication wires at the back side of the indoor unit when installing the wired remote control N L N L N L N L ELCB MCCB ELB V1 V2 Outdoor Unit Indoor Unit 1 Indoor Unit 2 Indoor Unit 3 Indoor Unit 4 Indoor Unit 5 Indoor Unit 6 EEV kit 220...

Page 13: ... 2 5 mm2 2 5 mm2 0 75 1 5 mm2 Refer to the unit nameplate for rating current Decide the capacity of ELCB or MCCB ELB by below formula Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord Code designation IEC 60245 IEC 57 CENELEC H05RN F or IEC 60245 IEC 66 CENELEC H07RN F The capacity of ELCB or MCCB ELB X A 1 25 X 1 1 X Ai X Th...

Page 14: ...vant local and national regulations Wire size must comply with local and national code For the power cable use the grade of H07RN F or H05RN F materials You should connect the power cable into the power cable terminal and fasten it with a clamp The unbalanced power must be maintained within 10 of supply rating among whole indoor units If the power is unbalanced greatly it may shorten the life of t...

Page 15: ...p the head and make proper tightening impossible Over tightening the terminal screws may break them See the table below for tightening torque for the terminal screws Tightening torque N m kgf cm M3 5 0 8 1 2 8 0 12 0 M4 1 2 1 8 12 0 18 0 Step 12 Optional Extending the power cable 1 Prepare the following tools Tools Spec Shape Crimping pliers MH 14 Connection sleeve mm 20xØ6 5 HxOD Insulation tape ...

Page 16: ...re and position your contraction tube in the middle of the insulation tape Three or more layers of insulation are required Method 1 Method 2 Insulation tape Insulation tape 40 mm 35 mm 6 Apply heat to the contraction tube to contract it Contraction tube 7 After tube contraction work is completed wrap it with the insulation tape to finish Insulation tape CAUTION Make sure that the connection parts ...

Page 17: ...g High Temp button and Low Temp button 3 Check if you have entered the option setting status 4 After entering the option setting status select the option CAUTION Option setting is available from SEG1 to SEG 24 SEG1 SEG7 SEG13 SEG19 are not set as page option Set the SEG2 SEG6 SEG8 SEG12 as ON status and SEG14 18 SEG20 24 as OFF status SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 0 X X X X X SEG7 SEG8 SEG9 SEG10 ...

Page 18: ...ess the button will be selected in rotation SEG4 SEG5 4 Setting Dry mode Press Mode button to be changed to Dry mode in the ON status 5 Setting SEG6 SEG8 option a Press Low Fan button to enter SEG6 value b Press High Fan button to enter SEG8 value Each time you press the button will be selected in rotation SEG6 SEG8 6 Setting Fan mode Press Mode button to be changed to Fan mode in the ON status 7 ...

Page 19: ...OFF status 11 Setting SEG14 SEG15 option a Press Low Fan button to enter SEG14 value b Press High Fan button to enter SEG15 value Each time you press the button will be selected in rotation SEG14 SEG15 12 Setting Cool mode Press Mode button to be change to Cool mode in the OFF status 13 Setting SEG16 SEG17 option a Press Low Fan button to enter SEG16 value b Press High Fan button to enter SEG17 va...

Page 20: ...ode button to be change to Heat mode in the OFF status 19 Setting SEG23 SEG24 mode a Press Low Fan button to enter SEG23 value b Press High Fan button to enter SEG24 value Each time you press the button will be selected in rotation SEG23 SEG24 5 After setting option press button to check whether the option code you input is correct or not 6 Press operation button with the direction of remote contr...

Page 21: ...dication DetailsI Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 A unit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Setting RMC address Group channel 16 Group address Indication and Details Indication Details Indication Details Indication Details Indic...

Page 22: ...SEG10 SEG11 SEG12 1 EEV Step when heating stops SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 External control External control output External heater On or Off signal S Plasma ion Buzzer Number of hours using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control of a remote control Heating setting compensation Removing condensated water in heating mode EEV Step of stopped unit during oil return...

Page 23: ... SEG9 SEG10 SEG11 SEG12 Explanation PAGE EEV Step when heating stops Indication and Details Indication Details Indication Details Indication Details Indication Details 1 0 Default value 1 Stopped Unit s Noise Decreasing Setting 2 B Running Unit s Noise Decreasing Setting 3 Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation PAGE Use of external control Setting the output of external control Ext...

Page 24: ... seconds at an interval of 5 minutes in Heat mode 2 1 Fan is turned on continually when the hot water heater is turned on 3 Fan is turned off when the hot water heater is turned on with cooling only indoor unit Cooling only indoor unit To use this option install the Mode Select switch MCM C200 on the outdoor unit and fix it as Cool mode 3 It is only for wall mounted indoor unit with EEV Integrated...

Page 25: ... C200 on the outdoor unit and fix it as Cool mode If Fan is set to off for cooling only indoor unit by setting the SEG9 3 or SEG15 3 you need to use an external sensor or wired remote control sensor to detect indoor temperature exactly 5 Default setting value 4Way Cassette Mini 4Way Cassette 5 C Other indoor units 2 C 6 This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only If...

Page 26: ... when using hot water external heater SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 05 series installation option Detailed Option No 02XXXX 1XXXXX 2XXXXX 3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE MODE Use of Auto Change Over for HR only in Auto mode When setting SEG3 Standard heating temp Offset When setting SEG3 Standard cooling temp Offset When setting SEG3 Standard for mode change He...

Page 27: ...5 30m or 2 Distance2 is 50 110m 6 Use 6sec 5 3 5 5 15 min 7 Use 7sec 6 4 6 7 20 min 8 Use 8sec 7 4 5 30 min 9 Use 9sec A Use 10sec B C D E F Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation Set to variable breeze Control variables when using hot water external heater Indication and Details Indication Details Indication Details Set temp for heater On Off Delay time for heater On 2 0 0 0 At th...

Page 28: ...ame time as the heating thermostat is on and turned off when the heating thermostat is off e g 2 Setting 02 series SEG15 2 Setting 05 series SEG18 A Room temp set temp f heating compensation temp External heater is turned on when the temperature is maintained as 4 5 C for 10 minutes Room temp set temp f heating compensation temp External heater is turned off when the temperature is maintained as 4...

Page 29: ...s setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE MODE The option mode you want to change The tens digit of an option SEG you will change The unit digit of an option SEG you will change Changed value Indication 0 D 2 1 7 1 CAUTION I...

Page 30: ... The appropriate indicator lights up and the air conditioner operates according to the selected mode or function 4 Press the button and check the following The airflow blades work properly Step 15 Providing information for user After finishing the installation of the air conditioner you should explain the following to the user Refer to appropriate pages in the user installation manual 1 How to sta...

Page 31: ...ror on Eva out sensor Short or Open Discharge sensor error Short or Open E122 E123 E126 Indoor fan error E154 Error on outdoor temperature sensor Short or Open Error on cond sensor Error on discharge sensor Other outdoor unit sensor error that is not on the above list E221 E237 E251 When there is no communication between the indoor outdoor units for 2 minutes Communication error received from the ...

Page 32: ...sensor is detached Low pressure sensor is detached Outdoor unit copression ration error Outdoor sump down_1 prevetion control Compressor down due to low pressure sensor prevention control_1 Simultaneous opening of cooling heating MCU SOL valve 1st detection Simultaneous opening of cooling heating MCU SOL valve 2nd detection Other outdoor unit self diagnosis error that is not on the above list E241...