ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION.

3900 Dr. Greaves Rd.          •          Kansas City, MO 64030          •           (816) 761-7476          •         FAX (816) 765-8955

INSTALLATION INSTRUCTIONS

1

1

/

2

HOUR UL CLASSIFIED

CURTAIN TYPE (D)IBD2,  (D)IBD2SS AND (D)IBDT FIRE DAMPERS

APPLICATION

The fire damper models shown on this sheet are marked with a

1

1

/

2

hour fire damper label and are approved for use in fire walls or

masonry floors with ratings of less than 3 hours. Fire Dampers

require a field-or factory-installed sleeve. Select a sleeve of suffi-

cient length to permit mounting angles attachment

.

Static and

Dynamic dampers must be installed with leading edge of the

closed blades within the wall or floor.

STATIC FIRE DAMPERS

–  IBD models

Not for use in Dynamic (fans on) Systems.

MODEL IBD2 MAXIMUM SIZE

Single Section

Vertical Installation – 48"w x 30"h or 33"w x 72"h  (1219 x 

762 or 838 x 1829) or 36"w x 36"h (914 x 914).

Horizontal Installation –  30"w x 45

1

/

2

"h (762 x 1156) or 33"w

x 38"h (838 x 965).

Multiple Section Assembly

Vertical Installation – 120"w x 72"h (3048 x 1829).

Horizontal Installation – 90"w x 91"h (2286 x 2311) or 114"w x

38"h (2896 x 965). 

MODEL IBD2SS MAXIMUM SIZE

Single Section

Vertical Installation – 48"w x 30"h or 33"w x 72"h (1219 x 

762 or 838 x 1829) or 36"w x 36"h (914 x 914).

Horizontal Installation –  30"w x 45

1

/

2

"h (762 x 1156) or 33"w

x 38"h (838 x 965).

Multiple Section Assembly

Vertical Installation – 99"w x 72"h (2515 x 1829).

Horizontal Installation – 90"w x 91"h (2286 x 2311) or 114"w x

38"h (2896 x 965). 

MODEL IBDT, IBDT1 and IBDT2 MAXIMUM SIZE

Single Section

Vertical Installation – 40"w x 48"h (1016 x 1219).

Horizontal Installation – 36"w x 36"h (914 x 914).

Notes:

1. Dimensions shown in parentheses (   ) indicate millimeters.
2. All multiple section dampers are constructed of equal single

section sizes no greater than the maximum single section sizes

indicated above

II-IBD-618/

Replaces II-IBD-616

© Ruskin June 2018

DYNAMIC FIRE DAMPERS

Use in Dynamic (fans on) or Static (fans off) Systems

MODEL DIBD2 MAXIMUM SIZE

Single Section

Vertical Installation – 33"w x 36"h (838 x 914).

Horizontal Installation – 24"w x 24"h (610 x 610).

Multiple Section Assembly

Vertical Installation – 72"w x 48"h (1828 x 1219) or 48"w x 

72"h (1219 x 1828) or 120"w x 24"h (3048 x 610).

MODEL DIBD2X MAXIMUM SIZE

Single Section

Vertical Installation – 18"w x 24"h (457 x 610).

Horizontal Installation – 18"w x 24"h (457 x 610) or 24"w x

18" h (610 x 457).

Multiple Section Assembly

Horizontal Installation – 36"w x 48"h (914 x 1219)  or 48"w x 

36"h (1219 x 914).

MODEL DIBD2SS MAXIMUM SIZE

Single Section

Vertical or Horizontal Installation – 24"w x 24"h (610 x 610).

Multiple Section Assembly

Vertical Installation – 72"w x 48"h (1828 x 1219) or 48"w x

72"h (1219 x 1828) or 90”w x 24”h (2286 x 610).

MODEL DIBDT, DIBDT1 and DIBDT2 MAXIMUM SIZE

Single Section

Vertical Installation – 24”w x 24”h (610 x 610).

INSTALLATION SUPPLEMENTS

Refer to the appropriate Ruskin installation instruction supplements

for additional information or special requirements:

• Optional Sealant of Dampers in Fire Rated Wall or Floor

Openings

• Transfer Openings and Duct Terminations

• Optional FireStop Material

• Extension of Fire and Combination Fire and Smoke Damper

Sleeves

• Fire  and  Combination  Fire/Smoke  Dampers  Installation  in

Concrete Floor with Steel Deck

• Drivemate No. 14880 Breakaway Connection

• Flanged System Breakaway Connections

• Mullions for Dampers in Oversized Concrete Wall Openings

California State Fire Marshal Listing No. 3225-245:005 