10-175UL

Access Control Power Supply/Charger 

Installation and Specifications Manual

®

10-175UL 

Power Supply

I N S T A L L A T I O N

Summary of Contents for 10-175UL

Page 1: ...10 175UL Access Control Power Supply Charger Installation and Specifications Manual 10 175UL Power Supply I N S T A L L A T I O N ...

Page 2: ...t of Buildings 18 98 E NFPA 101 Life Safety Input 115VAC 60 Hz 6 amps Switch selectable 12VDC or 24VDC power limited output 1 75 amps continuous supply current 12VDC or 24VDC Latching fire alarm tie in with manual reset Filtered and electronically regulated output Charge current 0 4 amps Max Aux relay output form C 1 amp 28VDC AC Fail output relay form C 1 amp 28VDC Enclosure Dimensions 15 5 H x 1...

Page 3: ...series for 24VDC operation Note For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries are desired they must be lead acid or gel type 5 Connect appropriate signaling notification devices to AC Fail supervisory relay outputs marked N C N O C Note To meet UL requirements AC Superviso...

Page 4: ... dry Form C contacts Shorting TRG1 and TRG2 together causes these contacts to switch They are typically used for controlling mul tiple 10 175ULs with fire alarm tie in Fig 4 and Fig 5 pg 7 8 AUX Continuous positive DC power output voltage It is not affected by TRG1 TRG2 operation COM Common negative output ground FACP Spare wiring terminal used for fire alarm tie in application Fig 1 pg 6 BAT BAT ...

Page 5: ...2 SW1 CLOSED 24V OPEN 12V NC C NO AC FAIL XFMR Green Lead ground Stand by Battery optional Constant output not affected by trigger Switched DC output trigger control Black Lead White Lead 115VAC input 60 Hz 6 amps AC DC JUMPER Reset Switch AC Power LED AC Molex Connector 5 ...

Page 6: ...m 4 50 114 3mm 1 50 38 1mm 4 50 114 3mm 4 50 114 3mm 1 50 38 1mm 1 25 31 8mm 1 25 31 8mm 4 50 114 3mm 0 94 23 8mm 0 88 22 2mm 0 88 22 2mm 9 88 250 8mm 12 00 304 8mm 15 50 393 7mm Enclosure Dimensions FIG 1 Typical mag lock with fire alarm tie in using aux output installation FIG 2 Multiple 10 175 power supply connections 6 ...

Page 7: ... Typical Single Mag lock or door strike installation with fire alarm tie in using trigger controlled output FIG 4 Typical dual mag lock installation with fire alarm tie in using trigger controlled outputs 7 ...

Page 8: ...om terminals Output voltage is not correct for the con nected equipment Trouble output relay is de energized Relay terminals are labeled shown in the Normal energized no trouble condition Relays are energized when no trouble is detected For Technical Support 1 800 265 6630 or 519 621 7651 www rutherfordcontrols com 2007 RUTHERFORD CONTROLS INT L CORP WWW RUTHERFORDCONTROLS COM USA 2697 INTERNATION...