background image

ANTI TAMPER SCREWDRIVER 
 
Each of the Cig-Arrête Smoke Detectors can be fixed 
securely in its base using the Anti-tamper screwdriver 
(part number CSA-ATS) to lock the sensor in its base. 
This will prevent any unauthorised removal of the 
detector.. Do not over-tighten the screw as this may 
cause the detector head to jam in its base! 
 
SITING OF DETECTORS 
 
When installing your Cig-Arrête Smoke Alarm, it is 
important that you plan the location of each of the Cig-
Arrête Smoke Detectors to optimise the performance of 
your system. We suggest that for example, when 
installing in a toilet area, each trap is fitted with its own detector, so that individual alarms can be 
identified easily. 
 
Never install the detectors next to an atomiser type air freshener, or in a location that may be 
subject to wind speeds in excess of 5 metres per second. Remember that the alarm is a highly 
sensitive piece of equipment, and as such performs better in a clean, calm atmosphere at high 
sensitivities. You can of course reduce the sensitivity settings as described overleaf should you 
find that unwanted alarms are being reported due to excessive air movement. 
 
 
DETECTOR CAGES 
 
Should you require additional protection for your Cig-
Arrête Anti-Smoking Alarm System, you may wish to 
purchase Anti-Vandal Cages (Part No CSA-AVC). The 
cages are made from high grade steel painted with a 
high gloss white powder coating to ensure aesthetic 
appearance in all applications 
 
Any enquiries regarding the installation of the Cig-Arrête 
Smoke Alarm or other Radal products can be made by 
telephoning the number, or writing to the address given 
below. 
 
Radal Technology Limited 
Customer Care Services 
Unit 1, Webber Court, Billington Road 
Burnley 
Lancashire 
England BB11 5UB 
Tel: +44 (0) 1282 463 770 
Fax: +44 (0) 1282 463 771 
 
INSTALLATION GUIDES AND PRODUCT SPECIFICATIONS MAY BE 
DOWNLOADED FROM :               

WWW.RADALTECHNOLOGY.COM

 

 

Smoke-free Alarm Systems made simple! 

 
 

Cig-Arrête Anti-Smoking Alarm Installation Guide 

 

PLEASE READ THIS GUIDE CAREFULLY BEFORE INSTALLING YOUR ALARM.  
 

THIS GUIDE IS PREPARED FOR THE FOLLOWING PRODUCTS & MAY BE DOWNLOADED 
IN ADOBE PDF FORMAT AT  

WWW.RADALTECHNOLOGY.COM

 

 

CSA-S5B, CSA-S5BAR,  CSA-FUV,   CSA-SGA,  SDI-01D,  CSA-ATS 

 

We would suggest the use of security type multi-core cable to install your Cig-Arrête Smoke 
Alarm System. The number of cores required will be dependent on your particular system. For 
example to install five detectors, a proprietary 8-core cable would be sufficient.  
 
1. 

In order to open the Cig-Arrête Main Controller, (part no. CSA-S5B) use a screwdriver to 

depress the plastic locking pins as shown in the diagram below. As the locking pins are 
depressed, slide the front cover carefully toward you, away from the back-plate. 
  

2. 

Once you have removed the front cover, you 

can disconnect the ribbon cable that connects the 
front and back printed circuit boards. Be sure that 
you re-attach the ribbon cable in the same way 
that it was supplied. 
 
3. 

Fix the bracket to the wall using suitable 

screws. The back-plate can then be fixed onto the 
bracket by sliding it on in the direction indicated.  

 
4.  Connect the cables from the as shown 
overleaf. If you are not installing the 
maximum five Detectors to your system, 
remember to include shorting links between 
Terminal ‘C’ and whichever inputs (D1 to D5) 
that you are not using, Otherwise those 
particular zones will be in a permanent fault 
condition, flashing yellow on the controller 

fascia. 

 
5.

 

Please note that if you have purchased the auto-reset controller (Part No CSA-S5BAR) 

then the reset and silence buttons will still be operable, but manual intervention will not be 
necessary. On receipt of an alarm condition, the auto-reset controller will sound an alarm 
condition for 30 seconds and then automatically silence and reset the Cig-Arrête system. 
 
6. 

Once the cabling is completed and checked, you can insert 4 ‘D’ Cell batteries into the 

battery box located on the back-plate of the controller. BE SURE TO OBSERVE THE CORRECT 
POLARITY! The batteries can then be held in place by means of the Velcro strip supplied. Re-fit 
the ribbon cable to the terminal printed circuit board, observing the correct polarity, and slide the 
front cover of the controller over the back-plate until the locating pins snap into position. The 
installation is now complete! 
 

 
 
 
 

 

 