Installation

The RCI 10 Series are for use in a controlled

environment.

Installation must be in accordance with all

electrical building and fire codes. Check with the

Authority Having Jurisdiction (AHJ) prior to installation.

The RCI 1012 and 1024 supply solid state regulated DC

power.

Features

Filtered Output Voltage

Maximum AC ripple at full load .280vrms

97.5% Regulation

Short Circuit Protection

The short circuit protection relay prevents damage to

the power supply board in the event of a short circuit.

Fuse Protection

The power supply board and transformer are protected

by a 1 Amp fast blow fuse located on the Printed

Circuit Board.

LED

The green indicator lamp on the cover indicates the

presence of AC voltage.

Provisions for External Fire Panel Contacts, Reset

Contacts and Manual Override Switch.

Options:

Battery Backup, Timer Modules

Cabinet Mounting

Four keyholes are provided on the back of the power

supply cabinet for mounting.

Wiring

- AC power connection to the power supply is made to

the primary transformer leads as shown in Fig. 1 and 2.

- With NR models, the external load (ie. magnetic lock or

strike) is connected to TB1-1 (negative) and TB1-2

(positive).

- For the FPD model connection of an external reset

switch, fire panel disconnect switch, or manual override

switch refer to the separate PDD-FT installation

instruction application diagrams

2-Year Limited Warranty

We will guarantee our products to the original purchaser

against defects in workmanship, materials or operation

subject to ordinary wear and tear as it pertains to

particular installations, No unauthorized person may

attempt repair or tamper with the product.

We assume no liability for consequential or indirect loss

or damage to persons or property as a malfunction or

non function of this product.

We will not warrant against defects due to improper

installation or for uses that our products are not intended.

Our only liability under this warranty is to repair, replace

or refund the original purchase price of the product which

has been returned to us with prior authorization and proof

of purchase. No other guarantee is authorized by or on

behalf of Rutherford Controls Int’l Corp.

Troubleshooting
Problem

No DC voltage

Possible Cause Absence of AC power input to supply

Solution

Turn breaker on

Possible Cause PDDFT N/ON not energized

Solution

Reset power supply

Possible Cause Negative side of power supply not

reaching relay

Solution

Check external switch wiring

Possible Cause Blown Fuse

Solution

Replace 1 Amp Fuse

Problem

AC indicator light will not stay on

Possible Cause Absence of AC power input to supply

Solution

Turn breaker on

Problem

Low voltage at electric lock

Possible Cause Voltage drop in cabling

Solution

Ensure that wire runs use appropriate

cable gauge

©2011 RUTHERFORD CONTROLS INT’L CORP. WWW.RUTHERFORDCONTROLS.COM

USA: 2517 SQUADRON COURT, SUITE 104, VIRGINIA BEACH, VA 23453 

 CANADA: 210 SHEARSON CRESCENT, CAMBRIDGE, ON  N1T 1J6 

PHONE 

 1.800.265.6630 

 519.621.7651 

 FAX: 1.800.482.9795 

 519.621.7939 

 E-MAIL: [email protected] 

ISPS10-1A

PCN110045

R07/11SH

I N S T A L L A T I O N

10 Series Power Supplies

Models 1012 & 1024

®

No Relay

With Fire Panel Disconnect

Model

1012NR-1A

1024NR-1A

1012FPD-1A

1024FPD-1A

Power Input

120V, 60Hz

Current Output

600 mA, 40VA

775 mA, 40VA

600 mA, 40VA

775 mA, 40VA

Voltage

12VDC

24VDC

12VDC

24VDC

* UL Tested @ 0.6 p.f.