USER’S MANUAL

 

 

On-Line  1K-3KVA 

Uninterruptible Power Supply

 

Summary of Contents for RP-UPH103R

Page 1: ...USER S MANUAL On Line 1K 3KVA Uninterruptible Power Supply...

Page 2: ...CONTENTS 1 INTRODUCTION 1 2 SAFTY INSTRUCTION 2 3 CABLE CONNECTION 4 4 SYSTEM DESCRIPTION 5 5 UPS OPERATION 12 6 TROUBLE SHOOTING GUIDE 18 7 OPERATION MODES OF THE UPS 24 8 COMPUTER INTERFACE 26 1...

Page 3: ...wer factor and DC start function 4 LED and LCD display for detail status and data real time alarm silence 5 Enhanced protections against light surges and disturbance etc 6 Remote monitoring with SNMP...

Page 4: ...o direct sunlight or near heat 4 Do not block off ventilation openings in the UPS system s housing and don t leave objects on the top of the UPS 2 Allow a minimum distance of 10 cm in the rear and two...

Page 5: ...gerous Before carrying out any kind of servicing and or maintenance disconnect the batteries and verify that no current is present 2 Only persons adequately familiar with batteries and with the requir...

Page 6: ...ld you find signs of damage Please keep the packaging in a safe place for future use 4 Please ensure that the incoming feeder is isolated and secured to prevent it from being switched back on again 3...

Page 7: ...e to select upward the UPS status on LCD Display 3 Down key Use to select downward the UPS status on LCD Display Beside press it simultaneously with the Up key to switch off the UPS 4 Enter Key It is...

Page 8: ...ly 4 2 Front Panel Description for LED Module 1 Line LED green To indicate the AC power is applied to the UPS input In case this LED blinks it means the main AC source is out of tolerance 2 Bypass LED...

Page 9: ...of the batteries LEDs light up to indicate the following information No 9 LED 0 25 battery low level No 8 9LEDs 26 50 No 6 7 8 9 LEDs 76 95 No 7 8 9 LEDs 51 75 No 5 6 7 8 9 LEDs 96 100 10 Fault LED r...

Page 10: ...4 3 Outline Description 1KVA Tower Case for LCD LED Model 9...

Page 11: ...2KVA Tower Case for LCD LED Model 10...

Page 12: ...3KVA Tower Case for LCD LED Model 11...

Page 13: ...1K 2K 3KVA Rack Mount for LCD LED Model 12...

Page 14: ...el Please follow the instructions below for UPS operation 1 Once the AC source is connected the LCD Display shall light up immediately to display first the main menu of greeting context and the Normal...

Page 15: ...4 LCD display menu Use Up Down key to select menu displays of the LCD described below This screen will refresh once the system power is enabled Rated Spec Status Voltage Frequency 14...

Page 16: ...Battery Status Output Power Temperature History Record 15...

Page 17: ...o protect the load the function of bypass auto transfer is activated only when the AC main voltage is within the range of LO low and HI high In this screen press Enter key to enter the following steps...

Page 18: ...ate the output voltage and frequency newly selected C Use Up or Down key to adjust the output voltage 220V 230V and 240V Press Enter key to confirm voltage and then the cursor will move to frequency s...

Page 19: ...l light up immediately to indicate ready to switch on the inverter In case this LED blinks it means the main AC source is out of tolerance 2 Press both of the Control Key and the ON TEST MUTE key simu...

Page 20: ...mal UPS is running normally but battery capacity is low referring to Battery Status Menu Buzzer beeps once every second for battery low Charger may break down Please replace charger board 2 AC utility...

Page 21: ...rloaded Warning LED lits up and buzzer beeps per second Please reduce the critical load to POWER 100 4 AC utility power is normal but UPS is overloaded up to 125 Warning LED does not fade out and buzz...

Page 22: ...Warning LED lits up and buzzer beeps continuously Please reduce the critical load to POWER 100 6 AC utility power fails The full load is supplied by battery power in UPS Buzzer alarm sounds every 4 se...

Page 23: ...hing low level Buzzer alarm beeps every second UPS will shut down automatically Please save data soon 8 AC utility power fails and battery runs out UPS has shut down automatically UPS will restart up...

Page 24: ...its up and buzzer beeps continuously Please contact your agent for service 3 AC utility power is normal but UPS is overloaded Warning LED lits up and buzzer beeps per second Please reduce the critical...

Page 25: ...please check the rated input or connected line 7 AC utility fails UPS is in battery backup mode and battery power is approaching low level Buzzer alarm beeps every second UPS will shut down automatica...

Page 26: ...is normal the AC loop and the battery charging loop The AC output power comes from AC utility input and passes through AC DC rectifier DC AC inverter and static switch to support power to load The ba...

Page 27: ...tput comes from battery passing through DC AC inverter and static switch within the battery backup time 7 4 Bypass Enable Under the following conditions the bypass will be enabled 1 Overload 2 Inverte...

Page 28: ...method the user is able to monitor the following parameters Input Voltage Indicates the present input voltage to the UPS system when AC power is present Output Voltage Indicates the present output vo...

Page 29: ...28...