background image

  

THREE JUMPER SELECTABLE INPUT RANGES

  

OUTPUT IS MAGNETICALLY ISOLATED FROM THE INPUT

  

INTERNAL POWER REGULATION

  

SPLIT-CORE CASE FOR EASY INSTALLATION

GENERAL DESCRIPTION

CTD transducer combines a Hall Effect sensor and a signal conditioner into a 

single package. This provides higher accuracy, lower wiring costs, easier 

installation and saves valuable panel space. The CTD has jumper selectable 

current input ranges and industry standard 4-20 mA output with a split-core case.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the 

literature or on equipment must be observed to ensure personal safety and to 

prevent damage to either the instrument or equipment connected to it. If 

equipment is used in a manner not specified by the manufacturer, the protection 

provided by the equipment may be impaired.

Do not use this unit to directly command motors, valves, or other actuators 

not equipped with safeguards. To do so, can be potentially harmful to persons or 

equipment in the event of a fault to the unit.

SPECIFICATIONS

1. 

OUTPUT SIGNAL

: 4-20 mA

2. 

OUTPUT LIMIT

: 23 mA

3. 

ACCURACY

: 1.0% FS

4. 

REPEATABILITY

: 1.0% FS

5. 

RESPONSE TIME

: to 90% of step change 100 msec

6. 

FREQUENCY RANGE

: DC

7. 

POWER SUPPLY

: 22 – 26 VAC/VDC, 50 – 60 Hz

Power input and output signal are not isolated.

24 VDC powered device: A fuse rated a maximum of 5 A shall be placed in 

series with the main input power terminal.

24 VAC powered device: A fused rated a maximum of 2.75 A shall be placed 

in series with the main input power terminal.

Copper busbars shall be sized at 1000 Amperes per square inch.

8. 

POWER CONSUMPTION

: 2 VA

9. 

LOADING

: 650 

 max.

10. 

ISOLATION VOLTAGE

: 3 kV (monitored line to output)

11. 

LINEARITY

: 0.75% FS

12. 

CURRENT RANGES

: Three selectable Ranges: 0 – 50 A

   

0 – 75 A

   

0 – 100 A

13. 

CASE

: UL 94V-0 Flammability rated thermoplastic

14. 

ENVIRONMENTAL

: -4 to 122 °F (-20 to 50 °C)

0-95% RH, non-condensing

Altitude: Up to 2000 meters

Installation Category II, Pollution Degree 2 as defined in IEC/EN 60664-1.

CAUTION: Read complete 

instructions prior to installation 

and operation of the unit.

CAUTION: Risk of electric shock.

WARNING - EXPLOSION HAZARD - DISCONNECT POWER 

AND ENSURE THE AREA IS KNOWN TO BE NON-HAZARDOUS 

BEFORE SERVICING/ REPLACING THE UNIT AND BEFORE 

INSTALLING OR REMOVING I/O WIRING.

MODEL CTD - DC CURRENT TRANSDUCER

Bulletin No.  CTD-B
Drawing No.  LP0654
Released  11/19

Tel +1 (717)767-6511
Fax +1 (717) 764-0839
www.redlion.net

0.85

(21.7)

2.25

(57.2)

1.18

(30)

0.45

(11.4)

Ø 0.19

(4.8)

0.85

(21.6)

3.53

(89.7)

3.04

(77.2)

2.40

(61)

DIMENSIONS  In inches (mm)

Reviews: