background image

The Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model F1S5 Series

Special Response 

Standard Spray

Model F1S5-56 Sprinkler

Standard Upright (SU)
Standard Pendent (SP)
Conventional (C u/p)

Model F1S5 LO Large Orifice Sprinkler 

with 

1

/

2

” Connection Threads

Standard Upright (SU)
Standard Pendent (SP)

Model F1S5-56 Recessed Sprinkler

Standard Pendent
w/F1, F2 and FP Recessed Escutcheon

Model F1S5 LO Large Orifice Recessed 

Sprinkler with 

1

/

2

” Connection Threads

Standard Pendent
w/F1, F2 and FP Recessed Escutcheon

Approvals

VdS Schadenverhütung GmbH

•  SP K80 - Certificate G4080043, EC Certificate 

0786-CPD-40238

•  SU K80 - Certificate G4990035, EC Certificate 

0786-CPD-40143

•  C u/p K80 - Certificate G4050047, EC Certificate 

0786-CPD-40147

•  Recessed SP - Certificate G4080045, EC Certificate 

0786-CPD-40240

•  SP K115 - Certificate G411005
•  SU K115 - Certificate G411006

Product Description

The F1S5 Series Glass Bulb Sprinkler combines the 

durability of a standard sprinkler with the attractive low profile 
of a decorative sprinkler. Whether installed on exposed piping 
or in an office ceiling, it is functional and attractive. 

Beautifully versatile is the description for the Reliable Model 

F1S5 Series Recessed glass bulb sprinkler. Recessing the 
F1S5 Series enhances its already low profile decorative 
appearance and facilitates a rapid and perfect installation.

Model F1S5 Series Recessed escutcheon is highly 

adjustable. The two piece construction makes field 
installation a very easy and rapid task. This also allows ceiling 
panels to later be removed without shutting down the fire 
protection system, thus facilitating maintenance of above 
ceiling services.

F1S5 Pendent

F1S5 Conventional

Recessed Pendent/F1/F2

F1S5 Upright

Recessed Pendent/FP

F1S5 LO Pendent

F1S5 LO Upright

Multilingual document:  

Select your language below

Bulletin 024 Rev. A_Multilingual

Bulletin 024 Rev. A_Multilingual

Summary of Contents for F1S5 Series

Page 1: ...SU K115 Certificate G411006 Product Description The F1S5 Series Glass Bulb Sprinkler combines the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler Whether installed on exposed piping or in an office ceiling it is functional and attractive Beautifully versatile is the description for the Reliable Model F1S5 Series Recessed glass bulb sprinkler Recessing t...

Page 2: ... to shatter opening the waterway and allowing the deflector to distribute the discharging water The F1S5 Series Sprinkler temperature rating is identified by the color of the glass bulb capsule as well as frame color where applicable F1S5 LO Pendent F1S5 LO Upright Model F1S5 56 Upright Pendent and Conventional Sprinklers Model F1S5 LO Upright and Pendent Sprinklers Installation Wrench Model D Spr...

Page 3: ...ler Height Sprinkler Identification 1 RTIc fts1 2 ms1 2 US Metric 1 2 15 mm 1 2 NPT R1 2 5 6 80 2 25 57 mm SP 2 110 150 60 80 Model F1S5 Large Orifice Recessed Pendent Sprinklers 3 90 150 50 80 20 mm R1 2 8 0 115 58 mm SP 1 c 1 09 ft s 1 2 0 60 m s 1 2 2 VdS Approval for 155 F 68 C 175 F 79 C and 200 F 93 C only 3 Currently not VdS Approved other recessed escutcheon will void all approvals and neg...

Page 4: ...off Max Recessed Min Recessed 7 16 11 mm 15 16 24 mm 11 2 38 1 mm 1 25 mm Maintenance The Models F1S5 56 F1S5 LO F1S5 56 Recessed and F1S5 LO Recessed Sprinklers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25 Do not clean sprinklers with soap and water ammonia or any other cleaning fluid Remove any sprinkler which has been painted other than factory ap...