background image

Long range Multi Reader  

AY-Z12A 

Installation Guide 

 

December 2010 

 

 

Summary of Contents for AY-Z12A

Page 1: ...Long range Multi Reader AY Z12A Installation Guide December 2010 ...

Page 2: ......

Page 3: ...talling the AY Z12A Long Range Reader 5 3 2 1 Single Reader Installation 6 3 2 2 Multiple Reader Installation 7 3 2 3 Installation process 7 4 Wiring and Configuration Instructions 8 4 1 Wiring instructions 8 4 2 Single Reader Configuration 9 4 3 Multiple Reader Configuration 10 5 Operation Instructions 11 Appendix A Limited Warranty 12 Appendix B Technical Support 14 ...

Page 4: ...imity card reader utilized with access control systems The reader can function in one of two scenarios Single reader installation default Multiple readers installation Figure 1 The AY Z12A Long Range Reader This Manual contains the following information Installation Wiring Instructions Operation Instructions ...

Page 5: ...stance Weigand 26 output format with a 23 6 60 cm maximum read range Environmental Characteristics Operating Temp Range 22 F to 145 F 30 C to 63 C Operating Humidity 0 95 non condensing Suitable for outdoor use IP54 Dimensions Height x Width x Depth 11 81 x 11 81 x 1 0 300mm x 300mm x 25 4 mm Weight 2 35 Lbs 1066g For maximum range set the reader as a single reader use Rosslare s AT R14 clamshell ...

Page 6: ...stallation procedure One Installation Template Four pan head screws wall plugs One L shaped security screw tool Three Security screws 3 2 Installing the AY Z12A Long Range Reader Figure 2 Removing the Top Cover Figure 2 shows the front view of the AY Z12A Long Range Reader When installing the reader you must remove the snap off cover to access the screw holes ...

Page 7: ... Spacer sold separately as described in the image below for a max range of 43cm 17 inch Figure 3 Installing the unit with the MP Z02 spacer 3 2 1 Single Reader Installation The AY Z12A Long Range Reader is designed to function with the best performance when installed isolated from other AY Z12A long range readers at least in a range of 2 4 meters the reader is therefor preconfigured as a single in...

Page 8: ...ge 10 for detailed configuration instructions 3 2 3 Installation process The physical installation of the unit is described below To Install the Reader 1 Determine an approximate location for the installation of the Reader 2 Peel off the back of the self adhesive installation label template and locate it at the required location 3 Using the template as a guide drill holes the size of which are ind...

Page 9: ... by cutting its jacket back 1 and strip the insulation from the wires 2 Prepare the Controller cable by cutting its jacket back 1 and strip the insulation from the wires 3 Splice the Reader s pigtail wires to the corresponding Controller wires and cover each joint with insulating tape If the tamper output is being utilized connect the purple wire to the correct input on the Controller Reader Color...

Page 10: ...ion For single reader installation follow the configuration process below this process is not required with new readers as it comes preconfigured from the factory to function as a single door reader To configure a single reader installation mode 1 Turn the reader power OFF 2 Connect the Data 1 wire White cable to Ground 3 Leave the LED Control wire Brown cable floating 4 Turn the reader power ON 5...

Page 11: ...ct the LED Control wire Brown cable to Ground 4 Turn the reader power ON 5 Release the LED Control wire from the Ground Reader LED turns Orange 6 Reconnect the LED Control wire Brown cable to Ground 7 The Reader s LED starts flashing continuously and the Buzzer sounds 8 Turn the reader power OFF 9 Disconnect the Data 1 wire White cable from the Ground 10 The Reader configuration for multiple reade...

Page 12: ...ng properly The LED returns to its idle state red 2 Present the appropriate type of proximity card to the Reader The LED will flash green briefly and a short beep is emitted thus indicating that the card was read properly The Reader transmits the card s data to the Controller the Controller checks the data if the card transmission is valid the LED changes briefly to green Refer to the Controller s...

Page 13: ...his warranty Unless otherwise requested by ROSSLARE ENTERPRISES LTD AND OR SUBSIDIARIES representative return of the failed product s is not immediately required If ROSSLARE has not contacted the Customer within a sixty 60 day holding period following the delivery of the warranty claim Customer will not be required to return the failed product s All returned Product s as may be requested at ROSSLA...

Page 14: ...ct if Product disassembled or repaired in such a manner as to adversely affect performance or prevent adequate inspection and testing to verify any warranty claim ROSSLARE does not warrant the installation maintenance or service of the Product Service life of the product is dependent upon the care it receives and the conditions under which it has to operate In no event shall Rosslare be liable for...

Page 15: ...s and Canada 1600 Hart Court Suite 103 Southlake TX USA 76092 Toll Free 1 866 632 1101 Local 1 817 305 0006 Fax 1 817 305 0069 E mail support na rosslaresecurity com Europe Global Technical Support Training Center HaMelecha 22 Rosh HaAyin Israel 48091 Tel 972 3 938 6838 Fax 972 3 938 6830 E mail support eu rosslaresecurity com South America Presbitero Actis 555 Oficina 31 San Isidro Buenos Aires A...

Page 16: ......