Installation, Operation and Maintenance Instructions

– Read and Save These Instructions –

This manual is provided to acquaint you with 
the dehumidifier so that installation, operation 
and maintenance can proceed successfully. 
Ultimate satisfaction depends on the quality 
of installation and a thorough understanding 
of this equipment. The dehumidifier is built 
around tested engineering principles and has 
passed a thorough inspection for quality of 
workmanship and function.

Quest DRY 150

Installation, Operation and Maintenance Instructions

4201 Lien Rd 

Phone 608-237-8400

Madison, WI 53704 

Toll-Free 1-800-533-7533

www.QuestProtect.com [email protected] 

– Read and Save These Instructions –

Specifications subject to change without notice.

TS-397

04/12

1

Quest DRY  115

Quest DRY 115:

•  Low dewpoint operation
•  115 Pints/Day @ AHAM
•  Wide operating range
•  22 Amps total power consumption
•  Factory installed 115VAC power cords  

(2 required @ 15 Amps each)

•  Simple ON/OFF operation with available  

low voltage control kit for remote/
dehumidistat operation

•  Vertical or horizontal operation
•  Multiple ducting options

Water Removal Rates (Pints/Day) 

 

56 Pints   

100°F, 20% 

160 Pints  

90° F, 90% 

135 Pints  

80° F, 80% 

115 Pints  

80° F, 60% (AHAM)

 

115 Pints  

70° F, 80% 

105 Pints  

70° F, 60% 

105 Pints  

60° F, 80% 

100 Pints  

60° F, 60% 

110 Pints  

50° F, 80% 

90 Pints   

50° F, 60% 

25 Pints   

10° F, 80%

quest

quest

Summary of Contents for DRY 115

Page 1: ...0 Madison WI 53704 Toll Free 1 800 533 7533 www QuestProtect com sales QuestProtect com Read and Save These Instructions Specifications subject to change without notice TS 397 04 12 1 Quest DRY115 Quest DRY 115 Low dewpoint operation 115 Pints Day AHAM Wide operating range 22 Amps total power consumption Factory installed 115VAC power cords 2 required 15 Amps each Simple ON OFF operation with avai...

Page 2: ...tion 5 2 1 Electrical Requirements 5 2 2 Inside Drying Space with 5 Single Reactivation Outlet Duct 2 3 Inside Drying Space with 5 Isolated Reactivation Outlet Duct 2 4 Outside Drying Space 5 3 Operation 5 4 Maintenance 5 5 Wiring Diagram 6 6 Service Parts List 7 Warranty 8 Serial No __________________________________ Purchase Date ______________________________ Dealer s Name _____________________...

Page 3: ...following cautions in mind The Quest DRY 115 is designed to be installed INDOORS ONLY If used near water the unit should be plugged into GFCI circuits DO NOT use the Quest DRY 115 as a bench or table Avoid discharging the process air directly at people Reactivation outlet air MUST be discharged into a location that can tolerate high temperature moist air If the reactivation outlet ductwork passes ...

Page 4: ...vation Duct 6 Start collars included Process Duct 8 Start collars included Range 10 F to 140 F Warranty 1 Year Parts and Labor Low temperature performance is dependent on reactivation air source Supplying warmer reactivation air will significantly increase water removal Dimensions Unit Shipping Width 20 25 Height 36 47 Depth 20 24 Weight 105 Lb 125 Lb Accessories 4026859 6 Metalized Polyester Flex...

Page 5: ... be ducted out of and back into drying space Works well if drying space is too small for mounting unit inside Reduces heat load on drying space 3 Operation The Quest DRY 115 comes complete and can be plugged in and turned on Connected this way the Quest DRY 115 will run continuously With the addition of a high or low voltage humidistat or a duty cycle timer the ON OFF switch will act as an overrid...

Page 6: ...1 800 533 7533 Quest DRY 115 Installation Operation and Maintenance Instructions 6 www QuestProtect com sales QuestProtect com quest quest 5 Wiring diagram ...

Page 7: ...SKID 18 4032315 CORD 2 PLACES Not 4026922 GASKET AND BELT REPLACEMENT KIT Shown 16 15 18 1 800 533 7533 Quest DRY 115 Installation Operation and Maintenance Instructions www thermastor com sales questprotect com quest Asset Protection and IAQ Solutions quest 9 0 8 5 6 Service Parts List Item Part No Description 1 4025076 FAN MOTORIZED IMPELLER PROCESS AIR 2 4025224 CAPACITOR RUN 15 MFD 370V DRY PR...

Page 8: ...reezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC reasonable control Limitations and Exclusions If any Quest DRY 115 Dehumidifier part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto but all warranty periods will be extende...

Reviews: