background image

0MNACCSA3ENUC 

 

 

 
 
 
 

 

 

 
 
 
 

 

 
 
 
 
 

 

 

Summary of Contents for NetMan 202 plus

Page 1: ...0MNACCSA3ENUC ...

Page 2: ... User SAFETY This part of the manual contains SAFETY precautions that must be followed scrupulously The device has been designed for professional use and is therefore not suitable for use in the home The device has been designed to operate only in closed environments It should be installed in rooms where there are no inflammable liquids gas or other harmful substances Take care that no water or li...

Page 3: ...he different material of which the packaging is made and dispose of all material in compliance with applicable standards in the country in which the product is used DISPOSING OF THE PRODUCT The device contains electronic PCBs and batteries which are considered TOXIC When the product reaches the end of its operating life dispose of it in accordance with applicable local legislation Disposing of the...

Page 4: ..._______________________________________________________ 11 Reports_________________________________________________________________ 12 UPS VALUES AND EVENTS HISTORY LOG ARCHIVE _______________________________13 Eventlog________________________________________________________________ 13 Datalog_________________________________________________________________ 14 ENVIRONMENTAL SENSORS OPTIONAL ______...

Page 5: ..._____________________________________ 33 Sensors Config menu_____________________________________________________ 33 I O Sensors menu ________________________________________________________ 35 Threshold sens menu_____________________________________________________ 36 Security menu ___________________________________________________________ 37 Save and load menu __________________________________...

Page 6: ...twork protocols SNMP v1 and v3 TCP IP HTTP and so on and is compatible with Ethernet 10 100Mbps IPv4 6 networks The UPS can therefore be integrated easily into medium and large sized networks The device also records UPS values and events in the history log archive NetMan 202 plus A network port B LED C Reset button D USB terminal E USB reserved F Serial reserved ...

Page 7: ... ENGLISH 7 OPENING THE PACKAGING AND CHECKING THE CONTENTS After opening the packaging first check the contents The packaging should contain NetMan 202 plus USB cable ...

Page 8: ...h it is possible to configure NetMan plus see paragraph Configuration via RS 232 serial line NETWORK SERVICES NetMan plus implements a series of services based on the main network protocols These services can be activated or deactivated according to requirements see paragraph Configuration A brief description for each of these is given below SSH By means of a ssh client available on all the main o...

Page 9: ...e respective access rights The agent can also send messages TRAP without a prior request from the manager to inform the latter of particularly important events SNMPv3 is the evolution of SNMP and introduces new important features related to security See paragraph SNMPv3 UDP UDP User Datagram Protocol is a low level network protocol that guarantees speed in the exchange of data and low network cong...

Page 10: ...th cases a client FTP is required configured with these parameters Host hostname or NetMan plus IP address User see chapter Users Password current password default configuration password The connection can also be established using a web browser all the most popular web browsers are supported by inserting the following address ftp user address NetMan plus where address NetMan plus is replaced with...

Page 11: ...The e mails can be sent to up to three recipients and they can be sent for seven different kinds of alarm SMTP Simple Mail Transfer Protocol is the protocol used to send the e mails They are sent to an SMTP server on port 25 For more details see paragraph Configuration Example of notification e mail ...

Page 12: ...S values and events history log archive This service can be used to periodically save the history log archives The Email service must be enabled in order to send reports the reports are sent to all the addresses configured for this service for more details see paragraph Configuration Example of report e mail ...

Page 13: ...ws the data to be ordered chronologically or by any text editor The format used to record the date and time is of the type MM DD YY HH MM SS Eventlog The Eventlog service is always active and records all relevant UPS events in the event log file The file can be downloaded via FTP or sent by e mail using the Email report service The data are saved in circular list mode thus the most recent data are...

Page 14: ...voltage line 3 Input frequency Output voltage line 1 Output voltage line 2 Output voltage line 3 Load on line 1 Load on line 2 Load on line 3 The interval of time between one recording and the next Log frequency can be configured by the user see paragraph Miscellaneous Menu The data are saved in circular list mode thus the most recent data are saved by overwriting the oldest data Data for up to 25...

Page 15: ...provided by the sensors may also be requested with SNMP according to the RFC 3433 standard The MIB file is inside the bundled CD Available sensors Temperature detects the environmental temperature in C Humidity Temperature detects the relative humidity in and the environmental temperature in C Digital I O Temperature detects the environmental temperature in C and features a digital input and a dig...

Page 16: ...icro USB port with the USB port of the PC execute the software HyperNetman press the Enter key of the PC at the login prompt enter admin at the password prompt enter the current password default configuration admin During password s typing no character is shown Once login has been effected the screen of the start menu is displayed From this screen it is possible to access the various menus to chan...

Page 17: ...ee paragraph Time settings Menu become effective without saving Users It is possible to access to NetMan 202 plus with various users admin password admin user with right to modify the configuration fwupgrade password fwupgrade user with right to upgrade the firmware user password user user with right to read but not modify the configuration and the log Start menu Netman 202 plus Setup View status ...

Page 18: ... to access the various submenus the function of each of which is shown in the table below Menu Function IP config To configure the network parameters Time setting To configure the internal clock UPS config To configure the type of UPS connected Services 1 To activate and or deactivate device services Services 2 Security To configure the password and access to the network Save and load To save a co...

Page 19: ...s entered Esc 1 Exit main menu 2 Return to previous menu 1 Some keys can have a different function depending on the menu 2 To exit from a menu a confirmation Y or N is required after pressing the ESC key The screen also displays some messages describing the kind of configuration data displayed and the status of the UPS The meaning of these messages is described below Data from flash means that the...

Page 20: ... ENGLISH 20 Here is a graphical rapresentation of the menus and submenus ...

Page 21: ...ter the name or the address of the network gateway Primary DNS Enter the name or the address of the preferred DNS to be used Secondary DNS Enter the name or the address of the alternative DNS to be used Mailhost Enter the name or the address of the SMTP server to be used to send e mails 1 1 Ensure that the SMTP server accepts connections on port 25 If a static IP address is assigned to the device ...

Page 22: ... 10 1 4 1 Ethernet Address 00 60 35 02 41 84 Primary DNS 10 1 4 2 Secondary DNS 10 3 4 1 DNS Timeout 0 ms DHCP Server 10 1 5 1 DHCP Enabled true DHCP Lease Ends Sun Jun 05 00 00 12 GMT 2005 66 hr 40 min 38 seconds left Mailhost mymailserver Restore From Flash Not Committed Time setting menu Time setting Set time Set timezone Sync with NTP Scheduled NTP From this menu the time and date of the devic...

Page 23: ...me CET GMT Asia Singapore Etc GMT 4 SystemV HST10 Enter the time zone selected from those shown then press the ENTER key and then ESC to exit Pressing the ENTER key corresponding to the Sync with NTP command displays a screen like the one shown below Current date is Thu Jun 16 14 17 06 ECT 2005 Insert IP Address or host name of the NTP server to synchronize time leg Synchronizing time to server se...

Page 24: ...ming a synchronization For each field is possible to enter the precise condition or leaving which means always On the example above synchronization will be performed every 1st day of month at 13 00 regardless of the day of week Field Parameters to be inserted NTP server Enter the name or address of the NTP server Sync only at h Enter the hour when the synchronization should occur or Sync only at w...

Page 25: ...scribed in the following table for the UPS to be able to communicate correctly with the device Field Parameters to be inserted PRTK Code Enter the PRTK code indicated at the back of the UPS 1 Name Enter the identifying name of the UPS UPS Address Insert 1 Serial number Enter the UPS identification code 1 The PRTK code is formed of 12 alphanumeric characters ...

Page 26: ...the following table Menu Function SNMP config To configure the SNMP service SNMP community Email config To configure the e mail service Email logic Miscellaneous To configure the other options Activation 1 To configure the services to be activated As well as being configured the services must also be activated to function correctly see paragraph Activation menu It is recommended to activate only t...

Page 27: ...to an SNMP manager for alarm notification Traps can be sent to seven different hosts SNMPv1 community menu SNMPV1 community Get community public Set community private Trap community public With this menu the protection password of the SNMP messages SNMP Communities can be configured as described in the following table Field Parameters to be inserted Get community Enter the community for read acces...

Page 28: ...ails are sent 1 Customer Enter an identifying string this additional information is included in the e mail Report interval Enter the delay measured in days between the sending of one report e mail and the next by using exactly 2 figures followed by a line an finally by the hour and minutes on which the email should be sent User name If the server requires authentication insert the User name Passwo...

Page 29: ...nding addresses see Email logic menu to set the addresses 0 when the event occurs NetMan plus does not send a notification e mail to the corresponding addresses The following table describes the meaning of the events These can vary depending on the UPS connected Event Meaning UPS Lock UPS is locked Ovrload Ovrtemp UPS in overload or in overtemperature UPS Failure Failure of the UPS On bypass Opera...

Page 30: ...onfigured as described in the following table Field Parameters to be inserted Log frequency Enter the delay measured in seconds between one data log and the next see paragraph Datalog UDP Port Enter the port where the UDP service is started 1 sysContact Enter the string to be associated with these SNMP variables sysName sysLocation 1 This port must be the same as configured in the UPSMon software ...

Page 31: ... It is recommended to activate only the services used Services 2 menu Services 2 WakeOnLan addr WakeOnLan delay Activation 2 Sensors config I O Sensors Threshold sens With this menu the configuration screens of the various services can be accessed as described in the following table Menù Funzione WakeOnLan addr To configure the Wake on LAN service WakeOnLan delay Activation 2 To configure the serv...

Page 32: ...u is possible to insert up to 8 MAC address to execute Wake on LAN Please make sure that your PC supports this function and that it is correctly configured Wake On LAN delay menu Wake on LAN delay Address 1 delay 2 sec Address 2 delay 40 sec Address 3 delay 2 sec Address 4 delay sec Address 5 delay sec Address 6 delay sec Address 7 delay sec Address 8 delay sec With this menu is possible to insert...

Page 33: ...some instants the device will be recognized and the device will be given an identifier number 1 Connect the next sensor if present and press N After some instants the device will be recognized and the device will be given an identifier number 2 Repeat the procedure for all the sensors and when the configuration is finalized press Y Sensors Devices 1 Sensor Digital I O Temperature 140000009A204C28 ...

Page 34: ...ct the second sensor Humidity Temperature and press N Sensors Devices 1 Sensor Temperature F100000013BE0628 Temperature 2 Sensor Humidity 4D00000083FF3326 Humidity Temperature Press Y to confirm N to insert a new sensor Wait until the second sensor is identified and then connect the third sensor Digital I O Temperature and press N Sensors Devices 1 Sensor Temperature F100000013BE0628 Temperature 2...

Page 35: ...ribes the meaning of the events These can vary depending on the UPS connected Event Description UPS Lock UPS is locked Ovrload Ovrtemp UPS in overload or in overtemperature UPS Failure Failure of the UPS On bypass Operation from bypass Battery work Operation from battery Battery low Battery low Communic lost Communication between the UPS and the device has been interrupted The Input sensor event a...

Page 36: ...active when the outbound value temperature or humidity is under the threshold with the degree of hysteresis that is configured Example with a maximum temperature of 30 C and 3 C hysteresis the alarm is activated when the temperature reaches 30 C and is removed when the temperature at 27 C Menu Significato Temperature max Threshold for maximum temperature Temperature min Threshold for minimum tempe...

Page 37: ...o change the password used for UDP UPSMon communication 2 Firewall To configure access from the network 1 default configuration password 2 this password must be the same as the one used by the UPSMon software Pressing the ENTER key corresponding to the UDP Password command displays a screen like the one shown below Enter the new UDP password Confirm the new UDP password Enter as requested the new ...

Page 38: ...Man plus can be configured The character can be used for one or more fields of the IP address to indicate that all values between 0 and 255 are accepted in that field The following table provides some possible configuration examples IP Access Description All the devices present on the network are enabled to communicate with NetMan plus default configuration 10 1 10 The devices with addresses betwe...

Page 39: ...arts to make the changes effective Revert changes Cancels the changes and reloads the last saved configuration excluding the the clock Time setting configurations Reset default Loads the default configuration 1 see paragraph Configuration of several devices Expert mode Expert mode enables the configuration of advanced parameters that should be set by skilled technicians These commands are supporte...

Page 40: ...l for privacy of this user during SNMP sessions Possible values are nopriv no privacy will be used des DES will be used for privacy authPassword is the password for authentication It must be set to when not used privPassword is the password for privacy It must be set to when not used The correct syntax for addGroup is addGroup securityModel userName groupName securityModel is the security model Wh...

Page 41: ...tch one of the view name The correct syntax for addView is addView viewName subtree mask included viewName is the name of the view subtree is the OID subtree which when combined with the corresponding instance of MASK defines a family of view subtrees mask the mask for filtering OID included the OID can be included or excluded Possible values are included for including excluded for excluding The c...

Page 42: ...HADES Auth protoc ol Noauth md5 Sha md5 Sha Priv protoc ol nopriv nopriv nopriv des des Auth passwo rd MD5UserAuthPassw ord SHAUserAuthPassw ord MD5DESUserAuthPassw ord SHADESUserAuthPassw ord Priv passwo rd MD5DESUserPrivPassw ord SHADESUserPrivPassw ord The SNMP agent will send SNMPv3 trap to address 10 2 10 1 ...

Page 43: ...TP Example of FTP connection for multiple installations MONITORING WITH HTTP The HTTP service uses TLS transport layer security in order to provide cryptographic security However the certificate used is self signed and therefore the web browser may prompt a security alert Once the hostname or the NetMan plus IP address has been inserted in your web browser the following screen will be shown From h...

Page 44: ...ISH 44 View HTTP It is possible to view the status of the UPS without entering the login by pressing View By pressing View a screen like the one shown below will be displayed with the main UPS operating data ...

Page 45: ...wing external sensors It is also possible to download the event log and data log if available from the Log menu Setup HTTP For configuration it will be requested to enter the log in and password These are the same of ssh config and are required to modify the configuration When inserting a valid log in and password is possible to configure the netman ...

Page 46: ...data for the current view is sent to the netman by pressing reset the data for the current view is discarded With HTTP each view is configured separately therefore is required to press submit for each for example when changing device config and ip config is required to press submit on device config and on ip config The changes becomes effective on next reboot ...

Page 47: ...d on the left hand side of the page Nominal Data opens a page displaying the nominal values of the UPS the list of active alarms and a diagram of UPS operation see image on next page FTP opens an FTP session see paragraph FTP About opens a page with copyright information ...

Page 48: ...ction are listed below together with the accessible registers SUPPORTED FUNCTION SUPPORTED FUNCTION FUNCTION DESCRIPTION ACCESSIBLE DATA AREA 1 0x01 BIT READING STATES 2 0x02 STATES 3 0x03 REGISTERS READING ALL 4 0x04 ALL 6 0x06 SINGLE REGISTER WRITING COMMANDS 16 0x10 MULTIPLE REGISTER WRITING COMMANDS ...

Page 49: ...1 YES 32 31 3 2 33 48 32 47 4 3 49 63 48 62 Communication lost with UPS 0 No 1 YES 64 63 5 8 4 7 65 128 64 127 1 The register number n must be addressed n 1 in the data packet 2 The bit number n must be addressed n 1 in the data packet REGISTER 1 UPS MEASUREMENTS UNIT NUMBER ADDRESS 9 11 8 10 12 11 Input mains star voltage V1 V 13 12 Input mains star voltage V2 V 14 13 Input mains star voltage V3 ...

Page 50: ... 1 Hz 45 47 44 46 48 47 Battery voltage 0 1 V 49 48 Positive battery voltage 0 1 V 50 49 Negative battery voltage 0 1 V 51 50 Battery current 0 1 A 52 51 Remaining Battery Capacity 53 52 54 53 Remaining back up time Minutes 55 58 54 57 59 58 Total output energy 32 bit Least Significant Register 0 1 kWh 60 59 Most Significant Register 61 60 62 61 Internal UPS temperature C 63 62 Sensor 1 temperatur...

Page 51: ... Command code 2 Integer 114 113 Shutdown delay time Seconds 115 114 Restore delay time Minutes 116 115 117 116 Command result 3 Integer 118 117 REGISTER 1 DIAGNOSTIC UNIT NUMBER ADDRESS 119 118 Counter of processed correct messages Integer 120 119 Counter of processed NOT correct messages Integer 1 The register number n must be addressed n 1 in the data packet 2 Refer to Command codes paragraph 3 ...

Page 52: ...ode Byte 3 of i xx code Flag 127 126 Byte 1 of a xx code Byte 2 of a xx code Flag 128 127 Byte 3 of a xx code Byte 4 of a xx code Flag REGISTER 1 NETMAN DATA UNIT NUMBER ADDRESS 129 128 Firmware version Integer 130 131 129 130 1 The register number n must be addressed n 1 in the data packet 2 In order to decode these registers please refer to the UPS manual UPS COMMANDS CODES CODE COMMAND 1 0x0001...

Page 53: ...lus firmware can be updated via FTP Connect via FTP with the user fwupgrade password fwupgrade and copy the updated firmware Then restart the card by pressing the reset button or via SSH enter into the menu with user admin and select Save changes ...

Page 54: ...rs of UTP cables of category 5 or higher The cable between the adaptor and the hub must not be more than 100m and not less than 2 5m NETWORK CABLE CONNECTIONS Signal Pin to Pin TX 1 1 TX 2 2 RX 3 3 RX 6 6 Pins 1 and 2 must be connected to one twisted pair pins 3 and 6 to another TECHNICAL SPECIFICATIONS NetMan 202 plus POWER SUPPLY Input voltage Vdc 12 Maximum input current mA 200 ENVIRONMENTAL CO...

Page 55: ...0MNACCSA3ENUC ...

Reviews: